W
3.4.
IRING AND
All power and user I/O wiring connections are brought out to the terminal block in the
front face of the unit; there should be no need to open the chassis during installation.
Be sure to review all pertinent AC drive and system documentation as well as the
information listed below before proceeding. Connection points and terminal numbers
of the AC drive will be found in the documentation provided with those units.
See Tables 3-1 and 3-2 and Figures 3-2 through 3-5 for connection details.
P
3.4.1.
OWER
Power connections are on the terminal block on TB-1 through TB-5. See
Figure 3-2.
Where possible, minimize the DC wire length between the M3645P and
the drive. The wire length should not exceed 10 feet.
Avoid routing and bundling the unit's AC/DC wire along with the drive
output leads to the motor.
Only qualified electricians should perform and maintain the interconnection
wiring of this product. All wiring should be in accordance with local codes.
CAUTION!
AC L
3.4.1.1.
• The AC Line connections should be to a source rated for at least 150%
of the continuous current rating.
impedance to return power to the grid.
• Do not install any external chokes or reactors between the M3545P and
the power source; the M3545P has an internal 5% reactor.
• A properly rated isolation transformer may be installed between the
M3545P and the power source, if desired.
• Do not connect to a generator unless minimum load at any time exceeds
the peak expected regen power.
• The M3545P units are not phase sensitive.
• The AC Line connections should have short-circuit current protection.
See Table 6-3.
• To use the M3545P on a single-phase AC grid, you MUST connect to AC
L1 (TB-1) and AC L2 (TB-2).
DC B
3.4.1.2.
• The DC bus connections may be made to the DC bus of an AC drive, the
DC output of a diode sharing unit, or to a common DC bus.
o If a reactor or choke are being used in the bus, make sure the actual
• The DC bus connections should have short-circuit current protection.
The recommended fuses are listed in Table 6-3.
C
C
USTOMER
ONNECTIONS
W
IRING
INE
US
connection is in parallel with filter capacitors of the drive/inverter.
User's Manual
This will ensure sufficient source
15