Certifications; Ul 61800-5-1; Rohs; Fuse Selection - bonitron M3545P Reference Manual

Regenerative dc bus power supply
Table of Contents

Advertisement

M3545P
C
6.4.
ERTIFICATIONS

UL 61800-5-1

6.4.1.
All M3545P models are UL Listed under this standard. UL file number E204386.
The M3545P regenerative power supply has a Short Circuit Current Rating (SCCR) of
65kA when protected by proper fusing. See Table 6-4 for required ratings and
recommendations.
R
6.4.2.
All M3545P models are in compliance with Directive 2011/65/EU of the European
Parliament and of the Council of 8 June 2011 on the restrictions of the use of certain
hazardous substances in electrical and electronics equipment (RoHS Directives).
F
S
6.5.
USE
ELECTION
Blown fuses typically indicate a semiconductor device failure or a severe transient. In
any case, blown fuses should not be replaced without first consulting Bonitron as
catastrophic damage can occur.
Use Table 6-3 when initially constructing the system.
AC L
DC L
28
HS
O
Table 6-4: Fuse Current Rating Requirements
C
URRENT
R
ATING
20A
INE
20A
INK
V
R
OLTAGE
ECOMMENDED
R
F
ATING
USE
600VAC
A60Q20-2
700VDC
A70QS20-14F