bonitron M3545P Reference Manual

Regenerative dc bus power supply
Table of Contents

Advertisement

Quick Links

Model M3545P
Regenerative
DC Bus Power Supply
Customer Reference Manual
Web: www.bonitron.com
Tel: 615-244-2825
Email: info@bonitron.com

Advertisement

Table of Contents
loading

Summary of Contents for bonitron M3545P

  • Page 1 Model M3545P Regenerative DC Bus Power Supply Customer Reference Manual ● ● Web: www.bonitron.com Tel: 615-244-2825 Email: info@bonitron.com...
  • Page 2 Bonitron has seen thousands of products engineered since 1962 and welcomes custom applications. With engineering, production, and testing all in the same facility, Bonitron is able to ensure its products are of the utmost quality and ready to be applied to your application.
  • Page 3 RIVE PTIONS In 1975, Bonitron began working with AC inverter drive specialists at synthetic fiber plants to develop speed control systems that could be interfaced with their plant process computers. Ever since, Bonitron has developed AC drive options that solve application issues associated with modern AC variable frequency drives and aid in reducing drive faults.
  • Page 4: Table Of Contents

    ESCRIPTION 2.1. Related Products ........................... 9 2.2. Part Number Breakdown ......................9 Figure 2-1: Example of M3545P Part Number Breakdown ..............9 Table 2-1: Voltage Ratings ........................10 Table 2-2: Chassis Styles ........................10 Table 2-3: Option Codes ........................10 2.3.
  • Page 5 RoHS ........................... 28 6.5. Fuse Selection ..........................28 Table 6-4: Fuse Current Rating Requirements ..................28 6.6. Dimensions and Mechanical Drawings ..................29 Figure 6-1: M3545P M4 Chassis Dimensional Outline ................. 29 7. A ..........................31 PPENDIX 7.1. Application Notes ........................31 7.1.1.
  • Page 6 M3545P This page intentionally left blank...
  • Page 7: Introduction

    1.2. URPOSE AND COPE This manual is a user’s guide for the Model M3545P regenerative power supply. It provides you with the necessary information to successfully install and use the M3545P unit in your application. In the event of any conflict between this document and any publication and/or documentation related to the application, the latter shall have precedence.
  • Page 8: Symbol Conventions Used In This Manual And On Equipment

    M3545P 1.4. YMBOL ONVENTIONS SED IN THIS ANUAL AND ON QUIPMENT Earth Ground or Protective Earth AC Voltage DC Voltage DANGER: Electrical hazard - Identifies a statement that indicates a shock or electrocution hazard that must be avoided. DANGER! DANGER: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss.
  • Page 9: Product Description

    DC bus. If the DC bus voltage begins to rise, due to the drive trying to brake or an overhauling load, the M3545P will sink energy back to the AC Line. Under motoring conditions, the M3545P rectifies the AC line and supplies power to the drive through its DC bus terminals.
  • Page 10: Table 2-1: Voltage Ratings

    M3545P ODEL UMBER The Base Model Number for these regenerative power supply is M3545P. OLTAGE ATING A code letter represents the AC line voltage of the power supply module. The voltage rating must be selected for the system voltage that will be applied. See Table 2-1 for available voltage ratings.
  • Page 11: General Specifications Chart

    User’s Manual 2.3. ENERAL PECIFICATIONS HART Table 2-4: General Specifications ARAMETER PECIFICATION • 230 - 480 VAC ±10% 50/60Hz AC Line Voltage 3-Phase Operation • 15A, continuous • 22.5A for 60 second overload DC Input Current 1-Phase Operation • 5A, continuous •...
  • Page 12: General Precautions And Safety Warnings

    M3545P 2.4. ENERAL RECAUTIONS AND AFETY ARNINGS • H IGH VOLTAGES MAY BE PRESENT • N EVER ATTEMPT TO OPERATE THIS PRODUCT WITH THE ACCESS DOORS OR COVERS OPENED • N EVER ATTEMPT TO SERVICE THIS PRODUCT WITHOUT FIRST DISCONNECTING POWER TO AND FROM THE UNIT DANGER! •...
  • Page 13: Installation Instructions

    The M3545P must be correctly oriented for proper heat flow through the unit. The M3545P must be mounted with the rear surface of the unit to the mounting surface. The unit may be mounted vertically or horizontally as shown in Figure 3-1A and 3-1D.
  • Page 14: Figure 3-1: M3545P Mounting Orientation

