Download Print this page

Honeywell 7800 SERIES Product Data page 8

Expanded annunciator
Hide thumbs Also See for 7800 SERIES:

Advertisement

7800 SERIES S7830 EXPANDED ANNUNCIATOR
1
BURNER
SWITCH
1
2
3
7. Check the power supply circuit. The voltage and
frequency tolerance must match those of the S7830. Do
not connect the S7830 to a power supply circuit that can
have wide line voltage variations. A separate power
supply circuit may be required for the S7830. Add the
required disconnect means and overload protection.
8. Check all wiring circuits (see Fig. 3) before installing the
S7830 on the wiring subbase.
9. Install all electrical connectors.
10. Restore power to the panel.
Mounting the S7830
NOTE: For installation dimensions, see Fig. 1 or 2.
65-0101—03
Q7800 WIRING SUBBASE
FOR S7830 FIELD WIRING
SINGLE FUEL - OIL
G
L2
L2
L1
3
(HOT)
MAIN VALVE
PROOF-OF-
CLOSURE
4
5
OPERATING
CONTROL
6
AUXILIARY
LIMIT 1
7
AUXILIARY
LIMIT 2
8
LOW WATER
CUTOFF
9
2
HIGH
LIMIT
10
AUXILIARY
LIMIT 3
11
120V, 50/60Hz POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
7800 SERIES TERMINAL 6 CAN BE CONNECTED TO ANY POINT S7830 TERMINAL 6 THROUGH 19.
(ANYTHING BEFORE CONNECTION ARE RUNNING LIMITS AND ANYTHING AFTER IT IS CONSIDERED
LOCKOUT INTERLOCKS DEVICE SPECIFIC.)
PLACE JUMPERS ON S7830 WIRING SUBBASE ONLY FOR UNUSED CONTROL, LIMIT, OR INTERLOCKS.
Fig. 5. S7830 wiring hookup—single fuel: oil.
3
12
HIGH OIL
PRESSURE
13
LOW OIL
PRESSURE
14
HIGH OIL
TEMPERATURE
15
LOW OIL
TEMPERATURE
16
ATOMIZING
SWITCH
17
18
19
AIR FLOW
SWITCH
20
AUXILIARY
LIMIT 4
21
AUXILIARY
LIMIT 5
22
20
6
PRE-
CONTROL
IGNITION
2
INTERLOCK
1. Mount the S7830 vertically (see Fig. 3, 4 and 5) or
horizontally with the knifeblade terminals pointing
downward. When mounted on the Q7800A Wiring
Subbase, the S7830 must be in an electrical enclosure.
2. Select the location in the electrical enclosure. Be sure to
allow clearances for servicing, electrical signal voltage
probes and electrical connections. Allow an optional
three inches (8 cm) minimum on both sides of the
S7830 for electrical signal voltage probes.
3. Make sure no subbase wiring is projecting beyond the
terminal blocks. Tuck in wiring against the back of the
subbase so that it does not interfere with the knifeblade
terminals or bifurcated contacts.
4. Mount the S7830 by aligning the four L-shaped corner
guides and knifeblade terminals with the bifurcated con-
tacts on the wiring subbase and securely tightening the
two mounting screws.
8
7800
7
SERIES
WIRING
LOCKOUT
SUBBASE
INTERLOCK
TERMINALS
M23115A

Hide quick links:

Advertisement

loading

This manual is also suitable for:

S7830