Positioner Adjustment End Position Closed (Inverse Operation); Positioner In Split Range Version (Option); Split Range: Description Of Functions; Split Range Programming - AUMA Matic Series Calibration Instruction

Table of Contents

Advertisement

AUMA Matic Positioner
Calibration Instruction
Possible LED indication:
(refer to Figure 3)
LEDs are not illuminated
LED
(V27 yellow) is
illuminated
LED
(V28 green) is
illuminated

Positioner Adjustment End Position CLOSED (inverse operation)

Run actuator with push-button
Connect max. command signal (nominal value E1) = 20 mA.
Possible LED indication:
(refer to Figure 3)
LEDs are not illuminated
LED
(V27 yellow) is
illuminated
LED
(V28 green) is
illuminated

Positioner in Split Range version (option)

For Split Range a modified version of the positioner is used. The standard version is not suitable for Split Range
operation.

Split Range: description of functions

Split Range allows the adaptation of the positioner to nominal value ranges which are for example necessary to
individually control several actuators (up to four actuators) with the same nominal value signal. Typical values for
two actuators are 0 - 10 mA and 10 - 20 mA or 4 - 12 mA and 12 - 20 mA. But all other values between 0/4 - 20
mA can also be set and adjusted.

Split Range Programming

Programming of the positioner at the code switches S1-7, S2-7, S3-7 can, with the exception indicated below, be
performed in the same manner as for normal operation.
NOTE: Switch S1-7 DIP 5 at code switch S1-7 must always be in position ON for Split Range version.
ISSUE 02/02
Required setting in end position OPEN
(refer to Figure 3)
Turn potentiometer "0" (P3) slightly clockwise until
LED
Turn potentiometer "0" (P3) slightly clockwise until LED
yellow) goes out and LED
Turn potentiometer "0" (P3) counter-clockwise until LED
green) goes out.
Then turn potentiometer "0" (P3) slightly clockwise until LED
(V28 green) lights up again.
(local controls) to end position CLOSED.
Required setting in end position CLOSED
(refer to Figure 3)
Turn potentiometer "max" (P4) slightly counter-clockwise until
LED
Turn potentiometer "max" (P4) clockwise until LED
yellow) goes out.
Then turn potentiometer "max" (P4) slightly counter-clockwise
until LED
Turn potentiometer "max" (P4) slightly counter-clockwise until
LED
up.
All information in this document is subject to change without notice.
(V28 green) lights up.
(V27 yellow) lights up.
(V27 yellow) lights up again.
(V28 green) goes out and LED
Page 8 of 11
AUMA Actuators, Inc. USA
(V28 green) lights up.
(V27 yellow) lights
SE-SI-35-0007
(V27
(V28
(V27

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for AUMA Matic Series

This manual is also suitable for:

Matic-cMatic-s

Table of Contents