Lennox ASC Series Installation, Operating And Maintenance Manual page 22

Air cooled condensing unit
Table of Contents

Advertisement

2. INSTALLATION
2.6- REFRIGERANT CONNECTIONS
TABLE 3.1 : REFRIGERANT CHARGE
020S
025S
030S
C1
5155
5315
5700
C2
------
------
------
020S
025S
030S
C1
5725
5900
6330
C2
------
------
------
Note :
MODELS 100D and 120D USE DIFFERENT SIZES OF PIPE CONNECTIONS : LARGE SIZE FOR CIRCUIT 1 AND
SMALL SIZE FOR CIRCUIT 2.
REFRIGERANT CHARGE FOR THE SET:
EXAMPLE:
To install a ASH 030S + Air treatment unit, with 22 m refrigerant line length between the condensing and Air treatment unit,
the refrigerant charge must be calculated as follows:
1 TABLE 1 (p. 20) shows that for 22m of line length between the condensing and Air treatment unit, the line sizes are: liquid 5/8"
and gas 1 1/8".
2 TABLE 2 (p. 20) shows, for line sizes of 5/8"-1 1/8", the charge per meter of line is: 177 g/m x 22m = 3894 g.
3 TABLE 3.1 shows charge of refrigerant for a set with 0m line length is: 6330 g.
4 To determine the charge of the set:
Add the charge in the refrigerant lines + the charge in the Air treatment unit and condensing refrigerant units.
Note: If the condensing unit includes the factory pre-charged kit, only the weight of refrigerant per meter of line in TABLE 2 is taken
into account.
100D to 140D units with 3 compressors are working using three capacity steps and 200D-230D with 4 capacity steps.
See the picture below for the installation in the case of units with tandem compressor circuit. An additional gas line has to be used
to assure the correct operation of the system.
Condensing unit with capacity reduction
Tandem compressor circuit
4
Min 0.25% gradient
2
H2
3
• 21 •
Charge of refrigerant (gr) R-410A for 0 meters of line (Cooling only) ASC + Air T. Unit
035S
040S
045D
7950
9745
6250
------
------
6250
Charge of refrigerant (gr) R-410A for 0 meters of line (Heat pump) ASH + Air T. Unit
035S
040S
045D
8835
10830
6940
------
------
6940
Total charge for the set: 3894 + 6330 = 10224 g
H1
H2
H4
2
3
H1
4
Models with tandem compressor
100D
Circuit 1
055D
070D
085D
5775
7870
9800
5775
7870
9800
055D
070D
085D
6420
8740
10900
6420
8740
10900
15 m max
5 m max
0,15 m min
Coupled trap
Lower trap with double tubes
Higher trap with double tubes
120D
Circuit 1
Circuit 1
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
100D
120D
140D
12130
15585
15500
10450
10045
15400
100D
120D
140D
13480
17315
17230
11600
11160
17100
2
H4
140D
200D
Circuits 1 & 2
200D
230D
23100
24250
23100
24250
200D
230D
25660
26950
25660
26950
3
4
H4
230D
Circuits 1 & 2