Accura 2300S/2350 Communication User Guide
Chapter 2 Modbus Map of Accura 2300S
Modbus Map Overview
Accura 2300S Modbus Map consists of five categories(System Information, Setup, Control,
Measurement data, Event data). Accura 2350 is named as module. Type of Accura 2350 is as
followed.
Module Type of Accura 2350
Accura 2350-3P
Accura 2350-1P
Accura 2350-GAS
Accura 2350-GW
Accura 2350-DO
Accura 2350-IDC
Accura 2350-VDC
Accura 2350-TEMP
Register is accessed as the address starting from 0. Register address is calculated by subtracting
one from register number on the Modbus map. Holding register 1-65536 is accessed as 0-65535
address.
Register Number
System Information
1-24
51-690
Setup
700
701-725
741-749
851-856
861-877
ⓒ 2013 Rootech Inc. All Rights Reserved
Description
Three phase current/power measuring
module
Single phase current/power measuring
module
Gas detecting module
Data transmission module of RS485
communication devices
Digital Output module
DC current measuring module
DC voltage measuring module
Temerature measuring module
Description
Accura 2300S System information
Accura 2350 System information
Remote Setup Unlock
General Setup
Network Setup
Network Time Protocol (NTP) Setup
Measurement Setup
Chapter 2 Modbus Map of Accura 2300S
Abbreviation
Three phase module
Single phase module
GAS module
GW module
DO module
IDC module
VDC module
TEMP module
Page 29