FT 3000 Speed measurement system 3-channel speed control and overspeed protection System documentation FT 3000 : • Operating instructions FT 3000 • Operating instructions sensor • Rack 19 ¨ description • Bloc function description • System configuration • Connection diagram •...
Operating Instructions FT 3000 JAQUET AG Operating Instructions 377E-63917 V 4.00 20.12.04 FT 3000 Table of contents THE REDUNDANT OVER SPEED PROTECTION CONCEPT : .............. 5 SAFETY WARNING ............................. 7 APPLICATIONS............................7 CONSTRUCTION ............................7 FRONT PANEL DESCRIPTION ........................8 FTFU 3024.............................
Operating Instructions FT 3000 JAQUET AG 2 Safety Warning During operation, parts of the FT 3000 are under dangerous voltages. The units conform to protection class 1 and require an earth connection on the corresponding module connector and/or terminal on the 19" rack.
Operating Instructions FT 3000 JAQUET AG 5 Front Panel description 5.1 FTFU 3024 PSU Monitor PSU Monitor Green if 18V < V < 33V Green if 18V < V < 33V Self check system fault = red No system fault (Green)
Operating Instructions FT 3000 JAQUET AG 5.3 FTK 3072 PSU 1 monitor PSU 2 monitor Green if 18V < V < 33V Green if 18V < V < 33V Self check system fault = red No system fault = green...
Operating Instructions FT 3000 JAQUET AG 5.5 FTBU 3034 PSU Monitor PSU Monitor Green if 18V < V < 33V Green if 18V < V < 33V Self check system fault = red No system fault (Green) 6 signal monitoring channels.
Operating Instructions FT 3000 JAQUET AG 6 Specifications 6.1 Statistics Mean Time Between Failure for each channel (without voting) : 188683 hours # 21.5 years Mean Time Between Failure for each OSP channel (FTFU 3024) : 230700 hours # 26,0 years...
Page 12
Operating Instructions FT 3000 JAQUET AG potential free, isolation 500V, 50Hz,1 Min. from electronics and earth ie from front panel and card frames. for connection of electromagnetic, ferrostat or HF sensors, proximity switches and sensors Input card E-01: with line amplifiers.
Page 13
Operating Instructions FT 3000 JAQUET AG For average/max values and direction 2 inputs with common +24 level reference voltage - U low: 0...+3V or open -V of supply U high: +10...+33V, I source = max 3mA. Limit values 1 - 4...
Page 14
Operating Instructions FT 3000 JAQUET AG Accuracy 0.2% of the range Temperature drift typically +/- 150ppm/ºK, max +/- 300ppm/ºK Reaction time (step change) The minimum measuring time may be entered. Where the input period is shorter than the Fixed Time, the reaction time is - twice Fixed Time + max input period + 7.5ms...
Page 15
Operating Instructions FT 3000 JAQUET AG Relay card FTV 3090 4.0W 4.2W Comms module FTK 3072 2.0W 2.5W Power on surge is limited as follows Motherboard FTFU 3024/E01 7A Input cards E01, E02, E03 3.3A Converter FTW 3013 0.1A Relay card FTV 3090 0.1A...
Operating Instructions FT 3000 JAQUET AG 6.4 Technical data TCCC TCCC = Trip Chain Control Card, FTBU 3x34 INPUT : IN1 – IN6 6 potential free inputs. Input voltage for IN1- IN6 20 – 50 V, active level is 0V.
7.2.3 Frequency measurement (Period measurement principle) FT 3000 tachometers work on the continuous period measurement principle. The measuring chains for 3 frequency measurements are implemented in hardware using ASIC’s. Each of the 3 ASIC’s contain a counter to measure the period duration of up to 3 frequencies.
Page 18
Always remember to reset the Max value memory following testing with internal generators. Speed measurement and over speed trip monitors are separate functions within the FT 3000. In operation, there are 2 main reasons why the recorded Max value may not correspond to the limit setting: - the trip point is reached but the machine runs on until the shutdown valve has closed.
