ZXM2
ZXM2
TB1
MXR
POLARIZED
ISOLATING
DAMPER
POWER
TERMINAL
MXC
BLOCK &
2.5 amp
BREAKER
F1
TB2
D
M6
M
M4
P
M2
Rugged
R
Damper
M1
6
Motor
Terminal
Blocks
D
with
M6
ZONE ID
M
M4
blocks
P
M2
R
5
M1
TB3
Heavy
duty
10 amp
contact
rated
relays
Rugged 10 pin
Expansion Header
Bus Cable not shown for clarity
The ZXM2 Expansion Module for the UZC4 series is pictured above. A
total of nine (9) ZXM2's can be connected to the UZC4 to create a 22 ZONE
system! The modules are housed and linked together via a factory supplied
10 conductor BUS CABLE and a unique Expansion Header Card. The
UZC4 expands by connecting factory assembled Expansion Systems
such as the ZXM2A, ZXM4A and ZXM6A that are pre-wired and
configured for you at the factory. The UZC4 connects to these housed
expansion assemblies via a flexible 20" long bus cable. Each Expansion
module has a set of address switches that must be set properly to allow the
UZC4 to recognize each expansion module in the correct order. Note the
"STATUS" LED provided on every Expansion Module to indicate
active micro-processor operation. There are also two "DAMPER"
LED's provided to indicate which damper(s) are energized open or
closed. Next to each Damper and Thermostat terminal block is a blank
white square, where the "Zone Number" can be written to easily identify it as
a new expanded zone. These blocks will be filled in for you at the factory
when a UZC 6 zone, 8 zone, 10 zone or higher has been ordered. The ZXM2
address switches will also be factory set for you. Note the same multi-input
thermostat terminals are supplied on the ZXM2 as are supplied on the
UZC4 Main Module. Most Important of all is to note the MXR & MXC
Damper Motor Power Input Block. The ZXM2 Expansion Module is
powered via the Bus Cable from the UZC4, but the power for the
dampers must be provided by a separate transformer and is isolated
from the module. This allows great freedom to connect as many dampers
as the 2.5 amp thermal breaker can handle. See page 19 for damper motor
power supply details. Make sure to read the ZXM2 Technical Bulletin for
the proper cabling scenarios and zone address settings for your
system or refer to the chart on the right.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362
ZXM2 FEATURES AT A GLANCE
R2
R1
R3
R4
J1
R7
R6
R5
C1
C2
U1
Z1
R9
D2
R12
K1
R13
R14
R15
R10
D3
K2
D1
R11
J2
R16
C4
U2
C9
R17
C5
U3
C3
R24
R8
C6
D4
U4
C12
R25
C7
U5
R32
SW1
D5
0
>
>
A
1
>
>
0
2
A
>
>
0
4
A
C15
>
>
0
8
A
R33
LED1
STATUS
6
R40
LED2
U6
DMPR
5
LED3
C18
R41
Bright STATUS LED
4 Switch ZONE
and DAMPER LED'S
ADDRESS Bank
with ZONE ID blocks
R18
R20
TB4
C10
C11
R21
R23
R19
R22
R26
R28
C13
C14
R27
R29
R30
R31
R36
R34
TB5
C16
C17
R35
R37
R38
R39
R42
R44
C19
C20
R43
R45
R46
R47
All Expansion module
Dip switch banks must
be set correctly for
proper zone address
identification. The 1st
expansion module
would be zones 5 & 6.
The 2nd expansion
module would be zones
7 & 8. The 3rd
expansion module
would be zones 9 & 10.
And so on up the line
for a total of 22 zones.
The switches are set
for you at the factory
unless you are
expanding the system
in the field. It is a good
idea to check them
anyway.
E-Mail- info@ewccontrols.com
D6
C
W1
E
W2
Rugged &
O
B
Versatile
T
Thermostat
Y1
S
Terminal
T
Y2
Blocks
A
R
T
G
6
D7
D8
C
W1
E
W2
FIELD
O
ZONE ID
B
T
Blocks
Y1
S
T
Y2
A
R
T
G
5
D9
Dip
Expansion
Switch
Panel No.
Settings
9
8
7
6
5
4
3
2
1
23
Need help?
Do you have a question about the Ultra-Zone UZC4 and is the answer not in the manual?