KEYSTONE FIGURE 221/222 BUTTERFLY VALVES
INSTALLATION AND MAINTENANCE INSTRUCTIONS
TROUBLESHOOTING
Symptom
Valve opens only a few degrees and stops
(it will not open to the full angle desired)
Leakage past the flange face
Leakage in the closed position
(leakage in the pipeline)
Excessively high torque
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product.
Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Keystone is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson
and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be
construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by
our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without
notice.
Emerson.com/FinalControl
Probable cause
Improper installation. The valve is improperly aligned Loosen the flange bolts, re-align the valve with flanges, and
1. Flange bolts are not evenly torqued
2. Improper flanges
The disc is not closing fully:
1. Actuator is not properly adjusted
2. Line pressure exceeds the valve's working pressure
1. Obstruction in the pipeline
2. Scale build-up on stem or seat
Solution
re-tighten the flange bolts to correct torque per ANSI requirements
1. Loosen the flange bolts and tighten the flange bolts to the correct
torque per ANSI requirements
2. Refer to "Flange and pipeline compatibility" on page 1
1. Refer to actuator adjustment procedures
2. Reduce line pressure to the valve's working pressure
1. Remove valve from pipeline and remove obstruction
3. Open and close the valve several times. Operate the valve at least
once a month. Check the valve seat for deterioration