Condensate Soakaway; Condensate Trap; Condensate Disposal Pipework; Inspection And Cleaning Of Trap - Grant Vortex Pro Internal Combi Series Installation And Servicing Instructions

Condensing oil boiler range
Table of Contents

Advertisement

6.5

COnDEnSatE SOaKaWaY

To keep external pipework to a minimum, locate the soakaway
as close as possible to the boiler but ensure it is at least 500 mm
from building foundations and away from other services, e.g. gas,
electricity, etc.
The condensate pipe may be run above or below ground level
and can enter either the top or side of the soakaway tube. Refer
to Figure 6-1.
Ensure that the drainage holes in the soakaway tube face away
from the building.
Backfill both the soakaway tube, and the hole around it, with 10
mm limestone chippings.
Only use a soakaway where the soil is porous and drains easily.
Do not use in clay soils or where the soil is poorly drained.
! CaUtiOn !
any damage due to condensate backing up into the boiler
due to a high water table, in the case of a soakaway, or
flooded drains when the condensate disposal is via a
gulley or soil stack, is not covered by the Grant product
guarantee.
6.6

COnDEnSatE tRap

Grant Vortex boilers are supplied with a condensate trap to
provide the required 75 mm water seal in the condensate
discharge pipe from the boiler.
The condensate trap is factory fitted inside the boiler casing
- mounted on the inside of the left hand side panel - in an
accessible position to allow for routine maintenance.
The upper holes can only be used on the Vortex Pro Combi XS
26.
! nOtE !
if required, this condensate trap may be re-located outside
the boiler casing. Refer to the procedure given in Section
6.9. this procedure must be carried out before the boiler is
installed.
This trap incorporates a float (which will create a seal when the
trap is empty) and an overflow warning outlet (fitted with a plastic
sealing cap), see Figure 6-2.
Overflow
warning
outlet
(with cap)
Condensate
outlet to
drain
figure 6-2: Condensate trap
A flexible hose connects the outlet of the condensing heat
exchanger to the trap inlet. Ensure the elbow connector on the
hose is fully pushed onto the 'top hat' inlet connector of the trap.
Section 6: Condensate Disposal
Condensate
drain pipe
from boiler
Unscrew
this cap for
maintenance
access
Condensate
trap
End cap
With the trap fitted inside the boiler casing, the sealing cap must
be fitted. If the trap is re-located outside the boiler then the
following applies:
If connecting the condensate discharge - either internally or
externally - into a waste system or soil stack - the sealing cap
must be fitted in the trap outlet.
On external discharge systems to a hopper, gully or
soakaway, the sealing cap should be removed from the trap
outlet.
If there is any discharge of condensate from the overflow
outlet, this could indicate a blockage (possibly due to
freezing). Turn off the boiler and investigate the cause. If
necessary contact your service engineer for assistance.
! WaRninG !
Care should be taken when siting the trap such that the
overflow outlet is readily visible and that any condensate
overflowing from the outlet cannot cause either a hazard to
persons or damage to surrounding property or equipment.
6.7
COnDEnSatE DiSpOSaL
pipEWORK
The condense trap outlet is at an angle of 48° below the
horizontal. This is to automatically gives a 3° fall on any
'horizontal' runs of condense disposal pipe. Refer to Figure 6-1
and see trap outlet/pipe.
The outlet of the trap will accept 21.5 mm to 23 mm OD
Polypropylene overflow pipe for the condensate discharge pipe.
This discharge pipe can exit through the left side of the boiler
through one of two pre-cut 'knock-outs' in the lower part of the
left casing panel. Push out the 'knock-out' from the required hole
taking care not to distort the side panel.
! nOtE !
When connecting plastic discharge pipe, ensure that the
pipe is fully pushed into the outlet end on the flexible hose
to prevent the possibility of leakage.
6.8
inSpECtiOn anD CLEaninG Of
tRap
The trap must be checked at regular intervals (e.g. on every
annual service) and cleaned as necessary to ensure that it is clear
and able to operate.
The bottom bowl can be unscrewed from the trap body for
inspection and cleaning.
To inspect and clean the trap:
1.
Disconnect flexible condensate hose from inlet connector.
2.
Unscrew the inlet connection nut.
3.
Remove the inlet connector and nut from trap.
4.
Disconnect the condensate disposal pipe from the trap outlet.
5.
Remove trap from bracket.
6.
Remove float from trap – clean if necessary.
7.
Inspect inside of trap and clean as necessary.
8.
Re-assemble trap, re-fit to boiler and re-connect flexible
hose. Ensure that hose is fully pushed onto the trap inlet
connector.
! CaUtiOn !
failure to regularly check and clean the condensate trap
may result in damage to the boiler and will not be covered
by the product guarantee.
page 19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Combi 26Combi 21Combi xsCombi xs 26Combi 36

Table of Contents