Lennox ASC Series Installation, Operating And Maintenance Manual page 24

Air cooled condensing unit
Table of Contents

Advertisement

2. INSTALLATION
2.7.- ELECTRICAL CONNECTIONS
POWER SUPPLY
Power supply
1
020S
5G x 4 mm²
025S
4G x 6 mm²
030S
035S
4G x10 mm²
040S
045D
4G x 16 mm²
055D
070D
3 x 25 mm² +
1 x 16 mm²
085D
100D
3 x 50 mm²
120D
1 x 25 mm²
140D
3 x 70 mm² +
200D
1 x 35 mm²
3 x 95 mm² +
230D
1 x 50 mm²
Standard - ELHS
020S
4G x 2,5 mm² +
025S
6G x 1,5 mm²
030S
035S
4G x 6 mm² +
040S
6G x 1,5 mm²
045S
055D
070D
085D
4G x 10 mm² +
6G x 1,5 mm²
100D
120D
140D
200D
N/A
230D
N/A
• 23 •
Power supply with
electrical heater
1'
5G x 16 mm²
4G x 16 mm²
4G x 1,5 mm²
(STD/HP1) & (HP2/HP3)
3 x 35 mm² +
1 x 16 mm²
3 x 50 mm² +
1 x 25 mm²
4G x 1,5 mm² (STD/HP1)
4G x 2,5 mm² (HP2/HP3)
3 x 70 mm² +
1 x 35 mm²
3 x 95 mm² +
4G x 2,5 mm² (STD/HP1)
1 x 50 mm²
2 x (4G x 1,5 mm²) (HP2/HP3)
N/A
N/A
Medium - ELHM
4G x 6 mm² +
6G x 1,5 mm²
4G x 10 mm² +
6G x 1,5 mm²
N/A
N/A
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
Power supply
Fan
Free-cooling
2
4
6G x 1,5 mm²
N/A
N/A
N/A
N/A
Power supply
Electrical heater (3)
High - ELHH
4G x 10 mm² +
6G x 1,5 mm²
4G x 25 mm² +
6G x 1,5 mm²
N/A
N/A
Exhaust fan
Return fan
5
6
N/A
4G x 1,5 mm²
4G x 1,5 mm²
4G x 2,5 mm²
N/A
N/A
N/A
N/A
n/a: not available
Modulating - EHHM
4G x 10 mm² +
7G x 1,5 mm²
4G x 25 mm² +
7G x 1,5 mm²
N/A
N/A
n/a: not available

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents