Check valve, port size 13 - 100mm 1/2"-4" for ammonia, r12, r22, r502 and other common refrigerants

Advertisement

Quick Links

CHECK VALVE
Type CK4A, CK4A-DN
Port Size 13 - 100mm (1/2" - 4")
FOR AMMONIA, R12, R22, R502
AND OTHER COMMON REFRIGERANTS
FEATURES
• UL Listed (Thru 3" Size)
• Installs in any position
• Compact
• Lightweight
• In-Line
• Design Pressure (PS): DN 13-25 34.5 bar (500 psi)
• Design Pressure (PS): 34.5 bar (500 psi)
• Complies with Pressure Equipment Directive 97/23/EC
• Complies with Pressure Equipment Directive 97/23/EC
Description
These compact valves are spring closing with a lapped,
stainless steel or chrome plated seat for positive closing
action and low leakage. A minimum pressure difference of
0.05 bar (0.75 psi) is required to hold the valve in the open
position. Removable seat plate with combination O-ring and
metal-to-metal knife edge seal allows the valve to be
disassembled for maintenance. They may be ordered with
male adapter rings for close-coupling to other Refrigerating
Specialties valves and may be installed in any position.
Refrigerating Specialties Division
310230
32 bar (460 psi)
DN 32-100 32 bar (460 psi)
• Complies with Pressure Equipment Directive 97/23/EC
Fig. 1
BULLETIN 50-16
Type CK4A-DN
February, 2002
Installation and Service Information
Purpose
The Type CK4A Check Valves prevent backward flow of fluid
in refrigerant suction, hot gas or liquid lines. The most frequent
use for these valves is in recirculating (overfeed) systems.
They are especially suited for high speed compressor
discharge, pump discharge, suction - down to -50°C (-60°F)
and hot gas lines (pan to evaporator).
Certain refrigerant flows pulsate sufficiently or with a
frequency in harmony with the valve's natural frequency,
which can cause "slapping" or even wholesale failure. These
valves are not recommended for slow speed compressor
discharge lines (See CK-1, Bulletin DN50-10) or for any
compressor discharge where a low speed machine
discharges into the same downstream header, or for use on
side-port suction lines on a screw compressor installation.
Operation
These are light spring-closing check valves. An increase in
the pressure drop across the valve overcomes the force of
the closing spring and the disc is forced away from its seat
permitting flow. As the flow decreases, the disc is forced
back against its seat by the expansion of the closing spring.
Flow is then stopped.
Installation
Keep dirt from entering the valve. Do not remove protective
packaging until ready to install.
Install the valve where it can be serviced easily. DO NOT
INSTALL AT THE INLET OF A SOLENOID VALVE, OR A
REGULATOR WITH AN ELECTRIC SHUT-OFF FEATURE; DO
NOT INSTALL AT THE INLET OF AN OUTLET PRESSURE
REGULATOR IN A SYSTEM WHERE LIQUID MAY BE
TRAPPED BETWEEN TWO VALVES. Check Valves when used
with such valves should always be installed at the outlet of
the valves.
NOTE: THE ODS COPPER FLANGES AVAILABLE ARE ONLY
FOR INSTALLATIONS WHERE R-12, R-22, AND R-502 OR
OTHER HALOCARBON REFRIGERANTS ARE USED. DO
NOT USE THESE FLANGES FOR AMMONIA. FOR
INSTALLATIONS USING AMMONIA THE FPT, SOCKET WELD
OR WELD NECK FLANGES SHOULD BE USED.
The Type CK4A Valves may be installed in any position. The
valve must be installed with the arrow pointing in the direction
of flow. After installing the valve, tighten the flange bolts evenly.
The CK4A Check Valves may be closed-coupled to
Refrigerating Specialties Refrigerant Valves and most hand
valves by using a Refrigerating Specialties Male Adapter Ring.
1
I S O
9 0 0 1
C E R T I F I E D

Advertisement

loading

Summary of Contents for Parker CK4A-DN

  • Page 1 CHECK VALVE BULLETIN 50-16 Type CK4A-DN Type CK4A, CK4A-DN Port Size 13 - 100mm (1/2” - 4”) FOR AMMONIA, R12, R22, R502 AND OTHER COMMON REFRIGERANTS FEATURES • UL Listed (Thru 3" Size) February, 2002 • Installs in any position Installation and Service Information •...
  • Page 2 For replacement parts and prices, consult PARTS KITS LIST PRICE SCHEDULE INDUSTRIAL AND FLO-CON (PK) CK4A 1-1/4" TO 4" PRESSURE BEARING COMPONENTS ITEM DESCRIPTION COMPONENT DESCRIPTION MATERIAL Gasket, Flange CASTING,BODY 1-1/4 CK4A DN DUCTILE IRON GGG 40.3 SEAT,VALVE 1-1/4, 2-1/2 & 3" CK4A BAR,RD 2.687 STL 1213 Valve Seat...
  • Page 3 Type CK4 – 1/2" thru 1-1/4" Type CK4 – 2" thru 4" Refrigerating Specialties Division...
  • Page 4 Refrigerating Specialties option, free of charge, F.O.B. Parker Hannifin Corporation • Refrigerating Specialties Division 2445 South 25th Avenue • Broadview, IL 60155-3891 USA Telephone: (708) 681-6300 • Fax (708) 681-6306...

This manual is also suitable for:

Ck4a