9.16 Description Of Parameters: Factory Settings conti.
Outdoor temperature sensor input configuration
00= with outdoor temperature sensor connected, external temperature value has influence to calculate
heating flow temperature set-point
P06
01= with outdoor temperature sensor connected, display shows external temperature value (no influence)
02...05 = no function is associated
00..02 = No function is associated
03 = This is an input contact for CH request (e.g. trigger phone).
When contact CN2 is closed and Room Thermostat (RT) requiring heat switches burner on.
Note: verify heating mode is enabled (winter or heat only mode)
04 = This is an input contact for Low Temperature Thermostat (e.g. floor heating system).
When Low Temperature Thermostat connected on CN2 cuts out, burner switches off and display shows
P07
E178 anomaly.
Note: verify heating mode is enabled (winter or heat only mode)
05 = This is an input contact for external DHW recirculation pump. When contact CN2 is closed the pump
runs for a specific period.
To enable input it is necessary to set parameter P04 or P05 = 08 and P69 = 05.
Pump will run at P19 minutes (Summer/Winter mode or Only Winter mode) or P19/2 minutes (only
Summer mode).
P09
Manufacturer information
Heating set-point setting OT / RT (Open Therm / Room Thermostat 120V~)
00 = with Remote Control (RC) connected, temperature request is RC set-point
P10
01 = Temperature Request is highest set point between RC and PCB
02 = Temperature request is RU setpoint. The RT enable the gas boiler operates
P11..P12
Manufacturer information
P13
Max. heating output (0-100%)
P14
DHW max. output (0-100%)
P15
Min. heating output (0-100%)
Maximum CH set-point (°C)
P16
00 = 176°F (80°C)
01 = 113°F (45°C)
P17
Pump overrun time in heating mode (01-240 minutes)
P18
Burner ignition delay in CH mode (00-10 minutes) - 00=10 seconds
P19
Manufacturer information
P20
Pump overrun time in DHW mode (seconds)
Anti-legionellosis function
P21
00 = Disabled -
01 = Enabled
Manufacturer information
P22
(set "22" to display parameters 42 and above)
P23
Maximum DHW set-point temperature 113°-140°F (45°-60°C), Default 49 = 120°F
P24
Manufacturer information
P25
No water safety device
P26..P31
Manufacturer information
P32..P41
Diagnostics (See SERVICE Instructions)
Temperature unit setting
00 = °C
P44
01 = °F
P71*
Maximum Fan Speed
P72*
Minimum Fan Speed
To calculate fan speeds
NOTE :
To scroll to parameters 42 and above, it is necessary to set P22 to 22 before scrolling up to the parameter.
* See Tables : SECTION 12.2 - Parameters Setting For High Altitude.
9 - START UP PROCEDURE
Setting
RPM
Setting
RPM
43
(P71 x 10) + 5000
(P72 x 10) + 750
240012564 REV A, [05/15/2019]
FACTORY SETTINGS
125
150
00
00
--
00
--
100
80
100
00
00
03
03
07
30
00
00
49
35
00
--
--
01
115
220
6150
7200
40
40
1150
1150