Page 1
Room Air Conditioners AUTO AUTO FAN CONTINUOUS ON OFF SET POINT SCHEDULE ROOM TEMP AUTO SPEED CHECK $MART FILTER SYSTEM FAN MODE POWER FAN SPEED SCHEDULE Q Chassis Models 115-Volt: SQ06, SQ08 115-Volt: EQ08 93001011_01...
Model information can be found on the name plate behind the front cover. Please complete and mail the owner registration card furnished with this product, or register online at www.friedrich.com. For your future convenience, record the model information here. MODEL NUMBER...
Safety Precautions Your safety and the safety of others are very important. We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety messages. This is a safety Alert symbol. This symbol alerts you to potential hazards that can kill or hurt you and others. All safety messages will follow the safety alert symbol with the word “WARNING”...
WARNING: Before Operating Your Unit Table 1. CIRCUIT RATING REQUIRED WALL Make sure the wiring is adequate for your unit. OR TIME DELAY RECEPTACLE FUSE MODEL VOLT NEMA NO. install or relocate this unit, be sure that the amperage rating of the circuit •...
Page 6
Standard Filter Cleaning / Installation Instructions STEP 2. STEP 1. up and outward. STEP 3. Procedure” on the inside of the front door. Figure 2 Figure 3 FILTER DOOR FILTER FILTER FRAME DOOR INSTRUCTIONS FRR075 FRR076 Premium Carbon Filter Installation Instructions STEP 1.
Page 7
Control Panel Operation seconds, the display switches off. Touching any button automatically changes the display to full brightness. CONTROL Figure 6 ONLY LOCKED COOL HEAT WI-FI CONNECTED (optional) SYSTEM Cycles between: - COOL TEMPERATURE - HEAT (if available) - FAN ONLY WAIT FAN MODE TEMPERATURE...
Page 8
Set TIME and DAY Figure 7 FRR130 time out and return to the normal operating display. 24-HOUR TIMER button is a 24-Hour FRIEDRICH AIR CONDITIONING CO. SAN ANTONIO, TX 1 30 set point cannot and will default to the last setting used. FRR097...
Page 9
Set Timer: Setting the Stop Time icon will remain illuminated, icon and as shown below. Press the FRR157 To deactivate and shut off the Timer, press the button again. Whether FRR145 the unit will turn back on in the last state operated. TIMER and PRE-PROGRAMMED SCHEDULING 24-Hour Timer - Re s i d e n t ia l S c h e d u l e...
Page 10
Residential Schedule AUTO FAN SET POINT SCHEDULE FRR161 FRR137 Timer - Scheduler Control Block Commercial Schedule button. FRIEDRICHLINK WI-FI CONTROL you to unlock the full control potential of your Kuhl unit. SCHEDULE and many other options remotely from a smartphone, tablet or computer. icon illuminates to indicate that the system is receiving a Wi-Fi connection.
Page 11
SETTINGS & ALERTS Check Filter Alert ºF - ºC Select icon displays. CHECK FILTER buttons simultaneously for three seconds. press the AUTO FAN normal with your desired setting. SET POINT CHECK FILTER FRR118 The alert can be dismissed by pressing the for 3 seconds.
Page 12
Remote Control Operation SCHEDULE Button – Press the SCHEDULE selected timer or schedule function. Pressing the button a second SCHEDULE Remote Control UP and DOWN Arrows - Pressing either the Getting Started changes the desired room temperature. These buttons are also used to located on the back of the unit.
Page 13
Figure 9 DISPLAY AUTO FAN CONTINUOUS AUTO SYSTEM FAN MODE SYSTEM FAN MODE POWER TEMPERATURE TEMPERATURE POWER DOWN FAN SPEED SCHEDULE SCHEDULE FAN SPEED FRR081 Figure 10 COOL HEAT FAN ONLY ICON ICON ICON SYSTEM MODE AUTO FAN CONTINUOUS MODE AUTO SPEED °F / °C...
Page 14
Friedrich dealer. CIRCUIT PROTECTION malfunction or failure of an air conditioner, therefore, it is necessary that the...
Page 15
Items required for installation (included in cooling only units, sold separately for heat/cool models) ITEM NO DESCRIPTION QTY. ITEM NO DESCRIPTION QTY. for replacement installations only Recommended tools required for installation: (not included) Required for all installations Recommended for thru-the-wall installations FOR WINDOW INSTALLATIONS, PROCEED TO THE NEXT PAGE.
Page 16
Standard Window Installation STEP 3. underneath the unit to lift and carry to the window, as shown IMPORTANT: Figure 14 ordinances prior to attempting installation. WARNING Falling Object Hazard Not following Installation Instructions for mounting your air conditioner can result in property damage, injury, or death.
Page 17
STEP 4. Place unit in window with the bottom support rail up against the curtains using both screw holes and your unit sleeve directly to onto upper support rail. The unit should be slightly the lower window stool using the instruction Steps 5.1 - 5.3 shown on the type of window, install the appropriate Steps 1 - 5, then you can proceed to Step 6 found on Page 18.