Operating Instructions FT 3000 JAQUET AG - gear machining inaccuracies, coupled with a low number of pulses configured for the trip setting may result in the over speed monitor activating the trip relay at a speed apparently lower than the limit set. The solution to this is to increase the number of pulses used to say 20% of the number of teeth on the gear 7.2.3.3 Comparators...
Page 20
Operating Instructions FT 3000 JAQUET AG F T 3 0 0 0 a c c e le r a tio n m e a s u r e m e n t e r r o r 1 0 0 0 .1...
Operating Instructions FT 3000 JAQUET AG 7.2.5 Limit value control There are 4 limit values available. There are independent upper and lower set points for each so that almost any hysteresis is possible. Limit1, Limit2 and Limit3 may be assigned to either speed monitor 1, speed monitor 2, speed monitor 3, comparator 1, comparator 2 or comparator 3 via software configuration.
Operating Instructions FT 3000 JAQUET AG 7.3.4 System monitoring The FTFU 3024 and FTK 3072 run background self tests on the most important CPU and EEPROM functions. SelftestOK is set (=1) when no fault exists, otherwise reset (=0). SystemOK in the status byte is an AND function of SelftestOK, SensorMonitorOK and PSOK. The constituents of SystemOK can be masked by software configuration.
Testing is only possible if there is no system fault, a speed monitor has been selected and TestOn is set active. The status of internal commands SpeedMonitorInputASelect, SpeedMonitorInputBSelect, UnderOverSelect and TestOn can be changed via configured binary inputs or FT 3000 PC commands. 7.8 Frequency outputs 3 frequency outputs are available.
Operating Instructions FT 3000 JAQUET AG Frequency output 2 having potential free, floating reference. Frequency output 3 controls the yellow front panel LED S. Every frequency output is programmable with one of 5 possible input signals (None, F1, F2, F3, F4).
Page 25
Operating Instructions FT 3000 JAQUET AG The FTBU card is designed to combine different trip commands to provide global shutdown control within the IEC 61508 SIL 3 regime. The overspeed functionality of the FT3000 is SIL 3 certified. The FTBU extends this certification to encompass trip signals from other sources such as temperature, pressure etc alarms.
Operating Instructions FT 3000 JAQUET AG 8 Installation 8.1 General The equipment conforms to protection class 1 and requires the connection of protective earth. This must be connected to the designated terminal before any other connections are made. The earth wire cross section must be at least the same size as the power cables.
Operating Instructions FT 3000 JAQUET AG 9 Setting parameters and operation 9.1 Software concept The input of various parameters is covered in section 5.11 and is via a user friendly operating system. Various windows permit the selection of functions and parameters using prepared menus.
Page 28
Operating Instructions FT 3000 JAQUET AG • Machine factor Global • Input card E01 / E02 / E03 • Optional converter Without / with • Converter type FTW 3013 • Relay card Without / with • Relay card type FTV 3090 •...
386DX, 486DX or higher, equipped with Microsoft® WindowsÔ 3.11 or higher, with serial interface COM1 or COM2 available and not running any application programs other than the FT 3000. The PC to FT 3000 interface cable must be a screened D9 male to D9 female, connected 1:1. (See 9.4.2) 9.2.2 PC software installation The FT 3000 software is supplied on 3.5"...
Operating Instructions FT 3000 JAQUET AG 9.2.3 Optimisation Various settings can be made in the initialisation file FT3000.INI that is saved in the Windows directory for the FT3000 application the first time the program is exited. The following settings are made from the FT3000 application menu - ‘Settings’ and should not be altered with a text...
RS-232 PC interface) or OFF-LINE by selection of the corresponding menu and change of the desirred parameters. OFF-LINE (without connected FT 3000-system): With the FT 3000 command: < configuration: module on the unit ..> the modules installed must be identified by means of activating the corresponding bush button on the configuration dialogue <module on the unit>...
Operating Instructions FT 3000 JAQUET AG 9.3.1.5 Measurement ( Min measuring time and number of measurements) The min. measuring time determines the minimum period during which the input frequency is measured. The effective measurement time is terminated upon completion of the min measuring time by the next positive edge of the input frequency.