    M3545P Figure 3-1: M3545P Mounting Orientation Figure 3-1A Figure 3-1D M3545 Line Regen POWER REGEN NOT READY AC L1 AC L2 AC L3 DRIVE BUS (+) DRIVE BUS (-) B NITRON INPUT COM FAULT RECALL OUTPUT COM READY GROUND RISK OF ELECTRICAL SHOCK.
  • Page 15: Wiring And Customer Connections

    • The M3545P units are not phase sensitive. • The AC Line connections should have short-circuit current protection. See Table 6-3. • To use the M3545P on a single-phase AC grid, you MUST connect to AC L1 (TB-1) and AC L2 (TB-2). DC B 3.4.1.2.
  • Page 16 12 AWG 7 lb-in Note: All power wire should be selected to match or exceed the voltage rating of the M3545P. Ground wiring should be, at smallest, one gauge smaller than the selected power wiring. Figure 3-2: M3545P Power & I/O Connection Location...
  • Page 17: I/O Wiring

    ONFIGURATIONS The diagrams shown in Figure 3-4 and Figure 3-5 illustrate typical connections of the M3545P units with generic VFDs. There are many other configurations that may be applied provided a basic connection criterion is maintained such as: • The AC Line connections should maintain a low impedance path back to the grid.
  • Page 18: Figure 3-4: M3545P Power Wiring

    • Any capacitive load requires precharge. Ensure that either the load has internal precharge, or that the M3545P unit has a –R option. Units without the –R option do not support precharge of any amount of capacitance. Applying power with no precharge in the system will result in fuse failure, and possible damage to the unit and load.
  • Page 19: Figure 3-5: M3545P Multiple Drives Field Wiring Diagram

    User’s Manual Figure 3-5: M3545P Multiple Drives Field Wiring Diagram...
  • Page 20 M3545P This page intentionally left blank...
  • Page 21: Operation

    DC terminals. If the DC voltage begins to rise, due to braking or an over-hauling motor, the M3545P acts as a 6-pulse inverter to efficiently sink this excess energy back to the power grid.
  • Page 22: System Faults

    Stack Math I/O C 4.4. ONNECTIONS All of the user inputs to the M3545P are 24VDC, active-high logic, and must be referenced to TB-7. The outputs are dry contacts that close to the output common: TB-9. N/C (TB-6) 4.4.1. This is a spare input reserved for future use and has no function at this time.
  • Page 23: Output Com (Tb-9)

    The output contact closes to this terminal (TB-10) 4.4.5. EADY This output closes to TB-9 when the M3545P is ready to operate. This contact will open if the unit is faulted. 4.5. TARTUP This section covers basic checks and procedures that should be used when performing a startup with a M3545P regenerative power supply.
  • Page 24 M3545P This page intentionally left blank...
  • Page 25: Maintenance And Troubleshooting

    5.3. ROUBLESHOOTING There are no user serviceable parts within the M3545P. If you are still experiencing problems after you have reviewed this whole section you may contact Bonitron for additional assistance at (615) 244-2825.
  • Page 26: Overtemperature Fault

    5.3.7. USES FAIL ON POWER ON Ensure that appropriate precharge is present in either the load VFD or in the M3545P (-R option). If precharge is present and fuses continue to fail, contact Bonitron for assistance. – B 5.4.
  • Page 27: Ngineering Ata

    ARALLEL 6.3. Tables 6-1 and 6-2 list the maximum watt loss generated by each of the M3545P units. When installing the units in an additional enclosure, consideration should be given to internal temperature rise. The watt loss rating in these tables is based upon the maximum continuous regen capability of each unit.
  • Page 28: Certifications

    UL 61800-5-1 6.4.1. All M3545P models are UL Listed under this standard. UL file number E204386. The M3545P regenerative power supply has a Short Circuit Current Rating (SCCR) of 65kA when protected by proper fusing. See Table 6-4 for required ratings and recommendations.
  • Page 29: Dimensions And Mechanical Drawings

    User’s Manual 6.6. IMENSIONS AND ECHANICAL RAWINGS Figure 6-1: M3545P M4 Chassis Dimensional Outline...
  • Page 30 M3545P This page intentionally left blank...
  • Page 31: Appendix

    M3545P 7.1.1. IZING THE The M3545P unit is sized for the amount of DC bus current, I which it must carry. To obtain the amount of DC bus current needed during deceleration; the load and motor inertias, desired change in RPM, and required stopping time must be known.
  • Page 32: Calculating Energy Savings

    ALCULATING NERGY AVINGS The M3545P directs energy from the mechanical load to the power distribution line, where the energy is available to other connected loads. These units provide system energy savings over dynamic braking kits, because the net energy required from the distribution system is reduced by the regenerated energy.
  • Page 33 User’s Manual NOTES...