Symantec. ® HyperTerminal is a registered trademark of Hilgraeve. ® Modbus is a registered trademark of Modicon. ® Contact Information ERLPhase Power Technologies Ltd. Website: www.erlphase.com Email: info@erlphase.com Technical Support Email: support@erlphase.com Tel: 1-204-477-0591 D02706R02.20 L-PRO 4000 User Manual...
3 Using the IED (Getting Started) ......3-1 Introduction ..............3-1 Start-up Sequence ............3-1 Interfacing with the Relay..........3-1 Front Panel Display............3-2 Terminal Mode ..............3-7 Relay Control Panel ............3-7 4 Protection Functions and Specifications .... 4-1 D02706R02.30 L-PRO 4000 User Manual...
Appendix B IED Settings and Ranges ......B-1 Settings and Ranges............B-1 Appendix C Hardware Description .......C-1 Appendix D Event Messages ........D-1 Appendix E Modbus RTU Communication Protocol ..E-1 Appendix F DNP3 Device Profile ......... F-1 Appendix G Mechanical Drawings .......G-1 L-PRO 4000 User Manual D02706R02.30...
Page 7
79 Auto-recloser Examples..........L-9 Appendix M Failure Modes ......... M-1 Actions ................M-1 Appendix N IEC61850 Implementation ......N-1 Protocol Implementation Conformance Statement (PICS) ................N-1 Model Implementation Conformance Statement (MICS)................N-8 Data Mapping Specifications .........N-40 Index ..................I D02706R02.30 L-PRO 4000 User Manual...
Service User input or keystrokes are shown in bold. Text boxes similar to this one Relate important notes and information. Indicates more screens. Indicates further drop-down menu, click to dis- play list. Indicates a warning. D02706R02.30 L-PRO 4000 User Manual...
IED - Intelligent Electronic Device IP - Internet Protocol (IP) address IRIG-B - Inter-range instrumentation group time codes LE- Load Encroachment LED - Light-emitting Diode LHS - Left Hand Side LMDA - Live Main Dead Aux D02706R02.30 L-PRO 4000 User Manual...
Page 12
SG - Setting Group SIR ratio - Source Impedance Ratio SOTF - Switch On To Fault TT - Transfer Trip TUI - Terminal User Interface UI - User Interface VI - Virtual Input WI - Weak Infeed L-PRO 4000 User Manual D02706R02.30...
Minor releases (designated with a letter suffix - e.g. v3.1a) maintain the same compatibility as their base version. For example. L-PRO firmware v3.1c and Offliner Settings v3.1a are compatible. L-PRO 4000 Firmware/Software Compatibility Guide L-PRO Setting Compatible Offliner Settings...
Insert the CD-ROM in the drive. The CD-ROM should open automatically. If the CD-ROM does not open automatically, go to Windows Explorer and find the CD-ROM (usually on D drive). Open the ERLPhase.exe file to launch the CD-ROM. D02706R02.30 L-PRO 4000 User Manual xiii...
Page 16
ERLPhase applications as a “potential threat”, it will be necessary to con- figure your anti-virus/anti-software to classify it as “safe” for its proper oper- ation. Please consult the appropriate anti-virus/anti-spyware software documentation to determine the relevant procedure. L-PRO 4000 User Manual D02706R02.30...
• Over / Under / Rate of change of frequency devices Relay Control Panel (RCP) is the Windows graphical user interface software tool provided with all 3000, 4000 series and higher (new generation) ERL re- lays to communicate, retrieve and manage records, event logs, fault logs, man- age settings (identification, protection, SCADA etc.,), display real time...
Page 18
Real Power External Inputs 11 External 7 Output Contacts Optional I/O Reactive Power Active Setting Group Inputs Output Contacts Figure 1.1: L-PRO Relay Function Line Diagram 50LS: Low set overcurrent PL: ProLogic WI: Weak infeed L-PRO 4000 User Manual D02706R02.30...
3. USB Port 150 for maintenance interface 4. Push buttons to manipulate information on settings, display and to clear targets 5. 11 Target Programmable LEDs 6. Ethernet Port 119 Figure 1.3: L-PRO Relay Front View (4U) D02706R02.30 L-PRO 4000 User Manual...
14.Ports 324-327, 330-333: AC voltage inputs 15.Ports 300-323: AC current inputs 16.Ports 230-235, 328, 329, 334, 335: Unused 17.Ports 336-337: Power supply 18.Port with GND symbol: Chassis Ground Figure 1.4: L-PRO Relay Rear View (3U) L-PRO 4000 User Manual D02706R02.30...
Page 21
The relay has 14 (3U) or 21 (4U) programmable relay contacts. Contacts Relay If the relay is in self check program or becomes inoperative, then the Relay In- Inoperative operative Alarm output contact closes and all tripping functions are blocked. Alarm Output D02706R02.30 L-PRO 4000 User Manual...
The external inputs are 48, 110/125 or 220/250 Vdc. The system base frequency is either 50 Hz or 60 Hz. The L-PRO 4000 is available in a standard 3U rack model or as 4U model with an optional I/O board as described above.
IRIG-B signals. The IRIG-B time signal is connected to the BNC connection on the back of the relay. When the IRIG-B signal is provided to the relay the IRIG-B functional Light-Emitting Diode (LED) comes on and the relay clock D02706R02.30 L-PRO 4000 User Manual...
Ethernet port 119 and 1 rear panel Ethernet Port 120 and 2 rear serial Ports 122 and 123) to provide direct access to its user interface and SCADA services. The relay’s user interface is accessed through the Relay Control Panel. L-PRO 4000 User Manual D02706R02.30...
To create an USB link between the relay and the computer, first the USB driver for the ERLPhase 4000 series device needs to be installed, as follows: Unzip the file (can be obtained from ERL website): ERLPhase_USB_driver.zip In this case we assume you unzipped to the desktop.
Page 26
“The wizard has finished installing the software for” “ERLPhase 4000 Series Device” Hit Finish. To verify the installation was successful, and to which comm port is the ERL- Phase 4000 Series Device configured, do the following: In Windows XP Start > Control Panel->Performance and Maintenance->System >Hard- ware >...
120 is assigned with an IP address of 192.168.101.80. If this address is not suit- able, it may be modified using the relay’s Maintenance Menu. For details see “Using HyperTerminal to Access the Relay’s Maintenance Menu” on page 2- D02706R02.30 L-PRO 4000 User Manual...
2-15. Rear Port 122 is for SCADA and Port 123 can be used for direct se- rial access and external modem. Ensure the relay port and the PC’s port have the same baud rate and communications parameter, see “Maintenance Menu Commands” on page 2-11. L-PRO 4000 User Manual D02706R02.30...
The Initialize setting allows the user to set the control codes sent to the modem at the start of each connection session. The factory defaults are: “M0S0=0&B1” for an external modem and “M0S0=0” for an internal modem. D02706R02.30 L-PRO 4000 User Manual...
Page 30
When an internal modem is installed, the relay’s Port 118 is used to interface to the modem internally. Appropriate Port 118 settings are configured at the factory when the internal modem is installed. The factory defaults are: “M0S0=0&B1” for an external modem and “M0S0=0” for an internal modem. L-PRO 4000 User Manual D02706R02.30...
If “Default Telnet Program?” windows pops up, Check “Don’t ask me this question again” Hit No. First time use of HyperTerminal will ask for “Location Information”. Fill with appropriate information, e.g.: “What country/region are you in now” Choose “Canada” D02706R02.30 L-PRO 4000 User Manual...
Page 32
Let’s assume in this case it is COM3. In the window “COM3 Properties” choose: “115200” “8” “None” “1” “Hardware” Hit Apply then hit OK At this time the connection should already be established. Hit Enter in the terminal window. 2-10 L-PRO 4000 User Manual D02706R02.30...
Page 33
Manually initiates a hardware reset. Note that the communication link is immediately lost and cannot be reestablished until the unit completes its start-up. Network utilities Enters network utilities sub-menu. Monitor SCADA Shows real time display of SCADA data. D02706R02.30 L-PRO 4000 User Manual 2-11...
The firmware update is used to update the relay’s software with maintenance or enhancement releases. Please see the L-PRO Firmware Update Procedure documentation that comes with the firmware update for instructions on how to update the firmware on the relay. 2-12 L-PRO 4000 User Manual D02706R02.30...
Details on how to set these respective baud rates are described above, except that the user modifies the Port 123 baud rate on the relay and the properties of the modem in HyperTerminal. D02706R02.30 L-PRO 4000 User Manual 2-13...
Appendices, for details see “Modbus RTU Communication Protocol” in Appendix E and “DNP3 Device Profile” in Appendix F Protocol To select the desired SCADA protocol go to L-PRO 4000 Offliner SCADA communications section. Select the protocol and set the corresponding param- Selection eters.
• Default Setting: 9600 baud N81 (no parity, 8 data bits, 1 stop bit). • User interface access through an external modem. The optional ERLPhase Modem Adapter converts this port to a Data Terminal Equipment (DTE) to simplify connection to an external modem. D02706R02.30 L-PRO 4000 User Manual 2-15...
Page 38
Table 2.5: Signal connections to pins on Relay Port Signal Name Direction PC<-> Relay Pin # on the Relay Port Common No connection Notes: Relay is DCE, PC is DTE. Pins 1 and 6 are tied together internal to the relay. Table 2.6: Cable Pin Connections Male DB-9 Cable End for Relay Port Female DB-9 Cable End for Computer Port...
Page 39
Pin # on the Modem Adapter Common No connection Notes: Relay (with modem adapter) is DTE, modem is DCE. Pins 1 and 6 are tied together internal to the relay. D02706R02.30 L-PRO 4000 User Manual 2-17...
3.3 Interfacing with the Relay The following ways can be used to interface with the relay: • Front panel display • Terminal mode (for maintenance and firmware upgrade) • Relay Control Panel D02706R02.30 L-PRO 4000 User Manual...
Occurs when an enabled relay function picks up. The red Alarm LED should be off if there are no inputs to the relay. If the Alarm LED is on, check the event log messages which are available through the menu system. L-PRO 4000 User Manual D02706R02.30...
Page 43
Target LED assignments are the default values but are configurable by the user through the Offliner settings (output matrix configuration). Push Buttons Table 3.3: Identification of Push Buttons Up, Down, Right, Left, Enter, Escape Used to navigate the front panel screens. D02706R02.30 L-PRO 4000 User Manual...
Page 44
Setting Group 6 Setting Group 7 Setting Group 8 Metering Analog Analog Inputs Line Quantities External Inputs Output Contacts Logic Logic Protections 1 Logic Protections 2 ProLogic Group Logics Virtual Inputs Records View Record List L-PRO 4000 User Manual D02706R02.30...
Page 45
Network Protocol Stats Active Sockets Routing Tables Ping Logout Where the access levels required to access each are indicated by: V: view C: change S: service To login into the LCD menu structure, follow these steps: D02706R02.30 L-PRO 4000 User Manual...
Page 46
1 2 3 4 5 6 7 8 9 0 - + = g h i j k l m n Sp p q r s t u v w x y z back select view Figure 3.4: Enter Password L-PRO 4000 User Manual D02706R02.30...
Please refer to the Relay Control Panel User Manual for details. Follow this sequence to configure RCP for USB link to the relay. 1. Execute. Relay Control Panel.exe 2. Execute. L-PRO 4000 Offliner.exe 3. Install Null Modem Driver. D02706R02.30 L-PRO 4000 User Manual...
Page 48
Table 3.5: Relay Control Panel Structure View Change Service Relay Control Panel Records Trigger Fault Trigger Fault Trigger Swing Trigger Swing Trigger Event Trigger Event Faults Erase Erase Events Erase Erase Metering L-PRO 4000 User Manual D02706R02.30...
Page 49
Toggle Outputs Close/Open Settings Group Save Save Passwords Configuration Present Settings (Get From Relay) Saved Settings (Load to (Load to Relay) Relay) Notice that some options are not available (N/A) depending on the access level. D02706R02.30 L-PRO 4000 User Manual...
All the distance functions are set in secondary ohms. The available range of impedance settings is based on the nominal current specified when the relay was ordered. The impedance reach ranges are given in “21P Phase/21N Ground Distance” on page 4-2. L-PRO 4000 User Manual D02706R02.30...
Page 53
Figure 4.2: Phase and Ground distance protection Quadrilateral Characteristics The shape of the Mho characteristic means that significant extensions are made to the relay characteristics in the R region of the R-X plane for ground faults. D02706R02.30 L-PRO 4000 User Manual...
Page 54
The directional element does not supervise Zone 3, Zone 4 and Zone 5 ele- ments if these zones are set as offset characteristic. The directional element is described in “Directional Element” on page 4-10. L-PRO 4000 User Manual D02706R02.30...
Figure 4.4: Load Encroachment (LE) Logic on page 4-5 shows how the LE function works. Phase-to-phase current monitoring has been added to the logic to ensure stable operation. Figure 4.4: Load Encroachment (LE) Logic D02706R02.30 L-PRO 4000 User Manual...
