Technical data
Operating voltage:
Fuse 230 V:
Switching elem. 230 V:
Switching power 230 V:
Rated current w/o valve drives:
Max current draw allowed
with connected valve drives:
Temperature setting range:
Target value calibration:
Reduction temperature:
Temperature measurement:
Measuring accuracy:
Ambient temperature:
Storage temp. range:
Admissible amb. humidity:
Temp. for ball pressure test:
CE conformity according to:
Protect. class 230 V:
Protection degree:
Rated impulse voltage:
Pollution degree:
Type action:
Weight:
Dimensions (W x H x D):
Antifreeze function: From +6 °C in heating mode, inactive in cooling mode.
Only thermostats with heating/cooling function:
Valve protection function: Once every 14 days for 6 minutes after the last
activation
This symbol means that electrical and electronic products may
NOT be mixed with unsorted household waste. Units must be
treated at a specialized treatment facility for reuse, recycling
and recovery.
By ensuring this product is disposed of correctly, you will help
to prevent potential negative consequences for the environment
and human health.
For more information, contact your installer or local authority.
2
230 V ±10 %, 50 Hz
T2AH
Relay
2 A resist. load
230 V: ≤2 mA
230 V: 1.8 A
10 °C - 28 °C
±2 K
2 K
0 - 40 °C
±0.5 K
0 - 50 °C
-25 to +75 °C
80%, not condensing
Terminals: 100 °C
Plastic enclosure: 75 °C
EN 60730
II
IP 20
1500 V
2
Type 1 / Type 1.C
90 g
86 x 86 x 29 mm
4P560991-1
2019.01
Need help?
Do you have a question about the EKWCTRAN1V3 and is the answer not in the manual?
Questions and answers