Grid feeding monitoring relay, cm range (13 pages)
Summary of Contents for ABB KLF-1
Page 2
41-748.31B KLF-1 Loss-of-Field Relay 2 1 ) . T h e p r i m a r y o r c u r r e n t w i n d i n g o f t h e Mechanically, the cylinder unit is composed of four...
41-748.31B KLF-1 Loss-of-Field Relay a spiral spring. The spring adjuster is also held in assembly, and a molded bridge. place by a spring type clamp. The electromagnet has two pairs of voltage coils. When the contacts close, the electrical connection is Each pair of diametrically opposed coils is connected in series.
Page 4
The type KLF-1 relay is available in one range. Long current and is equal to T. Each secondary com- Reach is 2.08 to 56 ohms. Short Reach is 0.79 to pensator voltage is in series with voltage V 18.0 ohms.
The main contacts will safely close 30 amperes at 250 volts dc and the seal-in contacts of the indicating The KLF-1 relay may be applied as a single-zone contactor switch will safely carry this current long device, or two relays may be used to provide enough to trip a circuit breaker.
Page 6
41-748.31B KLF-1 Loss-of-Field Relay The single-zone and two-zone setting recommenda- Continue this process with other points from curves tions are modified when two or more machines are such as those of Figure 7 (page 23) until a complete bussed at the machine terminals. The voltage and curve like that of Figure 8 (page 23) is obtained.
---------- - ± 0.15 1.15 Assume that a KLF-1 relay is to be applied to the fol- lowing machine: This is 99.7% of the desired setting. 3-phase, 60 cycles, 3600 rpm, 18 kV, rated at 0.9 pf, To set Z = 3.29 ohms:...
Page 8
58 V . (Equivalent to 100 able to use an external timer in conjunction with the KLF-1 Relay. The following examples are applica- L-L. tions where an external timer would be desirable: 3. For all applications where the alarm function 1.
7.0 SETTING THE RELAY larger impedance characteristic and will detect partial loss-of-field conditions. A typi- The type KLF-1 relay requires a setting for each of cal setting would be to just allow the machine the two compensators T and T...
41-748.31B KLF-1 Loss-of-Field Relay COMPENSATOR (T AND T Values for which an M setting can be made are from -.15 to +.15 in steps of .03. The value of a setting is Each set of compensator taps terminates in inserts...
41-748.31B KLF-1 Loss-of-Field Relay screws may be utilized for grounding the relay. The current until contacts just close. This current should be within ± 3% of 17.9 amps, (17.3 - electrical connections may be made directly to the terminals by means of screws for steel panel mount- 18.5 amps).
41-748.31B KLF-1 Loss-of-Field Relay Repeat above except pass 85% of ICS name- For the most accurate calibration preheat relay plate rating current. Contacts should not pickup for at least an hour by energizing terminals 4, 5, and target should not drop.
Page 13
41-748.31B KLF-1 Loss-of-Field Relay such that the contacts will just close. De-ener- With 50 volts and 5 amperes applied, vary gize the relay. The moving contact should return the phase shifter to obtain the two angles to open position against the right-hand stop.
Page 14
41-748.31B KLF-1 Loss-of-Field Relay 1) Contact Gap Adjustments 1/16” ahead. The cover may be removed and the tab holding the target reformed slightly if a. L.H. (Normally Closed) Contact Adjustment necessary. However, care should be exer- With the moving contact arm in the closed...
Page 15
FOR RELAYS RATED 1. Connect the relay as shown in Figure 9 (Dia- AT 120 VAC gram of Test Connections for KLF-1 Relay The proper adjustments to insure correct operation of on page 24), with the switch in position 1 and this relay have been made at the factory.
Page 16
41-748.31B KLF-1 Loss-of-Field Relay 2. Decrease the voltage until the contacts close between R and tap being measured. Exam- to the left. This value should be 90 ± 3% volts. ple 100 (1 + .03 + .06) = 109 volts.
Page 17
3/4 of one turn Using the connections of Figure 9 (Diagram of for a contact gap of .22”. Test Connections for KLF-1 Relay on page 24), apply 10 volts ac 90° leading, to terminals 4 and 2. With relay de-energized adjust the restraint 5 pass 0.63 amperes through current circuit ter-...
Page 18
41-748.31B KLF-1 Loss-of-Field Relay the directional unit need not be cooled F. Indicating Contactor Switch (ICS) during initial rough adjustment. But, the Initially adjust unit on the pedestal so that arma- directional unit should be cool when final ture fingers do not touch the yoke in the reset adjustment is made.
41-748.31B KLF-1 Loss-of-Field Relay should jump from 0 to the rated voltage after between lead L and terminal 5. a time delay of 0.4 ± 10% seconds. A trimpot a. For T = 15.8 the voltage measured on the PC board can be adjusted to obtain should be 158 volts ±...
Page 21
41-748.31B KLF-1 Loss-of-Field Relay Sub 1 185A181 Figure 2. Compensator Construction Sub 5 3531A60 Figure 3. Internal Schematic of Type KLF-1 Relay in FT41 Case...
Page 23
0.64 SCR, inner-cooled, 3600 rpm) Sub 2 *Sub 2 188A320 185A184 Figure 6. Effect of Compensator Voltage (Z is positive) Figure 8. Typical Machine Capability Curves and Sample KLF-1 Settings - Per Unit Impedance * Denotes change since previous issue...
Page 26
41-748.31B KLF-1 Loss-of-Field Relay *Sub 3 3335A32 Figure 12. Zone 2 Impedance Characteristic Sub 2 3491A09 Figure 13. KLF-1 Frequency Response For Impedance Unit For 60 Hz Relay...
Page 27
41-748.31B KLF-1 Loss-of-Field Relay *Sub 4 3533A29 Figure 14. Relay Type KLF-1, Time Delay Schematic for Class 1E Application...