Features
Speaker design detail summary:
 Separate models are available with 4-1/2" or 8"
speakers, and with 25 or 70 VRMS input
 Output power is selectable as 1/4, 1/2, 1, 2, or 4 W;
Note: Refer to product selection below and sound
output ratings information on page 2 for listings and
application guidance
 One inch speaker coil provides high quality sound
 Finish is satin white baked enamel
 Grills are heavy gauge steel
 Mounting is into square or round backbox (refer to
page 2 for models and compatible backboxes)
 ULC listed to Standard CAN/ULC-S541*
 Fire alarm listed frequency response is 400 to 4000 Hz
Description
2902-93xx Series Speakers provide voice and tone
notification when used with Simplex
Voice/Alarm Communication fire alarm control panels.
Heavy gauge steel grills provide resistance against
warping. Standard screws are used to mount the speaker
into its compatible backbox.
Convenient Wattage Selection. Input line matching
transformers are pre-installed and a jumper switch allows
selection of the desired output wattage. The cone is
moisture proof and treated with an antifungal, tropical
environment compatible agent.
Fire Alarm Applications Note: These speakers must
not be painted or have their finish altered in any way.
* Refer to Product Selection and Sound Output Ratings for additional details.
Products are ULC listed under SimplexGrinnell, div of Tyco International of
Canada
LTD.
Product Selection
(refer to diagram on page 2 for dimension reference (A, B, C)
Speaker Model
25 V Input
70 V Input
2902-9310
2902-9311
2902-9313**
2902-9312
(see Note)
2902-9314
2902-9315
2902-9316
2902-9317
** Note: The combination of speaker 2902-9313 and backbox 2975-9304 requires use of the 1 W tap to achieve 85 dB per ULC
sound chamber testing.
Metal Grill Speakers for Canadian Fire Alarm Applications
®
Emergency
Speaker
Grill Description (A)
Size
Round Grill, 8-9/16"
4-1/2"
(217 mm) diameter
(114 mm)
Square Grill, 6-3/8"
4-1/2"
(162 mm)
(114 mm)
Round Grill, 12-3/4"
8"
(324 mm) diameter
(203 mm)
Square Grill, 12-1/2"
8"
(318 mm)
(203 mm)
Multi-Application Peripherals
Audible Notification Appliances,
Round 2902 Series Speaker
(12-3/4" diameter grill shown)
Square 2902 Series Speaker
(12-1/2" grill shown)
Compatible Backboxes with Dimensions (B x C)
Semi-Flush Mount
2975-9302; 6" round x 3-7/16" deep
(152 mm x 87 mm)
2975-9303; 5-9/16" square x 4-11/16"
deep (141 mm x 119 mm)
2975-9305; 10" round x 4" deep, with
11-5/8" lip (254 mm x 102 mm x
295mm)
2975-9306; 11-3/4" square x 4" deep
(298 mm x 102 mm)
Surface Mount
Not Available
2975-9304**; 6-5/8"
square x 4" deep
(168 mm x 104 mm)
(see Note below)
Not Available
2975-9307; 12-7/8"
square x 4" deep
(327 mm x 102 mm)
S12902-0005-5 7/2010

Advertisement

loading
Need help?

Need help?

Do you have a question about the Tyco 2902-93 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Simplex Tyco 2902-93 Series

  • Page 1 (12-3/4” diameter grill shown) Description 2902-93xx Series Speakers provide voice and tone ® notification when used with Simplex Emergency Voice/Alarm Communication fire alarm control panels. Heavy gauge steel grills provide resistance against warping. Standard screws are used to mount the speaker into its compatible backbox.
  • Page 2 Standard for Electrical Installations, Section 32. Tyco is a registered trademark of Tyco International Services GmbH and is used under license. Simplex, and the Simplex logo are trademarks of Tyco International Ltd. and its affiliates and are used under license.

This manual is also suitable for:

Tyco 2902-9310Tyco 2902-9314Tyco 2902-9312Tyco 2902-9316Tyco 2902-9311Tyco 2902-9313 ... Show all