Page 56
Load Impedance (Ohms) R (Ohms secondary) -150.0 to 150.0 Both X (Ohms secondary) -150.0 to 150.0 Both Load Encroachment Enable/Disable Both Impedance (Ohms sec- 0.01 to 66.0 (5 A) Both ondary) 0.05 to 330.0 (1 A) L-PRO 4000 User Manual D02706R02.30...
Page 57
70.0 to 140.0 70.0 to 140.0 70.0 to 140.0 70.0 to 140.0 70.0 to 140.0 (degrees) Pickup Delay (seconds) 0.00 to 99.00 0.00 to 99.00 0.00 to 99.00 0.00 to 99.00 0.00 to 99.00 Both D02706R02.30 L-PRO 4000 User Manual...
No Memory Voltage Full Memory Voltage Figure 4.5: Effect of using Memorized Voltage on a 3-phase forward fault condition L-PRO 4000 User Manual D02706R02.30...
VTs until the voltage output of the ring filter is correct. If the measured positive sequence voltage is below 1 Vsec, then the Mho/Quad elements use the positive sequence voltage derived from the memory voltage D02706R02.30 L-PRO 4000 User Manual...
The sensitivity for the negative- and zero- sequence elements may be set by the user, to correctly account for load condi- tions and system configuration. Both of these elements may be disabled as well. The positive-sequence element is always active. 4-10 L-PRO 4000 User Manual D02706R02.30...
Page 61
To perform this calculation, the default minimum amount of zero-se- quence voltage (3 ) required is 1.0 V secondary, and the default minimum amount of zero-sequence current (3 ) required is 0.2 A secondary. D02706R02.30 L-PRO 4000 User Manual 4-11...
Selecting “Directional Element Override Enabled” allows user settings for the negative-sequence and zero-sequence directional elements. 4-12 L-PRO 4000 User Manual D02706R02.30...
Our algorithm overcomes this problem. D02706R02.30 L-PRO 4000 User Manual 4-13...
Page 64
Table 4.5: Angular difference between negative and zero sequence currents for various faults Fault Fault Fault Fault Fault Fault Angle Diff. between I and I (AngleDiff_I2_I0_A) Angle Diff. between I and I (AngleDiff_I2_I0_B) Angle Diff. between I and I (AngleDiff_I2_I0_C) 4-14 L-PRO 4000 User Manual D02706R02.30...
Page 65
21P5, and then plus 8 cycles (8 cycles is the maximum breaker opening). This ensures that if 21P did not trip on the phase-phase-ground fault for some reason, 21N is allowed to trip on this fault after this maximum blocking time delay has expired. D02706R02.30 L-PRO 4000 User Manual 4-15...
A special CCVT transient compensation algorithm (Patent Pend- 21 Devices ing) has been included in L-PRO 4000 relay to address this issue. The CCVT transient compensation algorithm uses a combination of techniques with digital filters, vector averages and other means to rebuild the correct volt- age from the transient distorted voltage waveforms.
If the user selects Device 68 to block for Power Swing conditions, the relay en- ergizes the front panel alarm LED when the 68 elements are blocking. If the user selects the 68 to trip for Power Swing conditions the relay energizes the front panel target light. D02706R02.30 L-PRO 4000 User Manual 4-17...
Page 68
Left Hand Side (LHS) Blinder Outer (R1) -100.0 to R2 ohms secondary (5A) -500.0 to R2 ohms secondary (1A) Inner (R2) R1 to R3 ohms secondary Right Hand Side (RHS) Blinder Inner (R3) R2 to R4 ohms secondary 4-18 L-PRO 4000 User Manual D02706R02.30...
The third input (the bottom one) produces an output only if the positive se- quence line current is less than 4% nominal or 4.0% of 5 A secondary = 0.20 D02706R02.30 L-PRO 4000 User Manual 4-19...
Figure 4.14: Switch On To Fault (SOTF) The logic diagram, Figure 4.14: Switch On To Fault (SOTF) on page 4-20, shows how the circuit actually works. The SOTF function has options as Close Command or Status Monitoring. 4-20 L-PRO 4000 User Manual D02706R02.30...
Page 71
Breaker signal setting is selected as Close Command) Main Breaker Status EI1 to EI 20, PL1 to PL24, VI1 to VI30 (This setting shall be enabled when the Breaker signal setting is selected as Status Monitoring) D02706R02.30 L-PRO 4000 User Manual 4-21...
Device 59 3V0 Pickup 0.0 to 100.0 V secondary Zone 2/Zone 4 Reset Delay (TWD1) 0.02 to 0.20 seconds Communication Cycle Reset Delay 0.02 to 0.20 seconds (TWD2) Communication Reset Time Delay 0.02 to 1.0 seconds (TW3) 4-22 L-PRO 4000 User Manual D02706R02.30...
Angle Difference 1.0 to 50.0 degrees Pickup Delay 0.00 to 10.00 seconds Main/Aux Enable Dead Main Live Aux. (DMLA) Enable/Disable Enable Live Main Dead Aux. (LMDA) Enable/Disable Enable Dead Main Dead Aux. (DMDA) Enable/Disable D02706R02.30 L-PRO 4000 User Manual 4-23...
T4) for the 3-phase recloser. The follow breaker open time interval is common for each reclosure attempt. This follower breaker reclose time can be set to use the 79 follower timer TF or the 79 reset timer TD. See L-PRO 4000 Function Logic Diagram for details.
Page 75
79 remotely or locally with external or virtual inputs. The 79 recloser mon- itors the breaker contact “a” status and automatically moves the follower breaker into the lead position when the lead breaker is removed from service, D02706R02.30 L-PRO 4000 User Manual 4-25...
Page 76
TM be set longer in duration than the single phase recloser time. Only one sin- gle phase reclose is attempted. If upon reclosure the fault persists, before timer TD5 has had a chance to dropout, the line will 3-phase trip and lockout. To get 4-26 L-PRO 4000 User Manual D02706R02.30...
Page 77
The drawing for the single phase reclosing logic is shown on the L-PRO 4000 Function Logic Diagram. Single-Phase/3-Phase Trip and Reclose Scheme...
The auxiliary overvoltage function operates exactly the same way as the main overvoltage function except that it uses the voltages from the auxiliary PT in- puts. Table 4.11: 59 Overvoltage Settings Main Enable/Disable Gate Switch AND or OR 4-28 L-PRO 4000 User Manual D02706R02.30...
Page 79
0.0104 (Fixed) 0.0228 (Fixed) 0.02 (Fixed) IEEE Very Inverse 3.880 (Fixed) 0.0963 (Fixed) 2.00 (Fixed) IEEE Extremely Inverse 5.67 (Fixed) 0.0352 (Fixed) 2.00 (Fixed) User-defined 0.0010 to 0.0000 to 0.01 to 10.00 1000.0000 10.0000 D02706R02.30 L-PRO 4000 User Manual 4-29...
Page 80
See Table 4.12: IEC and IEEE curves 0.01 to 10.00 0.0010 to 1000.0 0.0000 to 10.0 0.01 to 10.0 0.10 to 100.0 59N Definite Time Delay Enable/Disable Pickup (Volt) 5.00 to 150.00 Pickup Delay (Sec) 0.00 to 99.99 4-30 L-PRO 4000 User Manual D02706R02.30...
(i.e. Ia-Ib, Ib-Ic and Ic-Ia), and the ground distance elements are supervised by both the phase current and the zero se- quence (3 ) current. D02706R02.30 L-PRO 4000 User Manual 4-31...
Page 82
This function is fast enough to provide blocking of the distance functions for schemes that use bus potential inputs that are sometimes transferred without the need for any external blocking inputs. 4-32 L-PRO 4000 User Manual D02706R02.30...
Page 83
The auxiliary CT Supervision function operates exactly the same way as the main CT Supervision function except that it uses the Inps current from the aux- iliary CT in-puts. Main CT Supervision Enabled Main CT Inps > Pickup Main PT Vnps < Pickup D02706R02.30 L-PRO 4000 User Manual 4-33...
0.25 pu provides an undervoltage inhibit on each element Frequency (Hz) Figure 4.19: Frequency Fixed Level df/dt (Hz/s) Figure 4.20: Frequency Rate of Change Table 4.18: 81 Over/Under Frequency Settings Disabled/Fixed Level/Rate of Change 4-34 L-PRO 4000 User Manual D02706R02.30...
0.02 to 10.0 A secondary (1A) Pickup Delay 0.00 to 10.00 Seconds Auxiliary (Input 2) Enable/Disable Pickup 0.10 to 50.0 A secondary (5A) 0.02 to 10.0 A secondary (1A) Pickup Delay 0.00 to 10.00 Seconds D02706R02.30 L-PRO 4000 User Manual 4-35...
Table 4.20: 50BF Breaker Failure Settings Main Enable/Disable Pickup Delay 1 0.01 to 99.99 Seconds Pickup Delay 2 0.01 to 99.99 Seconds Breaker Current Pickup 0.10 to 50.0 A secondary (5A) 0.02 to 10.0 A secondary (1A) 4-36 L-PRO 4000 User Manual D02706R02.30...
Page 87
ProLogic input. This input can be a phase segregated input that can come from a single pole trip from an external relay and is shown on the Scheme Selector screen. D02706R02.30 L-PRO 4000 User Manual 4-37...
For I > pickup T I TMS B ----------------------------------- - ----------------- - – Pickup For I < pickup T I ----------------------------------- ----------------- - – Pickup 4-38 L-PRO 4000 User Manual D02706R02.30...
Page 89
Phase Setting Multiplier for Single-Phase Open Pole Condition 50 Pickup Current Multiplier 0.10 to 2.00 50 Pickup Time Multiplier 0.10 to 2.00 51 Pickup Current Multiplier 0.10 to 2.00 51 Pickup Time Multiplier 0.10 to 2.00 D02706R02.30 L-PRO 4000 User Manual 4-39...
For details see Table 4.21: IEC and IEEE Curves on page 38. 0.01 to 10.00 0.0010 to 1000.0000 0.0000 to 10.0000 0.01 to 10.00 0.10 to 100.00 Directional Angle Setting Alpha -179.90 to 180.00 Beta 0.10 to 360.00 4-40 L-PRO 4000 User Manual D02706R02.30...
46-51 Enable/Disable Directional Directional, non-directional or combined Pickup 0.50 to 50.00 (5 A) 0.10 to 10.00 (1 A) Curve Type For details see Table 4.21: IEC and IEEE Curves on page 0.01 to 10.00 D02706R02.30 L-PRO 4000 User Manual 4-41...
(i.e. between 2 A and 5 A for 5 ACT). The threshold is equal to nominal 40%*I if 2*PickupLevel < 40%*I . The threshold is equal to I nominal nominal nom- if 2*PickupLevel>I inal nominal 4-42 L-PRO 4000 User Manual D02706R02.30...
The relay fault locator uses the Takagi method of fault location. The imped- ance calculated for a fault initiated by any of the above functions will be cal- culated and compared with the line impedance to calculate distance to fault. D02706R02.30 L-PRO 4000 User Manual 4-43...
E inputs are status points of devices that are user-selectable. Each ProLogic output can be given a specific name, pickup and reset time delay. Op 1 Op 2 Op 3 Op 4 Op 5 Figure 4.24: ProLogic 4-44 L-PRO 4000 User Manual D02706R02.30...
Change Active Group The user can at any time change the active setting group. When initiating a set- ting group change, this change takes precedence over an automatic setting group change. D02706R02.30 L-PRO 4000 User Manual 4-45...
Page 96
The protection processor does not have any interruption in service. Automatic Settings Change Relay configuration changes during a relay-initiated setting; change does not disrupt the relay protection functions. Since the relay setting file does not 4-46 L-PRO 4000 User Manual D02706R02.30...
The scheme selector can also be configured to enable the 50N/67F and 50N/ 67R directional overcurrent elements as inputs to ProLogic statements. The D02706R02.30 L-PRO 4000 User Manual 4-47...
Zone 2, Zone 4, 51N, or 50N/67 elements could pick up. If any of these functions pick up, they block the WI scheme by putting a high in- put into inverted input of AND 110. The blocking condition is required last for D02706R02.30 L-PRO 4000 User Manual 4-49...
durations greater than 6 ms. The blocking logic continues to block the scheme send and scheme trip signals when the fault detection or loss of potential sig- nals go low. Timer setting TWD1 determines the block extension time. TWD1 should be set to coordinate with the communication-reset time of the PT signal. It should be set greater than the time it takes for the remote end’s Zone 2 to re- set and for the PT channel to reset.
• Record length (0.2 to 10.0 seconds => 12 to 600 cycles @ 60 Hz Base) with automatic extension to capture successive triggers • Recorder triggering by any internal logic or external input signal (e.g. 52 A) • Pre trigger time configurable between 0.10 to 2.00 seconds D02706R02.30 L-PRO 4000 User Manual 4-51...
Also the relay display provides the option to initiate Fault Recording, under the following path: Main Menu > Records > Fault Recording A swing record can take a couple of minutes to produce due to the long post-trigger time. 4-52 L-PRO 4000 User Manual D02706R02.30...
A listing of stored records is available through the Relay Control Panel under the Records > List menu. The listing transfers records to a connected PC and Retrieval and deletes them from storage. Deletion D02706R02.30 L-PRO 4000 User Manual 4-53...