Limit 4 is always defined as Comparator. The FT 3000 Windows software will allow a minimum pulse value to be set, which is appropriate to the limit setting. In the event that trips occur at speeds apparently below the limits selected, then this may be the result of gear machining inaccuracies.
Operating Instructions FT 3000 JAQUET AG Relay output: After connecting the supply the relays are initially inactive and then assume the state defined under <Limit value control> The first positive edge of the signal input starts the first frequency measurement •...
Operating Instructions FT 3000 JAQUET AG 9.5.1 Calibration tools • Frequency sources: Accurate frequency generator or generator with digital tachometer having accuracy better than 0.05% of the frequency setting. Where a lower demand on the accuracy exists, calibration can take place on the machine. The sensors then act as the frequency source and would be measured by a digital tachometer.
Operating Instructions FT 3000 JAQUET AG When the frequency is raised past the upper set points, the relays configured ‘normal’ energise and those configured ‘inverse’ de-energise. When the frequency drops back down to the lower set points, the relays configured ‘normal’ de-energise and those configured ‘inverse’...
Operating Instructions FT 3000 JAQUET AG 10 Mechanical construction See also sections 3 and 4. Up to 21 19" rack modules of 4 unit width can be installed in one rack. Every module is fixed into the rack using slides and retained screws.
Page 38
Operating Instructions FT 3000 JAQUET AG 377E-63917 Rev 4.00 page 38 of 47...
Operating Instructions FT 3000 JAQUET AG 11 Circuit description See also section 5 11.1 FTFU 3024 Motherboard and input card 11.1.1 Frequency measurement The measurement chains for the 3 frequency measurements are implemented in hardware in the 3 ASIC’s. The resultant floating point measurements <AbsolutA>, <AbsolutB> and <AbsolutC> are fed to the mpu for further processing.
Operating Instructions FT 3000 JAQUET AG 11.1.5 Reset and non-maskable interrupt (NMI) A hardware NMI reset circuit monitors the voltage Ulogic. The reset time constant is 200ms. Following this time, the mpu carries out a reset routine. A hardware NMI reset circuit monitors the input voltage +Vin to the Ulogic regulator.
Operating Instructions FT 3000 JAQUET AG For 1 of 2 monitoring the max permissible difference between 2 measurements (as absolute speed or % of nominal) is monitored ie Measured value A - Measured value B. The sensor status is derived from this difference as follows: Difference >...
Operating Instructions FT 3000 JAQUET AG 11.1.15 Direction of rotation discriminator The determination of phase relationship between the input signals enables the direction to be established. The required logic is in the ASIC’s. The mpu controls the display and eventual relay status. The front panel LED’s BW (backwards) and FW (forwards) signal the direction of rotation.
Operating Instructions FT 3000 JAQUET AG 11.4.2 RS 232 interface The interface is accessed via the front panel D9 connector on the FTK 3072. Transfer rate: 2400 Baud Parity: None The connection diagram shows the names with respect to Data bits: the equipment interface.
Operating Instructions FT 3000 JAQUET AG 12 Maintenance The electronic boards do not need any special maintenance activity. 12.1 Periodic test 12.1.1 Description The periodic test is used for proving the capacity of the system to detect an overspeed and to transmit the detection.
Operating Instructions FT 3000 JAQUET AG 12.2 Trouble shoting : Trouble shoting is needed when the S + M + P Alarm signal is asserted, or when the system behaviour under periodic test condition is false. 12.2.1 Procedure for the OSPS...
Operating Instructions FT 3000 JAQUET AG 12.2.2 Procedure for the TCCC : The Following procedure has to be applied : If the OK LED of a channel is red : (System Monitoring) Exchange the channel module (see chapter Module exchanging) If the trouble stays, check the rack wiring.
The short term storage temperature range is -40 ... +90ºC (max one day at any time, without any mechanical loading) If the unit is suddenly cooled, condensation may occur, which considerably reduces the insulation resistance. 14 Warranty The FT3000 is guaranteed for 12 months from the ship date. Please see JAQUET’s full terms and conditions. 15 Drawings Description Type Dwg.