Pentair Hydromatic SPC-PANEL Installation And Service Manual page 4

Pump controls for 2 hp grinder pumps, simplex, single phase pump control panel
Table of Contents

Advertisement

Panel
Maintenance
vol tage to pull in without
chatter. If the problem is
a recurring one, measure
voltage with re cord er on a
24 hour basis.
b. Contactor may have dust
around magnet of coil
struc ture. Dry or clean
as re quired.
c. Make
sure
are located away from
any turbulence.
d. Dry out the junction box
(if furnished); moisture in
the junction box may tend
to cause relays to energize
intermittently.
6. Nuisance
tripping
overload on motor starters
or circuit breakers.
a. Check all reset buttons and
tripped breakers.
b. Check pump amp draw with
amp probe and compare to
nameplate amps on pump.
c. The impeller may be locked
up due to excessive debris
or solids.
d. Possible motor failure (fault
on windings).
e. Pump may be miswired to
terminal blocks.
7. Short cycling pump.
a. Check float controls.
8. Run light stays on.
a. Selector switch may be in
the Hand position.
4
9. Test for blown fuse.
a. Check for continuity with a
V-O-M set on ohm scale.
Single Phase Pump Only:
Connections
components
WARNING:
power from the panel before
making these checks.
1. Motor winding resistance
the
floats
readings.
a. Disconnect
motor leads.
b. Using a volt-ohm meter,
with the scale set on RX1,
measure
be tween the leads with the
following chart.
of
Winding
Main
Start
Both
2. Capacitor Check.
a. Make sure the capacitors
are discharged. Use extreme
caution; severe shock hazard
may exist with capacitors.
b. Disconnect the capacitor
leads
volt-ohmmeter
capacitor terminals.
c. The meter should indicate
low ohms when it is
first connected, but as the
ca pac i tor becomes charged
and
start
Disconnect
all
all
three
the
resistance
Typical
Motor
Resistance
Leads
Reading
Black to
Lowest
White
Black to
Next
Red
Lowest
(Middle)
White to
Highest
Red
and
connect
to
the
(by the meter), it will return
to a reading of infinity
(open circuit).
NOTE: Set the meter on the
RX10,000 scale to check
the run capacitor.
Set the meter on the
RX1,000 scale to check the
start capacitor.
3. Start relay check.
a. With power off, check the
start relay coil resistance. It
should be 3000 to
ohms.
b. Turn power on and run
pump in Hand position.
After the pump starts, check
the voltage from terminal
1 to terminal 2 on the start
relay to be sure that the
relay has operated. The
voltage from terminal 1 to
terminal 2 on the start relay
must exceed 10 VAC. For
some pumps the voltage
may exceed 400 VAC. If
after 5 seconds the voltage
from terminal 1 to terminal
2 on the start relay does
not exceed 10 VAC, stop
the pump as damage to the
start capacitor will occur
in about 15 seconds. If the
start relay is not operating,
check the pump and the
system voltage to be sure
that they match. Check the
power wiring to ensure
that the pump is connected
properly. Start the pump
once more and check to
see if the voltage from the
terminal for the black wire
a
to the white wire is within
system tolerance. Call for
help if you cannot resolve
the problem.