Download Print this page

Power Supply Specification; Environmental Specifications For Product; Digital Input (Di) Specification; Digital Output (Do) Specification - Haiwell H Series User Manual

Programmable logic controller

Advertisement

www.haiwell.com
3.

Power Supply Specification

Item
Power Supply Voltage
Power Supply Frequency
Power Consumption
Instantaneous Surge
Power Loss Time
Fuse
5V Output Voltage (for CPU)
24V Output Voltage (for output and extension)
24V Output Voltage (for input and peripheral)
Insulation Type
Power Protection
4.

Environmental specifications for Product

Item
Temperature/Humidity
Vibration Resistance
Impact Resistance
Interference Immunity
Over Voltage Resistance
Insulation Impedance
Ground
Operating environment
5.

Digital Input (DI) Specification

Item
Input Signal
Action driving
Input Impedance
Maximum Input Current
Reaction Time
Insulation Type
Input Indication
Power supply
6.

Digital Output (DO) Specification

Item
Resistive Load
Maximum load
Inductive Load
Lamp load
Minimum Load
Voltage Specification
Drive Capability
Reaction Time
Insulation Type
Output Indication
Power Supply
AC Power Supply
100~240VAC
50~60Hz
25VA MAX
20A 1.5ms MAX @220VAC
20ms or less @220VAC
2A, 250VAC
5V, -2%~+2%, 1.2A MAX
24V, -15%~+15%, 500mA MAX
24V, -15%~+15%, 300mA MAX
Transformer isolation or optoelectronic isolation
,1500VAC/1 minute
DC24V output over current
Operating temperature:0~+55℃ Storage temperature:-25~+70℃ Humidity: 5~95%RH, No condensation
10~57 HZ, amplitude=0.075mm, 57HZ~150HZ acceleration=1G, 10 times each for X-axis, Y-axis and Z-axis
15G, duration=11ms, 6 times each for X-axis, Y-axis and Z-axis
AC EFT:±2500V
Surge:±2500V
1500VAC/1min between AC terminal and PE terminal, 500VAC/1min between DC terminal and PE terminal
≧5MΩbetween AC terminal and all input/output points to PE terminal @500VDC
The third kind of grounding(Connecting to the ground of high voltage system is prohibited)
Avoid dust, moisture, corrosion, electric shock and external shocks
No voltage contact or NPN/PNP
ON>3.5mA
OFF<1.5mA
Input Impedance≈4.3KΩ
10mA
6.4ms DEFAULT, can be configured to 0.8~51.2ms
Optoelectronic isolation for each channel
LED's lighting indicates ON, no light indicates OFF
MPU internal power supply:DC power supply (SINK or SOURCE) 5.3mA@24VDC
Output point type : Relay - R
2A/1 point, 8A/4 points COM
50VA
100W
10mA
Below 250VAC, 30VDC
Maximum contact capacity: 5A/250VAC
Off→On 10ms, On→off 5ms
Mechanical isolation
LED's lighting indicates ON, no light indicates OFF
MPU internal 24VDC power supply
Haiwell PLC - H/N series PLC MPU user manual
DC24V
——
——
20A 1.5ms MAX @24VDC
10ms or less
2A, 250VAC
5V, -2%~+2%, 1.2A MAX
24V, -15%~+15%, 500mA MAX
Use external 24VDC power supply
No Electrical isolation
DC input power polarity reverse, over voltage
Environment Specification
DC EFT:±2500V
Digital Input (DI)
4 / 6
DC Power Supply
-15%~+20%
Surge:±1000V
NPN or PNP transistor output T/P
0.5A/1 point, 2A/4 points COM
5W/DC24V
12W/DC24V
2mA
30VDC
1A MAX, 10 seconds
Off→On 10μs,On→Off 120μs
Optoelectronic isolation for each channel

Advertisement

loading

This manual is also suitable for:

N seriesH16s0r-eH16s2r-eH16s2rH16s0rH16s0t/p-e ... Show all