This display is a snapshot of the event list which must be manually refreshed to display new events that occur while the display is up. There is a list of Event Messages, for details see “Event Messages” in Appendix D 4-54 L-PRO 4000 User Manual D02706R02.30...
46-50/67 Trip - “Line” Current Negative Sequence Phasor (3I2) 46-51/67 Trip The fault log can be viewed in three ways: • Relay Front HMI • Relay Control Panel interface is in the Events tab D02706R02.30 L-PRO 4000 User Manual 4-55...
Page 106
4 Protection Functions and Specifications • 61850 SCADA protocol included in the L-PRO allow the SCADA client access to Trip event data 4-56 L-PRO 4000 User Manual D02706R02.30...
The SCADA protocol deals with the Modbus and DNP (Distributed Network Protocol) protocols. The SCADA configuration and its settings are described. The parameters for SCADA communications are defined using L-PRO 4000 Offliner software. Finally, details on how to monitor SCADA communications are given for maintenance and trouble shooting of the relay.
Page 108
1. Establish a TUI session with the relay and login as maintenance. The fol- lowing screen appears. Figure 5.1: L-PRO 4000 System Utility L-PRO 4000 User Manual D02706R02.30...
Page 109
5 Data Communications 2. Select the first option by entering the number 1 followed by Enter. The fol- lowing screen appears. Figure 5.2: Change the network parameters as needed for the particular application D02706R02.30 L-PRO 4000 User Manual...
Page 110
As noted before, there is no field to configure the number of data and stop bits. These values are fixed as follows: • Modbus Serial – 7 data bits, 1 stop bit • DNP Serial – 8 data bits, 1 stop bit L-PRO 4000 User Manual D02706R02.30...
Page 111
Maintenance user interface. 1. Establish a TUI session with the relay and login as maintenance. 2. Select option 9 by entering the number 9 followed by Enter. The following screen appears. Figure 5.4: Login Screen D02706R02.30 L-PRO 4000 User Manual...
Page 112
3. Pressing the Enter key results in all SCADA communications characters to be displayed as hexadecimal characters. Individual exchanges are separat- ed by an asterisk as the following sample illustrates. Figure 5.5: Hyperterminal 4. Press Ctrl-C to end the monitor session. L-PRO 4000 User Manual D02706R02.30...
The problems associated with this incompatibility are quite serious, and result in increased costs for protocol integration and system maintenance. Implementation The L-PRO 4000 conforms to IEC 61850-8-1, commonly referred to as Station Details Bus Protocol. Implementation includes the following documents (“IEC61850 Implementation”...
Page 114
Figure 5.6: Maintenance Interface 2. Select the first option by entering the number 1 followed by <Enter>. The following screen appears. Figure 5.7: Change the network parameters as needed for the particular application L-PRO 4000 User Manual D02706R02.30...
Page 115
“PD Name”. The publisher con- figuration is fixed and defined in the ICD file and available for reading to any IEC61850 client. Subscriber functionality is also fixed and supported for the Virtual Inputs only. D02706R02.30 L-PRO 4000 User Manual...
Record Length, Setting Groups, ProLogic, Group Logic, Output Matrix and Settings summary. Finally, a description of how the settings on the relay can be viewed through the RecordBase View analysis software is provided. Setting Tree Setting Area Figure 6.1: Opening Screen D02706R02.30 L-PRO 4000 User Manual...
Maximize Makes the active window as large as possible Close Closes the active Offliner setting docu- ment Next Switches to the next open Offliner set- ting file, if more than setting file is being edited L-PRO 4000 User Manual D02706R02.30...
Page 119
Displays the Offliner version Toolbar Create a new document. Create a new document of the most recent setting version Open Open an existing document. Open an existing document Save Save the active document. Save the active document D02706R02.30 L-PRO 4000 User Manual...
Page 120
If this option is checked then the LHS Tree Tree view will be hidden Print Print active document. Prints Graphs or the setting summary, depending on which seen is selected About Display program information. Displays the Offliner version L-PRO 4000 User Manual D02706R02.30...
When the user releases the mouse, the trace assumes a new zoom position determined by the area of the zoom coordinates. D02706R02.30 L-PRO 4000 User Manual...
ID menu item. Type this serial number into the L-PRO Serial No. box in the Identification tab display area of Offlin- er Settings. Alternately the user may check the Ignore Serial Num- ber check box to bypass serial number supervision. L-PRO 4000 User Manual D02706R02.30...
Page 123
Use File/Save As to save the sample file to a new file name. Then edit the setting file and the serial number, save it and load it into the relay. D02706R02.30 L-PRO 4000 User Manual...
1. For further instructions refer to the RecordBase View Manual at the back of the printed version of this manual. L-PRO 4000 User Manual D02706R02.30...
The user can choose to ignore the serial number enforcement in the identification screen. The relay only checks for proper relay type and setting version if the ignore serial number has been chosen. D02706R02.30 L-PRO 4000 User Manual...
Page 126
Nominal CT Secondary Current can be set to either 1 A or 5 A. Nominal System Frequency can be set to either 50 Hz or 60 Hz. Ensure setting selection matches that of target the relay. 6-10 L-PRO 4000 User Manual D02706R02.30...
Page 127
These names appear in any fault disturbance records the relay pro- duces. Table 6.4: Analog Inputs Main Voltage LVA, LVB, LVC Main Current LIA, LIB, LIC Aux. Voltage BVA, BVB, BVC Aux. Current IA2, IB2, IC2 Current IA3, IB3, IC3, IA4, IB4, IC4 D02706R02.30 L-PRO 4000 User Manual 6-11...
Page 128
Table 6.5: External Input Names 1 to 20 User-defined Output Contacts Figure 6.8: Output Contacts The Output Contacts are also identified during the setting procedure using meaningful names. The dropout delay time settings are made here. 6-12 L-PRO 4000 User Manual D02706R02.30...
Page 129
SBO (select before operate), Direct Operate, or Direct Operate with no acknowledge to control virtual inputs. Use virtual inputs to: • control circuit breakers • enable or disable reclosing • enable or disable under-frequency load shedding D02706R02.30 L-PRO 4000 User Manual 6-13...
Page 130
• provide interlocking between local/remote supervisory control Setting Groups Figure 6.10: Setting Groups Table 6.8: Setting Groups Setting Groups 1 to 8 User-defined System Parameters Figure 6.11: System Parameters Table 6.9: System Parameters System Parameters 6-14 L-PRO 4000 User Manual D02706R02.30...
Page 131
(e.g. ring bus application), the user must enable ring bus configuration to configure the relay. If enabled, the cur- rents from the 2 sets of CTs are added to the relay to form the line current. For D02706R02.30 L-PRO 4000 User Manual 6-15...
Page 132
SCADA Communication Figure 6.12: SCADA Communication The relay has configurable SCADA communication parameters for both Serial and Ethernet (TCP and UDP). For DNP3 Level 2 (TCP) up to 3 independent Masters are supported. 6-16 L-PRO 4000 User Manual D02706R02.30...
Page 133
The list contains separate sections for Binary Inputs, Binary Outputs, and An- alog Inputs. The list is scrollable by using the scroll control on the right hand side. Configuration - Class Data Figure 6.14: Class Data D02706R02.30 L-PRO 4000 User Manual 6-17...
Page 134
This includes SCADA Communication parameters and (if the SCADA mode is set to DNP) Binary Input, Binary Output, and Analog In- put information including Deadband and Scaling factors. This SCADA Summary screen is scrollable and can be printed. 6-18 L-PRO 4000 User Manual D02706R02.30...
Page 135
This screen displays the record length for each of the two types of recordings provided: fault and swing. Pre-trigger times are configurable between 0.10 to 2.00 seconds for fault records and fixed at 30 seconds for swing records and are included as part of the record length. D02706R02.30 L-PRO 4000 User Manual 6-19...
Page 136
View the active setting group (ASG) from the Terminal Mode, from the front panel or from a record stored by the relay (the active setting group is stored with the record). 6-20 L-PRO 4000 User Manual D02706R02.30...
Page 137
Zero Sequence Impedance (Z0) (ohm) 0.01 to 300.00 (5A) 0.05 to 1500.00 (1A) Zero Sequence Angle (Z0) (deg) 5.0 to 89.0 K0 Override Enable/Disable K0 Magnitude 0.00 to 10.00 K0 Angle (deg) -180.0 to 180.0 Mutual Compensation D02706R02.30 L-PRO 4000 User Manual 6-21...
Page 138
The K factor used is a default factor based on the line parameters (K = [Z ] / 3Z ). The user can specify by selecting K Override Enable. Scheme Selector Figure 6.19: Scheme Selector 6-22 L-PRO 4000 User Manual D02706R02.30...
Page 139
Disabled, EI 1 to EI20, PL1 to PL24 Auxiliary C Phase Disabled, EI 1 to EI20, PL1 to PL24 50N-67F - Overcurrent Carrier Start Action DEF Scheme Only/DEF & Dist Scheme/DEF & ProLogic/DEF, Dist & ProLogic Direction Forward D02706R02.30 L-PRO 4000 User Manual 6-23...
Page 140
0.02 to 0.20 A secondary (1A) Zero Sequence Directional Element Enable/Disable 3V0 Sensitivity Level 1.0 to 10.0 Volts secondary 3I0 Sensitivity Level 0.2 to 2.0 A secondary (5A) 0.04 to 0.40 A secondary (1A) 6-24 L-PRO 4000 User Manual D02706R02.30...
Page 141
Apply ProLogic to multiple inputs to create an output based on qualified in- puts. ProLogic enables up to 24 ProLogic control statements and programs those logics to output contacts. The user can name the function being created D02706R02.30 L-PRO 4000 User Manual 6-25...
Page 142
The processing cycle happens once every half sec- ond (0.5 s). When using ProLogic statements the user must keep in mind that a latch or dropout timer should be used if the initiating condition does not last at least 0.5 seconds. 6-26 L-PRO 4000 User Manual D02706R02.30...
Page 143
Print the entire output matrix by selecting Print under the File menu. This print- out is produced on 2 pages. D02706R02.30 L-PRO 4000 User Manual 6-27...
Page 144
Settings Summary Figure 6.24: Settings Summary Select Settings Summary to view and print the relay settings in text form, for details see “IED Settings and Ranges” in Appendix B.
To edit the setting file associated with the summary, the user must use File/Save As to save the summary to a file. Then close the summary screen and open the setting file for editing. Figure 6.25: View Setting Summary in RecordBase View D02706R02.30 L-PRO 4000 User Manual 6-29...
“IED Settings and Ranges” in Appendix B. Test Equipment • 3 ac voltage sources (variable frequency capability) Requirements • 3 ac current sources • 1 ohmmeter • 1 - 125 Vdc test supply D02706R02.30 L-PRO 4000 User Manual...
Page 148
Control Panel at the Service access level to the front USB Port. Proceed to the Utilities>Analog Input Calibrate. The Calibrate menu leads the user through every analog input and prompts the user to apply the appropriate quantity. Figure 7.1: Enter actual applied signal level L-PRO 4000 User Manual D02706R02.30...
Page 149
The output contacts are toggled from open to closed by pressing the Closed button. Verify the output contact status using an ohmmeter. When ex- Contacts iting this sub-menu, each contact status reverts to the open position. D02706R02.30 L-PRO 4000 User Manual...
• 50BF Breaker Fail • Example of Inputs 3 and 4 being used for Breaker Fail • 81 Over/Under/Rate of Change of Frequency • 25C Sync Check • 79 Recloser • 79-1-3 single pole trip device number L-PRO 4000 User Manual D02706R02.30...
Page 151
7. From the Configuration submenu select Import. 8. Browse to the converted acceptance test file and click on Open. 9. Select the file under Saved Settings list and click on the Load to IED button on the right. D02706R02.30 L-PRO 4000 User Manual...
Page 152
Impedance Characteristics Available in L-PRO (Mho and Quadrilateral) Reactive (x) Forward Characteristic Angle = 90 degrees Line Angle Resistive (R) Directional Reverse Supervision Figure 7.4: MHO Circle (Characteristic Angle = 90) Available for 21P and 21N L-PRO 4000 User Manual D02706R02.30...
Page 153
Figure 7.5: MHO Tomato (Characteristic Angle < 90) Available for 21P and 21N Reactive (x) Forward Characteristic Angle = 90 degrees Line Angle Resistive (R) Reverse Directional Supervision Figure 7.6: MHO Lens (Characteristic Angle > 90) Available for 21P and 21N D02706R02.30 L-PRO 4000 User Manual...
Page 154
PT Ratio - Potential Transformer Ratio Zero Sequence Impedance calculations for phase-to-ground impedance ele- ment tests (using secondary Positive and Zero Sequence Line Impedances): 5.9 80 1.03 j5.81 16.0 74 4.41 j15.38 L-PRO 4000 User Manual D02706R02.30...
Page 156
81-1 46-51 81-2 81-3 Main1 Aux1 Aux 2 50BF- 81-4 Main2 L-PRO 4000 SIMPLIFIED REAR VIEW Main Line Currents Auxilliary Line Currents Main Voltages Auxilliary Voltages Power Supply For Prot./Sync./Rec. These Currents only VA VB VC VN required for Ring Bus...
