ABB KA-4 Instruction Leaflet page 10

Carrier auxiliary relay

Advertisement

41-923.4M
7.4. FOR RELAYS TO BE USED WITH
KR-TYPE CARRIER OR TA-3 TONES
7.4.1.
Receiver Unit
Calibrate as outlined under TC Type Carrier. Apply
15 mA dc current for polarity check. The pickup value
should be 4 milliamperes dc (armature moves to left)
instead of 40 mA. The calibration of reset (armature
moves to the right) should be done at 6 milliamperes
instead of 60 mA.
7.4.2.
Alarm Unit
Calibrate as outlined under TC-type Carrier. Check
pick-up at 8 mA ±5% instead of 80 mA. Dropout
should be between 4 and 6 mA instead of 40 and 60
mA.
8.0 RENEWAL PARTS
Repair work can be done most satisfactorily at the
factory. However, interchangeable parts can be fur-
nished to the customers who are equipped for doing
repair work. When ordering parts, always give the
complete nameplate data.
10
9.0 ENERGY REQUIREMENTS
9.1. CURRENT BURDEN AT 60 CYCLES
Current
Amperes
Amperes
0.5
5
20
40
1240
60
2760
Current lagging voltage.
††
Current leading voltage.
9.2. RATING OF OVERCURRENT UNIT
Continuous rating 5 amperes. One second rating 100
amps.
Power
Volt
Factor
Angle
2.2
33°
43
70°
††
394
49°
††
39.2°
††
32.5°