Overview
Mounting
Electro-Magnetic Interference (EMI) Issues
Important note:
A built-in RC noise
suppression circuit may
be connected in parallel
with relay contacts.
Full AC voltage isolation
may NOT be provided
when relay contacts
are open.
Small AC current
(≈ 1.5 mA at 230 VAC)
may still flow through
the RC circuit!
BBI250 is a programmable process indicator
with an input for various linear current, voltage,
or resistive signals, a fully programmable tri-color
LED bargraph that allows setting the color
of each dot, 'dot' or 'bar' display mode as well
as customized scale, and a bright 3-digit LED
display. The device may be also equipped with
up to 2 programmable relays providing ON/OFF
control / alarm with or without pulse mode.
Place BBI250 into a 42x90 mm panel cut-out.
Tighten it into place using the enclosed
mounting brackets.
All signal wires must be shielded.
They must not be packaged together
with power cables!
Never lay the signal wires close
to inductive or capacitive noise sources,
such as relays, contactors, motors, etc.!
All shields have to be grounded ONLY
at one end, as closer as possible
to the indicator terminals!
Avoid sharing supply lines with powerful
consumers, especially with inductive loads,
switched on and off.
To stop unwelcome interference signals
entering through the power supply lines,
use shielded 1:1 isolation transformer!
Shunt all switched (not only those switched
by the indicator) inductive consumers
with special suppression networks:
RC group and varistor - for AC loads,
or diode - for DC loads.
If the indicator operates in a very powerful
EMI area, it has to be mounted inside
a grounded metal shielding box!
2