Page 157
7 Acceptance/Protection Function Test Guide Figure 7.9: Protection Functions Metering Screens D02706R02.30 L-PRO 4000 User Manual 7-11...
Page 158
303, 0.5 A -120 – Ph C: 303 304, 0.5 A +120 Observe: 60 Alarm = Low 4. Instantaneously reduce single-phase voltage to 48 V or less. 60 Alarm = High Contact 2 Closed 7-12 L-PRO 4000 User Manual D02706R02.30...
Page 159
2. Increase any single-phase current to 1.1 A. 3. Reduce single-phase voltage to 0. Observe 60 Alarm remains low. Observe Contact 2 remains open. 4. Reduce all sources to 0. End of 60 test. D02706R02.30 L-PRO 4000 User Manual 7-13...
Page 160
- Phase Current Phase The minimum 3-phase current required is: (Remember: I is the phasor difference between any 2-phase currents; add Delta 5% to ensure the Minimum I Logic is high for this test). DeltaSupervision 7-14 L-PRO 4000 User Manual D02706R02.30...
Page 161
Ph C: 332, 20.0 V +120 Ph N: 333 4. Apply 3-phase currents from 0 to 5.3 A to start the timer (this is 80% of Zone 1 Reach = 64% of the line = 12.4 miles). D02706R02.30 L-PRO 4000 User Manual 7-15...
Page 162
The minimum delta current required = 3.0 A; add 5% to ensure supervision is met: (19) 3.0 105 percent 3.2 A Since B-phase = C-phase, actual minimum current required is equal to 7-16 L-PRO 4000 User Manual D02706R02.30...
Page 163
FaultMin TestMin And using appropriate values, the Minimum Fault Voltage is (23) 7.38 2 1.6 A 23.6V FaultMin where - Minimum Fault Voltage FaultMin - Minimum Fault Test Current TestMin D02706R02.30 L-PRO 4000 User Manual 7-17...
Page 165
For this B-C test a minimum fault voltage of 23.6 V is required as calculated in “B-C Fault Voltage Injections, for details see Table 7.15: B-C Fault Voltage Injections on page 7-19. Select the next highest voltage. In this case 34.5 V (70% reduction) is used. D02706R02.30 L-PRO 4000 User Manual 7-19...
Page 166
For B-C fault adjust Phase B angle toward Phase C angle and adjust Phase C angle toward Phase B angle: B Phase Angle = -120 - 32.5 = -152.5 C Phase Angle = +120 +32.5 = 152.5 7-20 L-PRO 4000 User Manual D02706R02.30...
Page 167
Ph B-C: 302 304, 1.5 A -170 Observe 21P2 Alarm = Low 4. Increase current. At 2.23 to 2.45 A (expect 2.34 A): 21P2 Alarm = High 5. Turn off voltage and current sources. D02706R02.30 L-PRO 4000 User Manual 7-21...
Page 168
This test demonstrates testing a single line (Phase A) to a ground fault. Preliminary calculations Since this is a single-phase test, use the compensated impedance value calcu- lated above; the calculated fault impedance Z fault (29) fault -------------- - fault fault 7-22 L-PRO 4000 User Manual D02706R02.30...
Page 169
Ph A: 300 301, 1.58 A +3.5 Observe 21N2 Pickup = Low 4. Reduce Phase A voltage. At 15.6 to 14.2 V (expect 14.9 V). 21N2 Pickup = High After 400 ms: 21N2 Trip = High D02706R02.30 L-PRO 4000 User Manual 7-23...
Page 170
2. Apply the following 3-phase voltages to the relay main ac V terminals: Ph A: 330, 62.0 V <0 Ph B: 331, 62.0 V <240 Ph C: 332, 62.0 V <120 Ph N: 333 7-24 L-PRO 4000 User Manual D02706R02.30...
Page 171
3 conditions to be met: (27V1, NOT (Zone 2 OR Zone 4R), NOT Loss of Potential). In this case a Virtual Input is set up to simulate the Permissive Trip Receive contact via ProLogic. Figure 7.17: Scheme Selector Settings (Offliner) D02706R02.30 L-PRO 4000 User Manual 7-25...
Page 172
Figure 7.18: Virtual Input Control Observe Relay Target: “POTT Trip (WI): 0.0 mi. Note: The 0.0 mi indicates that there was 0 impedance measured due to 0 line voltage being applied. End of Weak Infeed test. 7-26 L-PRO 4000 User Manual D02706R02.30...
Page 173
Switch On To Fault can be configured to operate based on two methods. Fault Test 1. Close Command (Circuit breaker close pulse) 2. Status Monitoring (Circuit breaker status) Figure 7.19: Switch On To Fault Logic D02706R02.30 L-PRO 4000 User Manual 7-27...
Page 174
Both inputs shall be changed at the same time. Analog input can be delayed by 1 – 3 cycles to simulate the delay in circuit breaker operation. 3. Observe target Switch On To Fault on A. End of Switch On To Fault Close Command test. 7-28 L-PRO 4000 User Manual D02706R02.30...
Page 175
Both inputs shall be changed at the same time. Analog input can be delayed by 1 – 3 cycles to simulate the delay in circuit breaker operation. 4. Observe target Switch On To Fault on A. End of Switch On To Fault Status Monitoring test. D02706R02.30 L-PRO 4000 User Manual 7-29...
Page 176
Z - Fault Impedance - Phase Voltage Phase - Phase Current Phase The minimum 3-phase current required must be greater than the I 1Supervision Setting (3.0 A). Add 5% to ensure that the supervision is met: 7-30 L-PRO 4000 User Manual D02706R02.30...
Page 177
2. Apply balanced 3-phase nominal voltages (66.4 V) to the relay terminals: Ph A: 330, 66.4 V Ph B: 331, 66.4 V -120 Ph C: 332, 66.4 V +120 Ph N: 333 D02706R02.30 L-PRO 4000 User Manual 7-31...
Page 178
1. In Relay Control Panel access Utilities>Virtual Inputs. 2. Select corresponding virtual input for “Switch to SG2”. 3. Click on Pulse On button to execute the command. 4. The Active Setting Group will become Group 2. 7-32 L-PRO 4000 User Manual D02706R02.30...
Page 179
At 31.0 to 29.0 V (expect 30 V): 27 Aux U/V = High Contact 13 closed 27 Main U/V remains Low Contact 14 open 4. With A Phase voltage still reduced, reduce B and C phase V: D02706R02.30 L-PRO 4000 User Manual 7-33...
Page 180
Ph A: 324 & 330, 66.4 V Ph B: 331, 66.4 V -120 Ph C: 332, 66.4 V +120 Ph N: 327 and 333 Observe: 59 Main O/V = Low 59 Aux O/V = Low 7-34 L-PRO 4000 User Manual D02706R02.30...
Page 181
If Directional or combined, T must be greater than 10 ms Out 6 50 3IO Alarm Timer is active, only if it's directional or combined 51N directional control Out 7 51 3IO Figure 7.25: Neutral Instantaneous and Time Overcurrent Logic (50N/51N) D02706R02.30 L-PRO 4000 User Manual 7-35...
Page 183
51 Alarm = High 4. Continue to raise current. At 14.3 to 15.8 A (expect 15 A): 50 Trip = High Contact 10 = Closed 5. Turn current off. 51 Alarm = Low 50 Trip = Low D02706R02.30 L-PRO 4000 User Manual 7-37...
Page 184
50 ILpos (4% I nominal RMS fixed) 50N directional control 50N Reverse Non-directional 46-51 Forward 46-51 directional control 46-51 Reverse Non-directional 46-50 Forward 46-50 directional control 46-50 Reverse Non-directional Figure 7.27: Directional Element Logic 7-38 L-PRO 4000 User Manual D02706R02.30...
Page 185
6. Slowly ramp the current phase angle in positive direction (i.e. less lag): At +5 to +15 (expect +10 51 Pickup Alarm = Low 7. Turn off voltage and current sources. End of 50/51 test. D02706R02.30 L-PRO 4000 User Manual 7-39...
Page 186
Positive sequence (I1), Negative Sequence (I2), Zero Sequence (3I0) are cal- culated by using the following equations: (35) --------------------------------------- where a = 1 (36) --------------------------------------- - where a = 1 7-40 L-PRO 4000 User Manual D02706R02.30...
Page 187
2. Set timer start from single-phase 0.0 A to 12.00 A transition (this equates to 4x pickup). Time Delay ------------------------------------- - – Multiple 5.64 5.64 0.02434 ------------- - 0.02434 --------- - 1.201s (39) – D02706R02.30 L-PRO 4000 User Manual 7-41...
Page 188
Directional Supervision is exceeded, the 46 drops out as it has now become Directional (forward) only. Testing is accomplished by applying 3-phase balanced I quantities sufficient to pickup the 46 element and then increasing the magnitude of any single- phase. 7-42 L-PRO 4000 User Manual D02706R02.30...
Page 189
Directional Element 50ILpos Threshold Test Procedure 1. In Relay Control Panel access relay Metering>Protection. Monitor: 46-50 Trip 2. Apply single-phase polarizing voltage to the relay terminals: – Ph A: 330 333, 66.4 V D02706R02.30 L-PRO 4000 User Manual 7-43...
Page 190
Main and Aux. Breaker Fails are set to be initiated via the Output Matrix from 50LS Pickup (1.0 A Main and Aux and 0 time delay). Note: Requires a mini- mum of 0.2 A on any phase to arm Breaker Fail. 7-44 L-PRO 4000 User Manual D02706R02.30...
Page 191
50LS using ProLogic. ProLogic 1: This boolean equation used to initiate and operate as a Breaker Fail for 52-3 (Input 3). Current above the 50LS threshold arms one input of the D02706R02.30 L-PRO 4000 User Manual 7-45...
Page 192
2. In the drop down list of virtual inputs, select the corresponding virtual input to “Switch to SG3”. 3. Cursor over to Action and select Pulse On. 4. Click on Pulse On to execute this command, the Active Setting Group is Group 3 now. 7-46 L-PRO 4000 User Manual D02706R02.30...
Page 193
333, 66.4 V @ 60 Hz (@ 50 Hz for 50 Hz Relay) 81-1 = Low 81-2 = Low 3. Ramp up the voltage frequency. At 60.499 to 60.501 Hz (50.499 to 50.501 Hz for 50 Hz relay): 81-1 = High D02706R02.30 L-PRO 4000 User Manual 7-47...
Page 194
Contact 9 = Open 8. Restore nominal frequency. 9. Ramp the frequency at a rate of -1.01 Hz/s for a duration of 2 seconds. Observe: 81-3 = Low 81-4 = High Contact 9 = Closed 7-48 L-PRO 4000 User Manual D02706R02.30...
Page 195
5. Set timer start on instantaneous frequency shift 66.4 V @ 60 Hz to 59.4 Hz transition. Expect time delay of 500 ms + approximately 1.5 cycle detection time. 6. Apply the frequency shift. Confirm the expected time delay. Target “81-2” End of 81 test. D02706R02.30 L-PRO 4000 User Manual 7-49...
Page 196
59 Vmain (Positive Seq, 20 V Fixed) 27 Vsync (Positive Seq, 20 V Fixed) Dead Main-Dead Sync Enabled 27 Vmain (Positive Seq, 20 V Fixed) 27 Vsync (Positive Seq, 20 V Fixed) Figure 7.33: Synchronism Check Logic (25/27/59) 7-50 L-PRO 4000 User Manual D02706R02.30...
Page 197
19 difference (expect 20 25/27/59 = High Contact 10 = Closed (after 200 ms) 7. Slowly ramp down the auxiliary voltage magnitude. At 41.0 to 39.0 V (expect 40 V): 25/27/59 = Low D02706R02.30 L-PRO 4000 User Manual 7-51...
Page 198
External Input 3 and initiates the 79 operation. Connect a 125 Vdc supply to the relay output and input terminals as shown, for details see Figure 7.34: Test Connections for 4-Shot Recloser Test on page 7- 7-52 L-PRO 4000 User Manual D02706R02.30...
Page 199
(closes Out 5) via ProLogic 3. Figure 7.35: Simulating Main Breaker Close Command using Virtual Input in ProLogic ProLogic 2: This equation is used to reset the Main Breaker Status via ProLog- ic 3 (Opens Out 5). D02706R02.30 L-PRO 4000 User Manual 7-53...
Page 200
2 (Breaker Status Reset) is activated. Figure 7.37: Main Breaker Status ProLogic 4: This equation applies the External Trip (Closes Out 7), 10 seconds after the Breaker Status (ProLogic 3) goes high (i.e. Main Breaker Status = Closed). 7-54 L-PRO 4000 User Manual D02706R02.30...
Page 201
Main Breaker Status (Out 5), then Auxiliary Breaker Sta- tus (Out 6) to simulate main and auxiliary breaker closed status. This latching function resets when the 79 Lead Lockout goes low. D02706R02.30 L-PRO 4000 User Manual 7-55...