Page 18
STEP 5.2. through screw hole in the bottom center of sill channel using 1 sup- plied 1 you may secure each curtain with an additional screw through the remaining screw hole, insuring each window curtain is secured accommodate varying window types. 1 screw per curtain and install the appropriate security lock as recommended by window manufacturer.
Page 19
Figure 21 STEP 6. First, measure the width from one side of the air condi- other Figure 20 Plug in unit. STEP 8. Simply plug in the power cord and follow the operation steps CIRCUIT PROTECTION your unit, verify the ampere rating of the time-delay fuse or circuit breaker which protects your unit.
Page 20
Cord Routing Change Figure 23 Unplug unit. to the left side of the unit. For convenience and optimum appearance the direction of the power cord can be changed from left to right by following the procedure below. outlet. STEP 1. Save to reinstall later..
Page 21
STEP 2. STEP 3. keep cord in place. Figure 27 Figure 25 CLOSE-UP OF CORD UNDER LEFT MOUNTING SCREW EMBOSSMENT FACTORY SETTING WITH LEFT-SIDE FRR099 CORD PLACEMENT FRR201 EntryGuard Security Lock Figure 26 a feature that helps prevents kick-in intrusions. To engage this feature, use 2 supplied 1 to secure decorative front cover to sleeve.
Page 22
Thru-the-wall Installation STEP 3. IMPORTANT: STEP 4. Place the sleeve in the framed opening. ordinances prior to attempting installation. Measure and shim void spaces between the side of sleeve and NOTE: WARNING wood framing before securing to wall. STEP 5. Falling Object Hazard STEP 6.
Page 23
Figure 32 FRONT EDGE OF LOUVERS MUST ALWAYS BE OUTSIDE OF EXTERIOR WALL SURFACE. 3/4” MINIMUM FRONT EDGE OF SLEEVE TO INSIDE WALL SURFACE. 3/4” MINIMUM TRIM AROUND THE SLEEVE WITH A SUITABLE WOOD SLEEVE FRONT MOULDING AND FINISH TO SUIT. CAULK ALL AROUND 1”...
Page 24
Final Inspection & Start-up Checklist This is a warm weather appliance cool a room if it is already cool outside. installed properly and that they have not been damaged during the installation progress. Condensation is normal for the removal of condensate water, and that they meet the approval of the end user.
Page 25
FriedrichLink™ Adapter Accessory: KWIFI additional lubrication. additional programming options Wall Sleeve Decorative Color Front Panel Kits: (limited availability) KWBGEQA KWBLKQA KWBLUQA KWPNKQA around the sleeve and reseal areas as needed. KWREDQA KWWHTQA See www.friedrich.com for additional accessories for your unit.
Troubleshooting Tips The unit is turned to the off position, Turn the unit to the on position and raise or lower ● ● operation. Plug into a properly grounded 3 prong receptacle. ● ● proper receptacle type for your unit. ●...
Page 27
● The outside temperature is below ● cooling mode when the outside temperature is and the unit may be damaged. ● The digital control is set to fan ● Since the fan does not circulate the room air cycling mode. continuously at this setting, the room air does not to obtain optimum comfort levels.
Page 28
Addendum 1 Schedule Table with Energy Saving Values Residen al Schedule Period Tues Thur Start Time 600 Start Time 600 Start Time 600 Start Time 600 Start Time 600 Start Time 600 Start Time System Mode Cool System Mode Cool System Mode Cool System Mode Cool System Mode Cool System Mode...
Page 29
Friedrich Air Conditioning Company 10001 Reunion Place, Suite 500 San Antonio, TX 78216 1-800-541-6645 www.friedrich.com ROOM AIR CONDITIONERS LIMITED WARRANTY FIRST YEAR ANY PART: SECOND THROUGH FIFTH YEAR SEALED REFRIGERANT SYSTEM: APPLICABILITY AND LIMITATIONS: Products on which the model and serial numbers have been removed.
Page 30
® Kühl Q Chassis Performance Testing Installation and Test Method The following instructions only apply to laboratory test procedures and do not apply to actual product installation and operation. ANSI/ASHRAE Standard 16-1983 (RA 2009) Method of Testing for Rating Room Air Conditioners and Packaged Terminal Air Conditioners shall be adhered to when testing for obtaining cooling capacity and airflow quality for rating this room air conditioning unit.
Page 31
® Kühl Q Chassis Performance Testing Installation and Test Method continued Test Unit Installation As per ANSI/ASHRAE Standard 16-1983 (RA 2009), section 4.2.2, this air conditioner shall be installed per the instructions specified in this Installation & Operation Manual. Test Unit Settings Louver position: •...
Page 32
Friedrich Air Conditioning Co. 10001 Reunion Place, Suite 500 • San Antonio, Texas 78216 1-800-541-6645 www.friedrich.com Printed in the U.S.A. 93001011_01...
Page 33
Unidades de Aire Acondicionado SYSTEM FAN MODE POWER FAN SPEED SCHEDULE Modelos Q Chassis Kühl 115-Voltios: SQ06, SQ08 Kühl + 115-Voltios: EQ08 Frío & Calor Eléctrico 93001011_01...