Name on
Code
Description
Visograph
Minimum pressure
(temperature)
LAC1
LAC1
alarm for
compressors in
Circuit 1
Minimum pressure
(temperature)
LAF1
LAF1
alarm for fans
section in Circuit 1
Maximum
pressure
(temperature)
HAC1
HAC1
alarm for
compressors in
Circuit 1
Maximum
pressure
HAF1
HAF1
(temperature)
alarm for fans
section in Circuit 1
C6.1.11/0718-0619/E
Alarms Circuit 1
Cause
▪ If AC1 = REL:
Suction pressure or
temperature ≤ SETC1 - AL3
▪ If AC1 = ABS:
Suction pressure or
temperature ≤ AL3
▪ If AC2 = REL:
Condenser pressure or
temperature ≤ SETF1 - AL24
for time AL26
▪ If AC2 = ABS: Condenser
pressure or temperature ≤
AL24 for time AL26
▪ If AC1 = REL:
Suction pressure or
temperature ≥ SETC1 + AL4
▪ If AC1 = ABS:
Suction pressure or
temperature ≥ AL4
▪ If AC2 = REL:
Condenser pressure or
temperature ≥ SETF1 + AL25
for AL26 delay
▪ If AC2 = ABS:
Suction pressure or
temperature ≥ AL25 for AL26
delay
Action
Only signalling
Only signalling
Only signalling
If AL27 = yes
▪ Compressors in Circuit 1
switch off with a delay from
2 different steps AL28
▪ All fans in Circuit 1 are
turned on. Inverter fan /
linear inverter for fan at
maximum speed
Reset
Automatically as soon as the pressure
or temperature reaches:
▪ If AC1 = REL:
SETC1 - AL3 + differential value
(differential = 0.3 bar or 1°C)
▪ If AC1 = ABS:
AL3 + differential value
(differential = 0.3 bar or 1°C)
Automatically as soon as the pressure
or temperature reaches:
▪ If AC2 = REL:
SETF1 - AL24 + differential value
(differential = 0.3 bar or 1°C)
▪ If AC2 = ABS:
AL24 + differential value
(differential = 0.3 bar or 1°C)
Automatically when the pressure or
temperature ≤
▪ If AC1 = REL:
SETC1 + AL4 - differential value
(differential = 0.3 bar or 1°C)
▪ If AC1 = ABS:
AL4 - differential value
(differential = 0.3 bar or 1°C)
Automatically when the pressure or
temperature ≤
▪ If AC2 = REL:
SETF1 + AL25 – differential value
(differential = 0.3 bar or 1°C)
▪ If AC2 = ABS:
AL25 - differential value
(differential = 0.3 bar or 1°C)
51