Page 202
Figure 7.40: Using Virtual Input to simulate SCADA Recloser Lockout Reset ProLogic 7: This equation is intended only for giving indication of when the 79 Lockout is reset. This indication, along with ProLogic 6, proves the 79 Reset timer (TD). Figure 7.41: Main Recloser Lockout Reset Indication ProLogic 8: This equation closes Out 6 to simulate auxiliary breaker closed status from SCADA breaker close command OR auxiliary recloser operation.
Page 203
3. Pulse On (This simulates a “SCADA 79 Lockout Reset Command”.) Observe the relay Target: “Init LO Reset VI: PL6” After 12 Seconds, Target: “Main LO is Reset: PL7” End of 79 Reset procedure. D02706R02.30 L-PRO 4000 User Manual 7-57...
Page 204
4. For detail of shot numbers, etc. observe the sequence of events by viewing Main Menu>Events 5. To perform this test again, reset the Lockout as per 79 Reset Procedure above, then repeat the 79 test procedure. End of 79 test. 7-58 L-PRO 4000 User Manual D02706R02.30...
Shielded cable is recommended, for pin-out see “Communication Port Details” on page 2-15. An adapter is available for connecting an external modem to Port 123 for de- tails see “Modem Link” on page 2-7. D02706R02.30 L-PRO 4000 User Manual...
Page 206
IRIG-B Wiring The relay accepts both modulated and unmodulated IRIG-B standard time sig- nals with or without the IEEE 1344 extensions. The IRIG-B connector on the back of the relay is BNC type. L-PRO 4000 User Manual D02706R02.30...
250 events circular log with 1ms resolution When event auto save is enabled, a compressed event record is created every 250 events. Record Capacity 75 records of a combination of transient, swing and optionally event records D02706R02.30 L-PRO 4000 User Manual Appendix A-1...
Page 208
33.6 Kbps, V.32 bis Optional internal modem SCADA Interface IEC61850 (Ethernet) or DNP3 (RS-232 or Rear port Ethernet) or Modbus (RS-232) Time Sync IRIG-B, BNC connector Modulated or unmodulated, auto-detect B003,B004,B123 and B124 Time Codes Appendix A-2 L-PRO 4000 User Manual D02706R02.30...
Page 209
25C. The relay can detect loss of re-establishment of external time source and automatically switch between internal and external time. Synchronization Accuracy Sampling clocks synchronized with the time source (internal or external) D02706R02.30 L-PRO 4000 User Manual Appendix A-3...
Page 210
±2.5% or ±1.5 cycle directional Frequency Timer ±2.5% of set value plus 1.25 cycles to 1.75 cycles of inherent delay (fixed level) at 2x pickup, error <40 ms (df/dt) at 0.1 Hz/s above pickup, error <100 ms Appendix A-4 L-PRO 4000 User Manual D02706R02.30...
Page 211
10 Vrms: 0.150 - 80 MHz Earth ground ports 10 Vrms: 0.150 - 80 MHz IEC/EN 60255-22-7 Power frequency Binary input ports: Class A Differential = 150 Vrms Common = 300 Vrms D02706R02.30 L-PRO 4000 User Manual Appendix A-5...
Page 212
30 V continuous, 300 V for 1s IEC/EN 61000-4-17 Ripple on dc power supply dc power port 1000% Note:The L-PRO 4000 is available with 5 or 1 amp current input. All current specifications change accordingly. Appendix A-6 L-PRO 4000 User Manual D02706R02.30...
50 Hz and 60 Hz. L-PRO Phase Mho Operating Times Phase-to-Phase Faults SIR 30 SIR 10 SIR 1 SIR 0.1 100% Fault Location (%of Z1 Reach) Figure A.1: Phase Mho Operating Times Phase-to-Phase Faults D02706R02.30 L-PRO 4000 User Manual Appendix A-7...
Page 214
Figure A.2: Ground Mho Operating Times Single Line -to-Ground Faults L-PRO Quadrilateral Operating Times Single Line-to-Ground Faults SIR 30 SIR 10 SIR 1 SIR 0.1 100% Fault Location (%of Z1 Reach) Figure A.3: Quadrilateral Operating Times Single Line-to-Ground Faults Appendix A-8 L-PRO 4000 User Manual D02706R02.30...
3.645 ms 2.083 ms 3.993 ms For a setting of 6, it will take between 1.042 and 1.909 ms for an External Input to be declared as high. The default setting is 4. D02706R02.30 L-PRO 4000 User Manual Appendix A-11...
Not Installed Comments Comments Date Created-Modified 10/29/2012 10:01 Station Name Station Name Station Number Location Location Line D245 Analog Input Names Main Voltage A Main Voltage B Main Voltage C Main Line Current A D02706R02.30 L-PRO 4000 User Manual Appendix B-1...
Page 220
Output2 ( Out Spare 2 ) 0.00 to 1.00 Output3 ( Out Spare 3 ) 0.00 to 1.00 Output4 ( Out Spare 4 ) 0.00 to 1.00 Output5 ( Out Spare 5 ) 0.00 to 1.00 Appendix B-2 L-PRO 4000 User Manual D02706R02.30...
Page 221
Virtual Input 29 VI 30 Virtual Input 30 Setting Group Names Setting Group 1 Setting Group 1 Setting Group 2 Setting Group 2 Setting Group 3 Setting Group 3 Setting Group 4 Setting Group 4 D02706R02.30 L-PRO 4000 User Manual Appendix B-3...
Page 222
0.01 to 300.00 Zero Sequence Angle (Z0) 5.0 to 89.0 K0 Override Disabled K0 Magnitude 0.67 0.00 to 10.00 K0 Angle -180.0 to 180.0 KM1 Mutual Line 1 Enabled KM1 Magnitude 0.10 to 2.00 Appendix B-4 L-PRO 4000 User Manual D02706R02.30...
Page 223
0.2 to 50.0 Pickup Delay 0.02 0.005 to 99.99 seconds 50N-67R - Overcurrent Carrier Block Action <diabled> Direction Reverse 3I0 Pickup 0.2 to 50.0 Pickup Delay 0.02 0.005 to 99.99 seconds 52 - Breaker Status D02706R02.30 L-PRO 4000 User Manual Appendix B-5...
Page 224
90.0 70.0 to 140.0 Pickup Delay 0.00 to 99.99 Delta Current Supervision 0.2 to 50.0 21P, Zone 4 Disabled Type Quadrilateral Forward Reach 0.00 0.00 to 66.00 Reverse Reach 2.00 0.00 to 66.00 Appendix B-6 L-PRO 4000 User Manual D02706R02.30...
Page 225
Right Reach (R2) 15.00 0.05 to 66.00 Mho Char. Angle 90.0 70.0 to 140.0 Pickup Delay 0.00 to 99.99 Phase Current Supervision 0.2 to 50.0 3I0 Supervision 0.2 to 50.0 21N, Zone 3 Disabled D02706R02.30 L-PRO 4000 User Manual Appendix B-7...
Page 226
3I0 Blocking 2.5 A Blocking Reset Time 2.00 s LHS Outer (R1) 27.0 LHS Inner (R2) 18.0 RHS Inner (R3) 18.0 RHS Outer (R4) 27.0 Top Outer (X4) 27.0 Top Inner (X2) 18.0 Appendix B-8 L-PRO 4000 User Manual D02706R02.30...
Page 227
Default Gate Default pickup value 5.0 s Gate switch option AND/OR 59N Definite Time Delay Disabled 59N Inverse Time Delay Disabled 27 Main Disabled Default pickup value 25.0 V Pickup delay 5,00 s D02706R02.30 L-PRO 4000 User Manual Appendix B-9...
Page 228
0.200 s Main Breaker current pickup 1.00 A 50BF Aux Disabled Main pickup delay 1 0.200 s Main pickup delay 2 0.200 s Main Breaker current pickup 1.00 A Disabled Disabled Disabled Disabled Appendix B-10 L-PRO 4000 User Manual D02706R02.30...
Page 229
Reverse Reach 0.00 to 66.00 Left Reach (R1) 0.05 to 66.00 Right Reach (R2) 0.05 to 66.00 Mho Char. Angle 70.0 to 140.0 Pickup Delay 0.00 to 99.99 Delta Current Supervision 0.2 to 50.0 D02706R02.30 L-PRO 4000 User Manual Appendix B-11...
Page 230
Left Reach (R1) 0.05 to 66.00 Right Reach (R2) 0.05 to 66.00 Mho Char. Angle 70.0 to 140.0 Pickup Delay 0.00 to 99.99 Phase Current Supervision 0.2 to 50.0 3I0 Supervision 0.2 to 50.0 Appendix B-12 L-PRO 4000 User Manual D02706R02.30...
Page 231
3I0 Supervision 0.2 to 50.0 68 - Power Swing Block/Trip: Zone 5 Mode Zone 1 Blocking Disabled Zone 2 Blocking Disabled Zone 3 Blocking Disabled Zone 4 Blocking Disabled Zone 5 Blocking Disabled D02706R02.30 L-PRO 4000 User Manual Appendix B-13...
Page 232
1.0 to 50.0 Pickup Delay 0.00 to 10.00 Frequency Difference Disabled Frequency Difference 0.010 to 2.000 Dead Main Live Aux. (DMLA) Disabled Live Main Dead Aux. (LMDA) Disabled Dead Main Dead Aux. (DMDA) Disabled Appendix B-14 L-PRO 4000 User Manual D02706R02.30...
Page 233
Pickup 1.0 to 138.0 Pickup Delay 0.00 to 10.00 59 Auxiliary Disabled Gate Switch Pickup 1.0 to 138.0 Pickup Delay 0.00 to 10.00 59N - Zero Sequence OverVoltage 59N Definite Time Delay Disabled D02706R02.30 L-PRO 4000 User Manual Appendix B-15...
Page 234
81 - Over/Under Frequency Fixed level/Rate of change 81-1 Disabled Pickup 57.600 [50.000, 59.995] or [60.005, 70.000] Pickup Delay 0.05 to 99.99 81-2 Disabled Pickup 57.000 [50.000, 59.995] or [60.005, 70.000] Pickup Delay 0.05 to 99.99 Appendix B-16 L-PRO 4000 User Manual D02706R02.30...
Page 235
50/51/67 - Phase Overcurrent Disabled Directional Control Directional Pickup 0.50 to 150.00 Pickup Delay 0.01 to 99.99 Disabled Directional Control Directional Pickup 7.50 0.25 to 25.00 Curve Type IEC STD Inverse, TMS:1,A:0.14,B:0,p:0.02,TR:13. 50,Alpha:0.00,Beta:180.00 0.01 to 10.00 D02706R02.30 L-PRO 4000 User Manual Appendix B-17...
Page 236
51N Pickup Time Multiplier times setting 0.10 to 2.00 46-50/46-51/67 - Negative Sequence Overcur- rent 46-50 Disabled Directional Control Directional Pickup 2.50 0.50 to 50.00 A Pickup Delay 0.01 to 99.99 46-51 Disabled Directional Control directional Appendix B-18 L-PRO 4000 User Manual D02706R02.30...
Page 237
<Unused = 0> ProLogic 2 [ProLogic 2] [ProLogic 2] Disabled Pickup Delay 0.00 to 999.00 Dropout Delay 0.00 to 999.00 Operator 1 Input A <Unused = 0> Operator 2 Input B <Unused = 0> D02706R02.30 L-PRO 4000 User Manual Appendix B-19...
Page 238
<Unused = 0> Operator 5 Input E <Unused = 0> ProLogic 5 [ProLogic 5] [ProLogic 5] Disabled Pickup Delay 0.00 to 999.00 Dropout Delay 0.00 to 999.00 Operator 1 Input A <Unused = 0> Appendix B-20 L-PRO 4000 User Manual D02706R02.30...
Page 239
<Unused = 0> Operator 4 Input D <Unused = 0> Operator 5 Input E <Unused = 0> ProLogic 8 [ProLogic 8] [ProLogic 8] Disabled Pickup Delay 0.00 to 999.00 Dropout Delay 0.00 to 999.00 D02706R02.30 L-PRO 4000 User Manual Appendix B-21...
Page 240
Input B <Unused = 0> Operator 3 Input C <Unused = 0> Operator 4 Input D <Unused = 0> Operator 5 Input E <Unused = 0> ProLogic 11 [ProLogic 11] [ProLogic 11] Disabled Appendix B-22 L-PRO 4000 User Manual D02706R02.30...
Page 241
Input A <Unused = 0> Operator 2 Input B <Unused = 0> Operator 3 Input C <Unused = 0> Operator 4 Input D <Unused = 0> Operator 5 Input E <Unused = 0> D02706R02.30 L-PRO 4000 User Manual Appendix B-23...
Page 242
ProLogic 14 [ProLogic 14] [ProLogic 14] Disabled Pickup Delay 0.00 to 999.00 Dropout Delay 0.00 to 999.00 Operator 1 Input A <Unused = 0> Operator 2 Input B <Unused = 0> Operator 3 Input C <Unused = 0> Operator 4 Input D <Unused = 0>...
