SBM51/06 Gateway Module for Danfoss Frequency
Inverters
Application
The SBM51/06 gateway module can be used to connect up
to eight different types of Danfoss frequency inverter (FI), via
the Danfoss bus, to the DDC3000/DDC4000 automation
system. The connection is made via the RS485 interface of
the SBM51/06. Danfoss FC protocol is used for communi-
cation.
You can use the following Danfoss series:
VLT 2800 series, VLT 5000 series, VLT 6000 series, VLT
HVAC Drive FC 102, VLT AQUA Drive FC 202, VLT Automa-
tionDrive FC 301, VLT AutomationDrive FC 302, VLT Micro
Drive FC 51
Content
Important Information Regarding Product Safety ..................................................................................................2
Item........................................................................................................................................................................3
Technical Data.....................................................................................................................................................3
Dimensions ..........................................................................................................................................................3
Connection...........................................................................................................................................................4
Installation and Removal .......................................................................................................................................6
Commissioning ......................................................................................................................................................7
Switching on the Power .........................................................................................................................................9
SBM51/06 Parameter Description .......................................................................................................................10
Basic Program ...................................................................................................................................................10
Project Planning: Frequency Inverter - SBM51/06 ..............................................................................................20
Determining Speed (Using the VLT 6000 as an Example) ................................................................................20
Malfunction messages .......................................................................................................................................20
V-Belt Monitoring (Load shedding) ....................................................................................................................20
Änderungen vorbehalten - Contents subject to change - Sous réserve de modifications - Reservado el derecho a modificación - Wijzigingen
voorbehouden - Con riserva di modifiche - Innehåll som skall ändras - Změny vyhrazeny - Zmiany zastrzeżone - Возможны изменения -
A változtatások jogát fenntartjuk - 保留未经通知而改动的权力
Kieback&Peter GmbH & Co. KG
Tempelhofer Weg 50, 12347 Berlin/Germany
Telefon: +49 30 60095-0, Telefax: +49 30 60095-164
www.kieback-peter.de, info@kieback-peter.com
Datasheet 2.50-40.051-71-EN
SBM51/06
Page
A

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SBM51/06 and is the answer not in the manual?

Questions and answers

Summary of Contents for Kieback&Peter SBM51/06

  • Page 1: Table Of Contents

    SBM51/06 Gateway Module for Danfoss Frequency Inverters Application The SBM51/06 gateway module can be used to connect up to eight different types of Danfoss frequency inverter (FI), via the Danfoss bus, to the DDC3000/DDC4000 automation system. The connection is made via the RS485 interface of the SBM51/06.
  • Page 2: Important Information Regarding Product Safety

    Important Information Regarding Product Safety Safety Instructions This data sheet contains information on installing and commissioning the product "SBM51/06". Each person who carries out work on this product must have read and understood this data sheet. If you have any questions that are not resolved by this data sheet, you can obtain further information from the supplier or manufacturer.
  • Page 3: Item

    Switch cabinet installed on top hat rail DIN EN 50022 – 35 x 7.5 Dimensions 125 x 77 x 60 (WxHxD in mm) Compatibility SBM51/06 is supported as follows: ■ DDC3000 as of version 6.7 ■ DDC4000 as of version 1.2.430 ■...
  • Page 4: Connection

    The shield is positioned on the spring-type terminal (or clamp for older VLT models) on one side of the FI only. The COM terminal on the SBM51/06 is not used and is only used in environments with severe interference. Clarify connection with Danfoss Support.
  • Page 5 Datasheet 2.50-40.051-71-EN Product Description SBM51/06 NOTE The bus-systems switch cabinet bus (DDC3000) and CAN bus (DDC4000) are identical. Hence, all technical information relating to the switch cabinet bus also apply to the CAN bus. Switch cabinet bus When connecting the switch cabinet bus, use a cable of at least type JY(St)Y 2x2x0.8 Lg: two x two leads stranded into a pair, plastic insulation and an electrostatic shield with a lead diameter of at least 0.8 mm.
  • Page 6: Installation And Removal

    Datasheet 2.50-40.051-71-EN SBM51/06 Product Description Installation and Removal Installation WARNING Contact with live parts of electrical domestic installation can cause death due to electric shock. Mounting/removal may only be carried out when power is switched off. NOTICE Switching on the power supply of unparameterized products can lead to unforeseen consequences such as malfunctions or material damage.
  • Page 7: Commissioning

    Rotary switch for setting the switch cabinet bus address Switch cabinet bus LED Signal Meaning Switch cabinet bus LED Green SBM51/06 is operating Switch cabinet bus LED Flashing green Data transmission Switch cabinet bus LED SBM51/06 not registered Switch cabinet bus LED...
  • Page 8 Datasheet 2.50-40.051-71-EN SBM51/06 Product Description Setting the switch cabinet bus address ► Disconnect the power supply of the SBM51/06. ► Press the lower edge of the front cover and remove the cover. The rotary switches for setting the switch cabinet bus address are located inside the SBM51/06.
  • Page 9: Switching On The Power

    VDE guidelines and local wiring regulations. Before switching on the power, ensure that the device has been mounted correctly and check the electrical connection. After turning on the power, check the transmission function of the SBM51/06. Page 9 / 26...
  • Page 10: Sbm51/06 Parameter Description

