Download Print this page

Price DFE Series Manual page 4

Exposed displacement diffuser

Advertisement

EXPOSED DISPLACEMENT DIFFUSER
INSTALLATION INSTRUCTIONS
DFE NO DUCT COVER
1.
Remove trim cover (Item 4) by putting finger in opening
(Section E-E) at bottom and pulling slowly to prevent
bending of trim piece. Keep close for use in final step of
installation.
2A. Mounting angles are shipped attached to the diffuser.
Remove two screws holding the mounting angle to corner
extrusion (Section E-E).
2B. Locate and install 1" x 1" x .100" mounting angles to
the wall in desired location. The mounting angles shall be
installed perpendicular to the floor as per Figure 1 and
spaced apart as per dimension given in Table 2. Failure to
position angles upright and perpendicular to the floor will
result in poor installation. Fasteners supplied by others.
FIGURE 9
2
Section E-E
1
E E
FRONT
E E
FIGURE 11
WALL BY OTHERS.
SHOWN AS REFERENCE ONLY.
SIDE
3
EXPOSED DISPLACEMENT DIFFUSERS - Manual | priceindustries.com
Section E-E
5
4
1
WALL BY OTHERS.
SHOWN AS REFERENCE ONLY.
TOP
NO DUCT COVER
NO DUCT COVER
3.
Attach duct to diffuser inlet.
4.
Install diffuser (Item 2) over the mounting angle so that
the back of the diffuser is flush with the wall (Figures 10 &
11). Fasten to mounted angles with screws (Item 5). Use
minimum 2 screws per side of diffuser.
5.
Tap trim cover into place with rubber mallet or neoprene
hammer. Care should be taken not to mark/damage trim
cover, diffuser or surrounding wall.
6.
Reinstall base cover if required.
READ INSTRUCTIONS COMPLETELY BEFORE STARTING
FIGURE 10
5
4
TOP
2
FRONT
E E
WALL BY OTHERS.
SHOWN AS REFERENC
SIDE
Section E-E
1

Advertisement

loading