Page 243
[ProLogic 19] Disabled Pickup Delay 0.00 to 999.00 Dropout Delay 0.00 to 999.00 Operator 1 Input A <Unused = 0> Operator 2 Input B <Unused = 0> Operator 3 Input C <Unused = 0> D02706R02.30 L-PRO 4000 User Manual Appendix B-25...
Page 244
<Unused = 0> ProLogic 22 [ProLogic 22] [ProLogic 22] Disabled Pickup Delay 0.00 to 999.00 Dropout Delay 0.00 to 999.00 Operator 1 Input A <Unused = 0> Operator 2 Input B <Unused = 0> Appendix B-26 L-PRO 4000 User Manual D02706R02.30...
Page 245
Operator 5 Input E <Unused = 0> Group Logic 1 [Group Logic 1] [Group Logic 1] Disabled Setting Group to Activate none Pickup Delay 0 to 999 Operator 1 Input A <Unused = 0> D02706R02.30 L-PRO 4000 User Manual Appendix B-27...
Page 246
Operator 2 Input B <Unused = 0> Operator 3 Input C <Unused = 0> Operator 4 Input D <Unused = 0> Operator 5 Input E <Unused = 0> Group Logic 2 [Group Logic 2] [Group Logic 2] Disabled Setting Group to Activate none Pickup Delay 0 to 999...
Page 247
<Unused = 0> Operator 3 Input C <Unused = 0> Operator 4 Input D <Unused = 0> Operator 5 Input E <Unused = 0> Group Logic 7 [Group Logic 7] [Group Logic 7] Disabled D02706R02.30 L-PRO 4000 User Manual Appendix B-29...
Page 248
Input A <Unused = 0> Operator 2 Input B <Unused = 0> Operator 3 Input C <Unused = 0> Operator 4 Input D <Unused = 0> Operator 5 Input E <Unused = 0> Appendix B-30 L-PRO 4000 User Manual D02706R02.30...
Page 249
Pickup Delay 0 to 999 Operator 1 Input A <Unused = 0> Operator 2 Input B <Unused = 0> Operator 3 Input C <Unused = 0> Operator 4 Input D <Unused = 0> D02706R02.30 L-PRO 4000 User Manual Appendix B-31...
Page 250
[Group Logic 15] Disabled Setting Group to Activate none Pickup Delay 0 to 999 Operator 1 Input A <Unused = 0> Operator 2 Input B <Unused = 0> Operator 3 Input C <Unused = 0> Appendix B-32 L-PRO 4000 User Manual D02706R02.30...
Page 251
Input A <Unused = 0> Operator 2 Input B <Unused = 0> Operator 3 Input C <Unused = 0> Operator 4 Input D <Unused = 0> Operator 5 Input E <Unused = 0> D02706R02.30 L-PRO 4000 User Manual Appendix B-33...
Page 252
Appendix B IED Settings and Ranges Appendix B-34 L-PRO 4000 User Manual D02706R02.30...
This board provides 9 digital input channels. Inputs are optically isolated, ex- Board (DIB) ternally wetted, and factory preset to the customer’s requested voltage level of 48, 110/125 or 220/250 Vdc. This board interfaces to the MPB. D02706R02.30 L-PRO 4000 User Manual Appendix C-1...
Page 254
The GFPDB provides the 240x128 monochrome graphics front panel display Panel Display and the keypad. The keypad is used to navigate the menus on the display to Board (GFPDB) control relay operation by a local user. Appendix C-2 L-PRO 4000 User Manual D02706R02.30...
• ABCG 46-51: Trip 46-50: Trip 51 ABC:Trip The possible phase information will be: • A • B 50 ABC:Trip • C • AB • BC • CA • ABC 51N: Alarm 46-51: Alarm D02706R02.30 L-PRO 4000 User Manual Appendix D-1...
Page 256
• A • B 27 Aux. ABC: Trip • C • AB 59 Main ABC: Trip • BC • CA 59 Aux. ABC: Trip • ABC 50LS Main ABC: Trip 50LS Aux. ABC: Trip Appendix D-2 L-PRO 4000 User Manual D02706R02.30...
Page 257
The DSP has an algorithm that detects continuous dc levels on the analog in- due to DC puts and initiates alarms and relay output contact blocking when the measured Offset Detector dc level exceeds the Alarm or Block level. The Alarm level is intended to pro- D02706R02.30 L-PRO 4000 User Manual Appendix D-3...
Page 258
The Alarm condition is allowed to reset if the continuous dc level drops below the pickup level. The Block condition has no reset level. If power is cycled to the relay it will go into its normal state until the continuous dc level is detected again. Appendix D-4 L-PRO 4000 User Manual D02706R02.30...
Page 259
Appendix D Event Messages Self Check Fail appears as “Aux. Failure Alarm” in the settings ver- sions before V 10. D02706R02.30 L-PRO 4000 User Manual Appendix D-5...
68 Power Swing 0: Off (inactive) 1: On (active) Z Circle Trigger 0: Off (inactive) 1: On (active) 51N Trip 0: Off (inactive) 1: On (active) 50N Trip 0: Off (inactive) 1: On (active) D02706R02.30 L-PRO 4000 User Manual Appendix E-1...
Page 262
Group Logic 15 0: Off (inactive) 1: On (active) Group Logic 16 0: Off (inactive) 1: On (active) 79 Initiated 0: Off (inactive) 1: On (active) 79 Blocked 0: Off (inactive) 1: On (active) Appendix E-2 L-PRO 4000 User Manual D02706R02.30...
Page 263
0: Off (inactive) 1: On (active) External Input 11 Change of state latch 10267 0: Off (inactive) 1: On (active) External Input 12 Change of state latch 10268 0: Off (inactive) 1: On (active) D02706R02.30 L-PRO 4000 User Manual Appendix E-3...
Page 264
1: On (active) Virtual Input 28 10540 0: Off (inactive) 1: On (active) Virtual Input 29 10541 0: Off (inactive) 1: On (active) Virtual Input 30 10542 0: Off (inactive) 1: On (active) Appendix E-4 L-PRO 4000 User Manual D02706R02.30...
Page 266
Ib summated Angle 40314 Degrees Ic summated Magnitude 40315 Ic summated Angle 40316 Degrees Self check fail parameter 40317 Read Input Register (Function Code 04) No input registers supported. Response from IED indicates “ILLEGAL FUNCTION.” Appendix E-6 L-PRO 4000 User Manual D02706R02.30...
Page 267
A fixed response is returned by the IED, including system model, version and issue numbers. Channel Type Bytes Value Model Number Read Only 0 and 1 0xFA0 = 4000 decimal Version Number Read Only 2 and 3 Version number D02706R02.30 L-PRO 4000 User Manual Appendix E-7...
Page 268
1970. Each of these 16-bit reg- isters contains an 8-bit portion of a 32-bit time value. Register 40573 contains the upper most 8 bits, and register 40576 contains the lowest 8 bits. Appendix E-8 L-PRO 4000 User Manual D02706R02.30...
(variations 1, 2, 3 and 4) • Analog Input events with time (variations 3 and 4) • Fault Location information as analog readings • Event Log messages as Object groups 110 and D02706R02.30 L-PRO 4000 User Manual Appendix F-1...
Page 272
*The Device Profile Config. Values contains only the Current Value column. 1.1.13 Connections Serial (complete section 1.2) Supported: IP Networking (complete section 1.3) Other, explain ______________________ Appendix F-2 L-PRO 4000 User Manual D02706R02.30...
Page 273
Not Supported Status: Fixed at_________ seconds Configurable, range _____ to ______ seconds Configurable, selectable from __,__,__ seconds Configurable, other, describe______________ 1.2.6 Supports DNP3 Collision Avoidance: Yes, explain ______________________ D02706R02.30 L-PRO 4000 User Manual Appendix F-3...
Page 274
Configurable, Selectable from ___, ___, ___ ms Configurable, other, describe______________ Variable, explain ____ 1.2.8 Inter-character gaps in None (always transmits with no inter-character transmission: gap) Maximum _____ bit times Maximum _____ ms Appendix F-4 L-PRO 4000 User Manual D02706R02.30...
Page 275
1.3.12 Destination UDP port None for initial unsolicited null Fixed at 20,000 responses (UDP only Configurable, range _______ to _______ Outstations): Configurable, selectable from ____,____,____ Configurable, other, describe______________ D02706R02.30 L-PRO 4000 User Manual Appendix F-5...
Page 276
Method 3 (browsing for static data) - optional 1.3.15 Time synchronization DNP3 LAN procedure (function code 24) support: DNP3 Write Time (not recommended over LAN) Other, explain _________________________ Not Supported Appendix F-6 L-PRO 4000 User Manual D02706R02.30...
Page 277
1.4.9 Maximum number of Fixed at 292 octets that can be Configurable, range ________ to _______ Received in a Data Link Configurable, selectable from ____,____,____ Frame: Configurable, other, describe______________ D02706R02.30 L-PRO 4000 User Manual Appendix F-7...
Page 278
Variable, explain _______________________ 1.5.8 Supports mixing object Not applicable - controls are not supported Analog Outputs groups (AOBs, CROBs not supported and Data Sets) in the same control request: Appendix F-8 L-PRO 4000 User Manual D02706R02.30...
Page 279
• Separate buffer for the Fault Locator events, size 100. 1.6.7 Sends Multi-Fragment Responses: 1.6.8 DNP Command Assign Class Not supported Settings preserved Analog Deadbands through a device reset: Data Set Prototypes Data Set Descriptors D02706R02.30 L-PRO 4000 User Manual Appendix F-9...
Page 280
Appendix F DNP3 Device Profile 1.7 Outstation Unsolicited If configurable, Capabilities Current Value Response Support list methods 1.7.1 Supports Unsolicited Not Supported Reporting: Configurable, selectable from On and Off Appendix F-10 L-PRO 4000 User Manual D02706R02.30...
Page 281
1.8.8 Maximum Event Time- • 0.1736 ms for tag error for local I/O 60Hz sys- other than Binary and tems Double-bit data types • 0.2083 ms for (ms): 50 Hz sys- tems D02706R02.30 L-PRO 4000 User Manual Appendix F-11...
Page 282
2. Binary Input data points are user selectable; the data points avail- Notes able in the device for any given Binary Input point selection can be obtained through the L-PRO Offliner software (see SCADA Setting Summary). Appendix F-12 L-PRO 4000 User Manual D02706R02.30...
Page 283
Virtual Input 17 Inactive Active Virtual Input 18 Inactive Active Virtual Input 19 Inactive Active Virtual Input 20 Inactive Active Virtual Input 21 Inactive Active Virtual Input 22 Inactive Active Virtual Input 23 Inactive Active D02706R02.30 L-PRO 4000 User Manual Appendix F-13...
Page 284
Inactive Active 68 Out of Step Inactive Active 51N Trip Inactive Active 50N Trip Inactive Active 46-51 Trip Inactive Active 46-50 Trip Inactive Active SOTF Inactive Active Distance Comm Scheme Trip Inactive Active Appendix F-14 L-PRO 4000 User Manual D02706R02.30...
Page 285
Inactive Active ProLogic6 Inactive Active ProLogic7 Inactive Active ProLogic8 Inactive Active ProLogic9 Inactive Active ProLogic10 Inactive Active ProLogic11 Inactive Active ProLogic12 Inactive Active Output Contact 1 Open Closed Output Contact 2 Open Closed D02706R02.30 L-PRO 4000 User Manual Appendix F-15...
Page 286
68 OutBlinder Alarm Inactive Active 68 InBlinder Alarm Inactive Active 25/27/59 Sync Check Inactive Active 50BF-1 Aux Inactive Active 50BF-2 Aux Inactive Active 50BF Initiate Inactive Active 79 – 3 Phase Initiated Inactive Active Appendix F-16 L-PRO 4000 User Manual D02706R02.30...
Page 287
Inactive Active ProLogic21 Inactive Active ProLogic22 Inactive Active ProLogic23 Inactive Active ProLogic24 Inactive Active IRIG-B Signal Loss Inactive Active 167* 27 Main A Trip Inactive Active 168* 27 Main B Trip Inactive Active D02706R02.30 L-PRO 4000 User Manual Appendix F-17...
Page 288
Active 21N5 Trip Inactive Active 21P5 Alarm Inactive Active 21N5 Alarm Inactive Active 59N Def Trip Inactive Active 59N Inv Trip Inactive Active 59N Def Alarm Inactive Active 59N Inv Alarm Inactive Active Appendix F-18 L-PRO 4000 User Manual D02706R02.30...
Page 289
Appendix F DNP3 Device Profile 60 CTS Main Inactive Active 60 CTS Aux Inactive Active Load Encroachment Inactive Active D02706R02.30 L-PRO 4000 User Manual Appendix F-19...
Page 290
Complete list is L-PRO Offliner Output Status/Control Configurable shown in the relay output block Other, explain_____________________ table below; (CROB) Point List: points excluded from the default configuration are marked with ‘*’ Appendix F-20 L-PRO 4000 User Manual D02706R02.30...
Page 291
None Pulse duration fixed at 1 s Virtual Input 4 Inactive Active None None Pulse duration fixed at 1 s Virtual Input 5 Inactive Active None None Pulse duration fixed at 1 s D02706R02.30 L-PRO 4000 User Manual Appendix F-21...
