Anderson Greenwood SerieS 95 Pilot oPerated Safety relief ValVeS
InstallatIon and MaIntenance InstructIons
7 VAlVe diAGnosis Guide
problem
Valve does not close on start-up with
little or no cargo tank pressure
Valve opens at a pressure below
nameplate set pressure
Valve opens at correct pressure but
does not close

8 repAir kits

Main valve size
2 x 3
3 x 4
4 x 6
6 x 8
Pilot
Backflow preventer (diaphragm)
Check valve (ball check)
© 2017 Emerson. All rights reserved.
causes
(refer to figure 1)
Main valve piston in lift position, pressurize dome through
field test handvalve (0.5 to 1.0 kp/cm
Set pressure incorrect
auxiliary setter device incorrect one for valve.
auxiliary setter device not screwed down all the way.
Pilot sense diaphragm leaks. Check for gas flow
through pilot spring bonnet vent.
Backflow preventer check valve leaks. (item 15, figure 2)
Check for gas flow at discharge tube to main valve outlet.
No gas flow should be detected.
Pilot not sensing correct tank pressure
Check valve in tank pressure sense line (figure 1) restricted.
filter screen in pilot or small orifices in pilot restricted.
iMportAnt
In an emergency, main valve can be closed by pressurizing dome
(top of piston) through close tee (Item 13, Figure 2) remove plug
(item 18) and apply pressure equal to tank pressure.
soft goods kit part number
04.4744.810
04.4744.804
04.4744.834
04.4744.835
04.4744.025
04.4744.781
04.4744.782
) to close piston.
2
Bolt kit part number
04.4744.330
04.4744.331
04.4744.332
04.4744.333
04.4744.333
04.4744.335
None
10