Troubleshooting
Common mistakes > Deviation between setpoint value and actual value signal
If the potentiometer settings for V
and V
restrict the
min
max
usable control range, this will change the characteristic
curve of the setpoint signal. Since the actual value
signal is always assigned to a characteristic curve of 0
V
, a restriction of the usable control range results in a
nom
different characteristic curve for setpoint value and
actual value signal.
In this case, a direct inference due to different signal
voltages at the setpoint value input or actual value
output without (rollover) calculation is not possible.

Control component Easy for VAV terminal units

27