    Basic Program Registering the SBM51/06 on the DDC After switching the supply voltage on, the SBM51/06 checks the availability of the switch cabinet bus and uses the basic program to register with the DDC3000/DDC4000 automation system. In addition, the SBM51/06 automatically registers the connected frequency inverter with the DDC.
  • Page 11 The DDC software menu, M090 SBM51 gateway (previously gateway menu), can be set to the SBM51/06 basic program up to 32 times. Two gateway menus with addresses 1 and 2, 3 and 4, etc. and the menu with address 32 are automatically created per FI. A maximum of 17 M090 menus are therefore required for a maximum of eight FIs that can be connected.
  • Page 12: Parameter Lists For The Ddc Software Menus M090 And Cd_Sb51 (Sbm51 Gateway)

    /03 and /04 for the frequency inverter with address 2, etc. When using a DDC3000, the basic program of the SBM51/06 is expanded with additional DDC software menus M090 according to the number of frequency inverters to be added. When using a DDC4000, all 32 menus are automatically created.
  • Page 13 Datasheet 2.50-40.051-71-EN Product Description SBM51/06 A module reset is performed if the Resync process could not be completed for all registered frequency inverters. Parameter 2216 “Q Digital Setpoint 1” Parameter 2216 switches bus system (FC bus) communication on or off: “0”...
  • Page 14 7 = Auto 8 = Manual NOTE The Danfoss frequency inverters that can be connected to the SBM51/06 do not support all possible parameters (see parameter reference tables from page 22). Parameter 2209 “External System OK” Is set to “0” when the communication to the external system is interrupted.
  • Page 15 Datasheet 2.50-40.051-71-EN Product Description SBM51/06 Parameter 2215 “Analog Actual Value 5” Parameter 2215 is only read once when the FI is registered. If the parameter is changed during operation, the new value is only valid when the FI has been registered again.
  • Page 16 8 = Manual NOTE The Danfoss frequency inverters that can be connected to the SBM51/06 do not support all possible parameters (see parameter reference tables from page 22). Parameter 2241 “Q Analog Setpoint 2” and 2242 “Q Analog Setpoint 3”...
  • Page 17 “1” - “2”, the SBM sets the selected parameter set and sends the setpoints. NOTE The SBM51/06 can switch to four parameter sets. Only the first two parameter sets can be parame- terized in the SBM51/06. The settings are active in the FI for parameter sets 3 and 4.
  • Page 18 Switch the parameter set using parameter 2240 “Q analog setpoint 1” of the second respective menu, SBM51 gateway (see Parameter 2240 “Q Analog Setpoint 1”, page 16). The “remote” setpoint is only adopted by the SBM51/06 in automatic FI mode. When the FI is in manual mode, the frequency inverter uses the “on-site setpoint”.
  • Page 19 0/1 edge of the assigned digital signal. Second Menu SBM51 Gateway (Even-Numbered Addresses) You can control the first two relay outputs with the SBM51/06 if the Danfoss frequency inverter is equipped with relay outputs. Relay control is enabled via the parameter 2245 “Q digital setpoint 3”.
  • Page 20: Project Planning: Frequency Inverter - Sbm51/06

    If the free display is to be used in another way, FI parameter 006 (unit of the scalable value) must be set such that it is not equal to “0”. In this case, automatic configuration of the SBM51/06 remains undone. The value displayed in the first respective software menu, SBM51 gateway, parameter 2253 “Analog actual value 7”...
  • Page 21 The number of frequency inverters can be set in order to ensure an optimal readout time (see Software Menu M090 and CD_SB51 Menu 32, page 17). If, for instance, only three frequency inverters are set, the SBM51/06 will only search addresses 1 to 3. This results in a shorter cycle time. Page 21 / 26...
  • Page 22: Comparison Tables For The Software Menu M090 And Cd_Sb51: Parameter - Data Points

    Datasheet 2.50-40.051-71-EN SBM51/06 Product Description Comparison Tables for the Software Menu M090 and CD_SB51: Parameter - Data Points Parameter Reference Table Software Menu M090 and CD_SB51: /01, /03, /05, /07, /09, /11, /13, /15 --- Danfoss Frequency Inverters VLT 6000, VLT 5000, VLT 2800...
  • Page 23 Datasheet 2.50-40.051-71-EN Product Description SBM51/06 Parameter 2253 on the Frequency Inverter VLT 5000 The “User-defined display” parameter is not available on the FI VLT 5000. Data point 558 (“Motor rpm x scaling”) is output to parameter 2253/01 “User-defined display”. Parameter Reference Table...
  • Page 24 Datasheet 2.50-40.051-71-EN SBM51/06 Product Description Parameter Reference Table Software Menu M090 and CD_SB51: /01, /03, /05, /07, /09, /11, /13, /15 --- Danfoss frequency inverters FC-102/FC-202, FC-301/302, VLT Micro Drive FC 51 Para DDC Parameter Text Meaning FC-102/ FC-301/ VLT Micro...
  • Page 25 Datasheet 2.50-40.051-71-EN Product Description SBM51/06 Parameter Reference Table Software Menu M090 and CD_SB51: /02, /04, /06, /08, /10, /12, /14, /16 --- Danfoss frequency inverters FC-102/FC-202, FC-301/302, VLT Micro Drive FC 51 Para DDC Parameter Text Meaning FC-102/ FC-301/ VLT Micro...
  • Page 26 Datasheet 2.50-40.051-71-EN SBM51/06 Product Description Page 26 / 26...

Table of Contents