Page 292
Virtual Input 30 Inactive Active None None Pulse duration fixed at 1 s Get Next Fault Inactive Active None None Pulse duration fixed Event at 1 s Output Contact 15 Inactive Active None None Appendix F-22 L-PRO 4000 User Manual D02706R02.30...
Page 293
Output Contact 17 Inactive Active None None Output Contact 18 Inactive Active None None Output Contact 19 Inactive Active None None Output Contact 20 Inactive Active None None Output Contact 21 Inactive Active None None D02706R02.30 L-PRO 4000 User Manual Appendix F-23...
Page 294
Fixed, list shown in table below Complete list is L-PRO Offliner Input Point List: Configurable shown in the Other, explain_____________________ table below; points excluded from the default configuration are marked with ‘*’ Appendix F-24 L-PRO 4000 User Manual D02706R02.30...
Page 296
Not used Retained for legacy applica- tions Not used Retained for legacy applica- tions Not used Retained for legacy applica- tions Not used Retained for legacy applica- tions Active Setting Group Number Appendix F-26 L-PRO 4000 User Manual D02706R02.30...
Page 297
Maximal values are calculated as (2 * Configured Nominal / Multiplier) for voltage channels and as (40 * Configured Nominal / Multiplier) for current channels (see Note 2 above for the nominal definitions). D02706R02.30 L-PRO 4000 User Manual Appendix F-27...
Page 300
Analog Input Event - 16-bit with time (read) 06 (no range, or all) (response) 17, 28 (index) 07, 08 (limited qty) Analog Output Status - Any Varia- (read) 06 (no range, or all) (response) tion Appendix F-30 L-PRO 4000 User Manual D02706R02.30...
Page 301
(read) 06 (no range, or all) (response) (limited qty) No Object (function code only) (cold restart) (response) No Object (function code only) (warm restart) (response) No Object (function code only) (delay meas.) (response) D02706R02.30 L-PRO 4000 User Manual Appendix F-31...
1. IRIG-B and comm ports shown separately on L-PRO rear panel layout drawing. 2. All output relays can be programmed to operate on any relay function. 3. All outputs are rated tripping duty, interrupting via breaker aux "a" contact Figure J.1: L-PRO DC Schematic D02706R02.30 L-PRO 4000 User Manual Appendix J-1...
The front display will go dark and reset if no user interaction has taken place for a period of time. Pressing any of the front panel control buttons brings the front panel to life. D02706R02.30 L-PRO 4000 User Manual Appendix L-1...
ProLogic 10 dropout timer allowing for the slower pro- cessing thread where Group Logic is processed and providing a definite timed pulse to the group logic. Figure L.1: ProLogic 9 Appendix L-2 L-PRO 4000 User Manual D02706R02.30...
Page 315
The example uses a ProLogic state- ment and an external input as qualifiers, see example “Using ProLogic to Qual- ify Group Logic Statements” in Appendix L’ on page Appendix L-8. Figure L.3: Group Logic 1 D02706R02.30 L-PRO 4000 User Manual Appendix L-3...
Page 316
ProLogic 9 and 10 equalling 0.52 seconds. Figure L.5: ProLogic 10 Group Logic 1 is used to switch to the new setting group; there is no intentional delay. Figure L.6: Group Logic 1 Appendix L-4 L-PRO 4000 User Manual D02706R02.30...
Page 317
We are using a ProLogic statement and an external input as qualifiers, see “Using ProLogic to Qualify Group Logic Statements” in Appendix L’ on page Appendix L-8. EI 1 low, EI 2 low, and EI 3 low Figure L.7: Group Logic 16 D02706R02.30 L-PRO 4000 User Manual Appendix L-5...
Page 318
Figure L.8: Group Logic 15 EI 1 low, EI 2 high, and EI 3 low Figure L.9: Group Logic 14 EI 1 high, EI 2 high, and EI 3 low Figure L.10: Group Logic 13 Appendix L-6 L-PRO 4000 User Manual D02706R02.30...
Page 319
Figure L.11: Group Logic 12 EI 1 high, EI 2 low, and EI 3 high Figure L.12: Group Logic 11 EI 1 low, EI 2 high, and EI 3 high Figure L.13: Group Logic 10 D02706R02.30 L-PRO 4000 User Manual Appendix L-7...
Page 320
Power Swing outer blinder alarm to drive the Block Group Logic statement. There is no intentional pickup delay and 0.5 second drop-out delay to hold the block on after the block condition has reset. Figure L.15: ProLogic 8 Appendix L-8 L-PRO 4000 User Manual D02706R02.30...
Most protection schemes require the ability to block the 79 when certain events happen. In our example we are using Virtual Input 7 (VI 7) to block. The 79 blocking is set to last for an additional time of 1.0 seconds (TDB). D02706R02.30 L-PRO 4000 User Manual Appendix L-9...
Page 322
52 - Breaker Status can use any external input or ProLogic statement. The re- closer does not have to be enabled for this logic to work. The 2 circuit breakers cannot share the same input. Appendix L-10 L-PRO 4000 User Manual D02706R02.30...
Page 323
79. Virtual Input 5 is used to trip circuit breakers 52-1 and 52-2, and to provide recloser initiation. Virtual Input 6 is used to provide recloser initiation without any tripping (used to help test logic) Figure L.21: Virtual Inputs D02706R02.30 L-PRO 4000 User Manual Appendix L-11...
Page 324
VI4 for auxiliary) the trip and no reclose while VI5 is the trip and reclose (common to main and auxiliary) signal. Figure L.22: ProLogic 1 – 52-1 Trip Figure L.23: ProLogic 3 – 52-2 Trip Appendix L-12 L-PRO 4000 User Manual D02706R02.30...
Page 325
VI1 provide the close signal ProLogic 1 provides the trip signal. The pickup and dropout time delays are used to simulate breaker tripping and closing times. Figure L.24: ProLogic 2 – 52-1 “a” Status Figure L.25: ProLogic 4 – 52-2 “a” Status D02706R02.30 L-PRO 4000 User Manual Appendix L-13...
Page 326
Testing the 79 1 Apply the previous settings to the relay. Recloser 2 Set PL9 to: Figure L.26: ProLogic 9 - TP Start 3 Set PL10 to: Figure L.27: ProLogic 10 - TP End Appendix L-14 L-PRO 4000 User Manual D02706R02.30...
Page 327
Figure L.28: ProLogic 6 - not 79 Lockout 5 Clear the event log. 6 Check the metering screen for ProLogic. 52-1 and 52-2 should be low. Figure L.29: ProLogic status for 52-1 and 52-2 are low D02706R02.30 L-PRO 4000 User Manual Appendix L-15...
Page 328
Appendix L L-PRO Setting Example 7 Check the metering screen for Protection. All 79 logic points should be low. Figure L.30: Protection Metering Screen Appendix L-16 L-PRO 4000 User Manual D02706R02.30...
Page 329
Figure L.31: Control Virtual Input '52-1 Close 52-CS' to 'Pulse On' 9 Check the event log for VI1 and VI3 along with PL2 and PL4. Figure L.32: '52-1 a status: High 'and '52-2 a status: High' D02706R02.30 L-PRO 4000 User Manual Appendix L-17...
Page 330
On action for the Virtual Input 6. This will initiate the recloser but no action will be taken because the circuit breakers remain closed. Figure L.33: Pulse On 'Manual 79' 11 Check the event log and confirm there was no reclosure action. Figure L.34: 79-3Ph Initiated: High Appendix L-18 L-PRO 4000 User Manual D02706R02.30...
Page 331
• TP - Close pulse time equals time from TP start: PL9 event to TP end: PL10 event. • TF - Follow breaker time equals time from 52-1 “a” status: PL2 event to 79 Au Auxiliary Reclose (shot 1) event. D02706R02.30 L-PRO 4000 User Manual Appendix L-19...
Page 332
Pulse On action for the virtual inputs. This will trip breaker 52-2 and in- itiate the reclosing sequence. 16 Check the event log and confirm that only 52-2 breaker reclosed and was in the lead position. Confirm that 52-1 breaker did not receive any reclose attempts. Appendix L-20 L-PRO 4000 User Manual D02706R02.30...
Page 333
20 Check the event log and confirm the 79 Lead Lockout event and that there was no follow breaker reclose attempt. • 79 Lead Lockout - The time equals time from 79 Initiate event to 79 Lead Lockout event (approx. TP + 1.0s). D02706R02.30 L-PRO 4000 User Manual Appendix L-21...
Page 334
Pulse On action for the virtual inputs. This will close breaker 52-1 and after a fixed delay of TD seconds the recloser will reset. Communication -aided Tripping L-PRO #1 L-PRO #2 Schemes Figure L.39: Current Reversal Logic example Appendix L-22 L-PRO 4000 User Manual D02706R02.30...
Page 335
Gate #116 of the functional logic diagram and timer TL1 and TD1 stretch the zone 4 logic and block the POTT scheme from tripping the breaker or sending the transfer trip signal to the remote end. D02706R02.30 L-PRO 4000 User Manual Appendix L-23...
Page 337
DCB = Block Signal (derived from 21-4R (OR 50N-67R) AND NOT 21-2) Stretches the Scheme Send signal to ensure that it's received by the remote end relay. Set longer than the channel pickup delay. D02706R02.30 L-PRO 4000 User Manual Appendix L-25...
Page 338
2 ter- minals on the unfaulted line may change state from forward to reverse and reverse to forward. The unfaulted line contribution may come either end on a networked system. Appendix L-26 L-PRO 4000 User Manual D02706R02.30...
“Relay Inoperative” on the rear panel closes to activate a remote alarm. There are two possibilities for DSP Self Check Fail, either Alarm or Block. Both are related to the dc offset on a channel which should not occur with prop- D02706R02.30 L-PRO 4000 User Manual Appendix M-1...
Page 340
The Test Mode LED changes from off to red until the MPC has rebooted. The watchdog will continue to attempt to re-start the MPC several times. After multiple failed attempts, the Service Required LED changes from off to red. Appendix M-2 L-PRO 4000 User Manual D02706R02.30...
Publisher side Subscriber Side Transmission of Sampled value model (SVC) Publisher side Subscriber side c1 - Shall be ‘M’ if support for Logical-device model has been declared O - Optional M - Mandatory D02706R02.30 L-PRO 4000 User Manual Appendix N-1...
Page 345
– shall declare support for at least one(BRCB or URCB) Table N.12: Logging(clause 14) Log Control block GetLCBValues SetLCBValues QueryLogByTime QueryLogAfter GetLogStatusValues c7- shall declare support for at least one(query log by time or Query LogAfter) D02706R02.30 L-PRO 4000 User Manual Appendix N-5...
Page 346
Table N.14: Transmission of sampled value model(SVC) (Clause 16) Multicast SVC SendMSVMessage GetMSVCBValues SetMSVCBValues Unicast SVC SendUSVMessage GetUSVCBValues SetUSVCBValues C10- shall declare support for at least one(Send MSV Message or Send USV Message) Appendix N-6 L-PRO 4000 User Manual D02706R02.30...
Page 347
Nearest negative power of 2 in sec- onds TimeAccuracy of Internal clock 10 (1 msec) Supported Time Stamp resolu- 10 (1 msec) Nearest value of 2**- tion n in seconds accord- ing to 5.5.3.7.3.3 D02706R02.30 L-PRO 4000 User Manual Appendix N-7...
Page 352
Proxy SPS_1_Proxy Indicates if this device is proxy Logical Node: LLN0 Description: Logical Node 0 LN Class: LLN0 Attribute Attr. Type Explanation INC_1_Mod Mode INS_1_Beh Behaviour Health INS_1_PhyHealth Health NamPlt LPL_1_NamPlt Name Plate Appendix N-12 L-PRO 4000 User Manual D02706R02.30...
Page 353
PhV2 WYE_1_PhV1 Phase to Ground Voltage WYE_1_PhV1 Phase Currents WYE_1_PhV1 Phase Currents WYE_1_W Phase Active Power (W) WYE_1_W Phase Reactive Power (Q) WYE_1_W Phase Apparent Power (S) WYE_1_W Phase to Ground Impedance (Z) D02706R02.30 L-PRO 4000 User Manual Appendix N-13...
Page 366
Data Attribute Service Parameters IEC 61850 – 7 - 2 Common Data Class: DPL_1_PhyNam Description: Standard Device Name Plate CDC Class: DPL Attribute Type Enumeration Comment Vendor VisString255 hwRev VisString255 swRev VisString255 serNum VisString255 Model VisString255 Appendix N-26 L-PRO 4000 User Manual D02706R02.30...
Page 367
BOOLEAN subVal Enum Health subQ Quality subID VisString64 Common Data Class: SPS_1_Proxy Description: CDC Class: SPS Attribute Type Enumeration Comment stVal BOOLEAN Quality Timestamp subEna BOOLEAN subVal BOOLEAN subQ Quality subID VisString64 D02706R02.30 L-PRO 4000 User Manual Appendix N-27...
