No.
Item
4
RS485
communication
s cable
5
(Optional)
Power cable of
the tracking
system
Note a: The value is valid only if the conductors of the PE cable and AC power cable use the same
material. If the materials are different, ensure that the conductor cross-sectional area of the PE
cable produces a conductance equivalent to that of the area S/2.
Note b: You are advised to use a soft cable to prevent poor terminal contact due to the bending
stress of the cable.
4.2
Installing the PE Cable
•
It is recommended that the PE cable
be connected to a nearby PE point.
Connect the PE points of all
SUN2000s in the same PV array to
ensure equipotential connections to PE
cables.
•
To enhance the corrosion resistance of
a ground terminal, you are advised to
apply silica gel or paint on it after
connecting the PE cable.
Type
Outdoor shielded
twisted pair cable
Three-core outdoor
copper cable with
dual-layer
protection
Specifications
•
Conductor cross-
sectional area: 0.25–1
2
mm
•
Cable outer diameter:
4–11 mm
•
Conductor cross-
sectional area: 10
2
mm
•
Cable outer diameter:
15–18 mm
6
Description
When three
communications cables
connect to the signal
cable connector, the
outer diameter of the
cables should be 4–8
mm.
-