ACS800-17LC-specific parameters in the IGBT Supply Control Program

The ACS800-17LC specific signals and parameters of IGBT Supply Control Program
are described in the tables below.

Terms and abbreviations

Term
B
C
Def.
FbEq
I
R
T.

Parameters

No.
Name/Value
16 SYSTEM CTR
INPUTS
16.15
START MODE
LEVEL
EDGE
31 AUTOMATIC
RESET
31.01
NUMBER OF TRIALS Defines the number of automatic fault resets the drive performs
0 ... 5
31.02
TRIAL TIME
1.0 ... 180.0 s
Definition
Boolean
Character string
Default value
Fieldbus equivalent: the scaling between the value shown on the control panel and the
integer used in serial communication
Integer
Real
Data type (see B, C, I, R)
Description
Parameter lock, parameter back-up etc.
Selects the start mode.
Starts the supply unit by the level of digital input DI2. The supply
unit starts to modulate and the charging resistors will be by-passed
when the supply unit RMIO board is powered, its digital input DI2 is
ON and there are no faults.
Starts converter by EDGE of control command. Control command
is selected by parameters 98.01 COMMAND SEL and 98.02
COMM. MODULE.
Automatic fault reset.
Automatic resets are possible only for certain fault types and when
the automatic reset function is activated for that fault type.
The automatic reset function does not operate if the drive is in local
control (L visible on the first row of the control panel display).
WARNING! If the start command is selected and it is ON,
the supply unit may restart immediately after automatic
fault reset. Ensure that the use of this feature will not
cause danger.
WARNING! Do not use these parameters when the drive
is connected to a common DC bus. The charging resistors
may be damaged in an automatic reset.
within the time defined by parameter 31.02.
Number of the automatic resets
Defines the time for the automatic fault reset function. See
parameter 31.01.
Allowed resetting time
115
T./FbEq
Def.
B
LEVEL
0
1
I
0
0
R
30 s
100 ...
18000
Start-up