Page 368
BOOLEAN subVal Enum subQ Quality subID VisString64 Common Data Class: INS_1_Beh Description: CDC Class: INS Attribute Type Enumeration Comment stVal Enum Quality Timestamp subEna BOOLEAN subVal Enum subQ Quality subID VisString64 Appendix N-28 L-PRO 4000 User Manual D02706R02.30...
Page 369
Description: CDC Class: LPL Attribute Type Enumeration Comment Vendor VisString255 swRev VisString255 VisString255 configRev VisString255 ldNs VisString255 Common Data Class: LPL_2_NamPlt Description: CDC Class: LPL Attribute Type Enumeration Vendor VisString255 hwRev VisString255 VisString255 D02706R02.30 L-PRO 4000 User Manual Appendix N-29...
Page 371
CDC Class: WYE Attribute Type Enumeration Comment phsA CMV_1_phsAB phsB CMV_1_phsAB phsC CMV_1_phsAB neut CMV_1_phsAB Common Data Class: WYE_1_W Description: CDC Class: WYE Attribute Type Enumeration Comment phsA CMV_1_phsAB phsB CMV_1_phsAB phsC CMV_1_phsAB D02706R02.30 L-PRO 4000 User Manual Appendix N-31...
Page 372
Enum Quality Timestamp Common Data Class: ACT_1_Op Description: CDC Class: ACD Attribute Type Enumeration Comment general BOOLEAN Quality Timestamp Common Data Class: ASG_1_PoRch Description: CDC Class: ASG Attribute Type Enumeration Comment setMag AnalogueValue_1 Appendix N-32 L-PRO 4000 User Manual D02706R02.30...
Page 373
Enumeration Comment setVal Enum DirMod Common Data Class: SPG_1_TmDlMod Description: CDC Class: SPG Attribute Type Enumeration Comment setVal BOOLEAN Common Data Class: ING_1_OpDlTmms Description: CDC Class: ING Attribute Type Enumeration Comment setVal INT32 D02706R02.30 L-PRO 4000 User Manual Appendix N-33...
Page 374
Quality subID VisString64 Common Data Class: SPC_1_RcdTrg Description: CDC Class: ING Attribute Type Enumeration Comment stVal BOOLEAN Quality Timestamp Oper SPCOperate_1 ctlModel Enum ctlModel subEna BOOLEAN subVal BOOLEAN subQ Quality subID VisString64 Appendix N-34 L-PRO 4000 User Manual D02706R02.30...
Page 375
Comment: General Analogue Value (w.r.t. Floating Point Value) Parent Type: AnalogueValue Attribute Type Enumeration Comment FLOAT32 Floating point value Component: Originator Comment: Originator Value Parent Type: Originator Attribute Type Enumeration Comment orCat Enum orCat orIdent Octet64 D02706R02.30 L-PRO 4000 User Manual Appendix N-35...
Page 376
Common Data Class attributes. The definition of the enumerations is ac- cording to IEC 61850-7-3 and IEC 61850-7-4 unless otherwise stated. Enumerated type: AutoRecSt Description: Auto-Reclose Status Ordinal Semantic Ready InProgress Successful Appendix N-36 L-PRO 4000 User Manual D02706R02.30...
Page 377
Appendix N IEC61850 Implementation Enumerated type: Beh Description: Behaviour Ordinal Semantic blocked test test/blocked Enumerated type: Mod Description: Mode Ordinal Semantic blocked test test/blocked Enumerated type: Health Description: Health Ordinal Semantic Warning Alarm D02706R02.30 L-PRO 4000 User Manual Appendix N-37...
Page 378
Appendix N IEC61850 Implementation Enumerated type: dir Description: Direction Ordinal Semantic unknown forward backward both Enumerated type: ctlModel Description: Control Model Ordinal Semantic status-only direct-with-normal-security sbo-with-normal-security direct-with-enhanced-security sbo-with-enhanced-security Appendix N-38 L-PRO 4000 User Manual D02706R02.30...
Appendix N IEC61850 Implementation N.3 Data Mapping Specifications L-PRO Logical L-PRO logical device identification Device L-PRO 4000 has the following IEC 61850 logical devices defined in its ICD file: • LPROMeasurements • LPROProtection • LPROSystem • LPROVirtualElements L-PRO Logical Nodes The following table 1 defines list of logical nodes (LN) of the L-PRO logical device.
Page 381
PTUF or PFRC (one type of protection at a time) LPROProtection PFRC3 Rate of change of Dev 81-3 Dev 81-3 can operate as PTOF PFRC3 frequency or PTUF or PFRC (one type of protection at a time) D02706R02.30 L-PRO 4000 User Manual Appendix N-41...
Page 382
General Process I/O Virtual Inputs 1 Virtual input incoming controls GGIO2 ments – 30 LPROVirtualEle- GGIO3 General Process I/O Virtual Inputs 1 Virtual input outgoing controls GGIO3 ments – 30 (Currently not support) Appendix N-42 L-PRO 4000 User Manual D02706R02.30...
Page 383
Phase voltage (Aux VC) MMXU1.MX.PhV2.phsC.cVal.ang.f Phase voltage (Aux VC) MMXU1.MX.A1.phsA.cVal.mag.f Phase voltage (Main IA) MMXU1.MX.A1.phsA.cVal.ang.f Phase current (Main IA) MMXU1.MX.A1.phsB.cVal.mag.f Phase current (Main IB) MMXU1.MX.A1.phsB.cVal.ang.f Phase current (Main IB) MMXU1.MX.A1.phsC.cVal.mag.f Phase current (Main IC) D02706R02.30 L-PRO 4000 User Manual Appendix N-43...
Page 384
Phase impedance Logical Device: LPROProtection PDIS1 This section defines logical node data for the logical node PDIS1 of the L-PRO logical device LPROProtection. Data Name Description PDIS1.ST.Str.General Start (21P1 Trip) PDIS1.ST.Op.General Operate (21P1 Trip) Appendix N-44 L-PRO 4000 User Manual D02706R02.30...
Page 385
PDIS4.ST.Op.General Operate (21P4 Trip) PDIS5 This section defines logical node data for the logical node PDIS5 of the L-PRO logical device LPROProtection. Data Name Description PDIS5.ST.Str.General Start (21N1 Trip) PDIS5.ST.Op.General Operate (21N1 Trip) D02706R02.30 L-PRO 4000 User Manual Appendix N-45...
Page 386
PDIS8.ST.Op.General Operate (21N4 Trip) RSYN1 This section defines logical node data for the logical node RSYN1 of the L- PRO logical device LPROProtection. Data Name Description RSYN1.ST.Rel.stVal Release (252759 Sync Check: Armed ) Appendix N-46 L-PRO 4000 User Manual D02706R02.30...
Page 387
Start (59 Main Trip Phase A) PTOV2 This section defines logical node data for the logical node PTOV2 of the L- PRO logical device LPROProtection. Data Name Description PTOV2.ST.Str.General Start (59 Main Trip Phase B) D02706R02.30 L-PRO 4000 User Manual Appendix N-47...
Page 388
Start (59 Aux Trip Phase B) PTOV6 This section defines logical node data for the logical node PTOV6 of the L- PRO logical device LPROProtection. Data Name Description PTOV6.ST.Str.General Start (59 Aux Trip Phase C) Appendix N-48 L-PRO 4000 User Manual D02706R02.30...
Page 389
This section defines logical node data for the logical node PTUV3of the L- PRO logical device LPROProtection. Data Name Description PTUV3.ST.Str.General Start (27 Main Trip Phase C) PTUV3.ST.Op.General Operate (27 Main Trip Phase C) D02706R02.30 L-PRO 4000 User Manual Appendix N-49...
Page 390
This section defines logical node data for the logical node PTUV6 of the L- PRO logical device LPROProtection. Data Name Description PTUV6.ST.Str.General Start (27 Aux Trip Phase C) PTUV6.ST.Op.General Operate (27 Aux Trip Phase C) Appendix N-50 L-PRO 4000 User Manual D02706R02.30...
Page 391
Operate (81-3 Trip) PTOF4 This section defines logical node data for the logical node PTOF4 of the L- PRO logical device LPROProtection. Data Name Description PTOF4.ST.Str.General Start (81-4 Trip) PTOF4.ST.Op.General Operate (81-4 Trip) D02706R02.30 L-PRO 4000 User Manual Appendix N-51...
Page 392
Operate (81-3 Trip) PTUF4 This section defines logical node data for the logical node PTUF4 of the L- PRO logical device LPROProtection. Data Name Description PTUF4.ST.Str.General Start (81-4 Trip) PTUF4.ST.Op.General Operate (81-4 Trip) Appendix N-52 L-PRO 4000 User Manual D02706R02.30...
Page 393
Operate (81-3 Trip) PFRC4 This section defines logical node data for the logical node PFRC4 of the L- PRO logical device LPROProtection. Data Name Description PFRC4.ST.Str.General Start (81-4 Trip) PFRC4.ST.Op.General Operate (81-4 Trip) D02706R02.30 L-PRO 4000 User Manual Appendix N-53...
Page 394
Operate (50LS Main Alarm – Phase C) PIOC4 This section defines logical node data for the logical node PIOC4 of the L-PRO logical device LPROProtection. Data Name Description PIOC4.ST.Op.General Operate (50LS Aux Alarm – Phase A) Appendix N-54 L-PRO 4000 User Manual D02706R02.30...
Page 395
Description RBRF1.ST.OpEx.General Operate (50BF Main-1 Trip) RBRF2 This section defines logical node data for the logical node RBRF2 of the L- PRO logical device LPROProtection. Data Name Description RBRF2.ST.OpEx.General Operate (50BF Main-2 Trip) D02706R02.30 L-PRO 4000 User Manual Appendix N-55...
Page 396
This section defines logical node data for the logical node PTOC1 of the L- PRO logical device LPROProtection. Data Name Description • PTOC1.ST.Str.General • Start (51 Alarm) • PTOC1.ST.Op.General • Operate (51 Trip) Appendix N-56 L-PRO 4000 User Manual D02706R02.30...
Page 397
PTOC5.ST.Op.General Operate (46-50 Trip) PTOC6 This section defines logical node data for the logical node PTOC6 of the L- PRO logical device LPROProtection. Data Name Description PTOC6.ST.Str.General Start (46-51 Alarm) PTOC6.ST.Op.General Operate (46-51Trip) D02706R02.30 L-PRO 4000 User Manual Appendix N-57...
Page 398
General indication (binary input) – ProLogic 20 GGIO1.ST.Ind21.stVal General indication (binary input) – ProLogic 21 GGIO1.ST.Ind22.stVal General indication (binary input) – ProLogic 22 GGIO1.ST.Ind23.stVal General indication (binary input) – ProLogic 23 GGIO1.ST.Ind24.stVal General indication (binary input) – ProLogic 24 Appendix N-58 L-PRO 4000 User Manual D02706R02.30...
Page 399
General indication (binary input) – External Input 17 GGIO3.ST.Ind18.stVal General indication (binary input) – External Input 18 GGIO3.ST.Ind19.stVal General indication (binary input) – External Input 19 GGIO3.ST.Ind20.stVal General indication (binary input) – External Input 20 D02706R02.30 L-PRO 4000 User Manual Appendix N-59...
Page 400
General indication (binary input) – Output Contact 18 GGIO4.ST.Ind19.stVal General indication (binary input) – Output Contact 19 GGIO4.ST.Ind20.stVal General indication (binary input) – Output Contact 20 GGIO4.ST.Ind21.stVal General indication (binary input) – Output Contact 21 Appendix N-60 L-PRO 4000 User Manual D02706R02.30...
Page 401
General indication (binary input) – Virtual input 25 GGIO1.ST.Ind26.stVal General indication (binary input) – Virtual input 26 GGIO1.ST.Ind27.stVal General indication (binary input) – Virtual input 27 GGIO1.ST.Ind28.stVal General indication (binary input) – Virtual input 28 D02706R02.30 L-PRO 4000 User Manual Appendix N-61...
Page 402
General Indication (binary input) – Virtual Input 17 GGIO2.ST.Ind18.stVal General Indication (binary input) – Virtual Input 18 GGIO2.ST.Ind19.stVal General Indication (binary input) – Virtual Input 19 GGIO2.ST.Ind20.stVal General Indication (binary input) – Virtual Input 20 Appendix N-62 L-PRO 4000 User Manual D02706R02.30...
Page 403
General Indication (binary input) – Virtual Input 15 GGIO3.ST.Ind16.stVal General Indication (binary input) – Virtual Input 16 GGIO3.ST.Ind17.stVal General Indication (binary input) – Virtual Input 17 GGIO3.ST.Ind18.stVal General Indication (binary input) – Virtual Input 18 D02706R02.30 L-PRO 4000 User Manual Appendix N-63...
Page 404
General Indication (binary input) – Virtual Input 27 GGIO3.ST.Ind28.stVal General Indication (binary input) – Virtual Input 28 GGIO3.ST.Ind29.stVal General Indication (binary input) – Virtual Input 29 GGIO3.ST.Ind30.stVal General Indication (binary input) – Virtual Input 30 Appendix N-64 L-PRO 4000 User Manual D02706R02.30...
Need help?
Do you have a question about the L-PRO 4000 and is the answer not in the manual?
Questions and answers