• Copyright: All content on this document, such as text, graphics, logos and images is the property of Sapcon Instruments Pvt. Ltd. The selection, arrangement and presentation of all materials on this document and the overall design of this document is the exclusive property of Sapcon Instruments Pvt.
User Manual & Datasheet V 2.3 1 Introduction 3 Features Elixir is a Vibrating Fork Liquid Level Limit Switch. It is • Universal Power Supply: 18 - 55V DC, 90 - 265V AC suitable for level detection in storage tanks, mixing contain- ers and pipelines, for liquids that do not react with stainless •...
Value Response Time • Cover Delay - 0.8 seconds • Uncover Delay - 1 seconds Hysteresis 3 - 4 mm Density Above 0.7gm/ Viscosity Suitable for liquids with viscosity up to 10,000 cP Table 2: Application Specifications Sapcon Instruments Pvt.Ltd.
10 Influences on Switching Point 1. Process Pressure - It has no significant effect on the switching point of the device as can be observed from the Figure 3. Figure 3: Influence of Process Pressure on Switching Point Sapcon Instruments Pvt.Ltd.
User Manual & Datasheet V 2.3 2. Process Temperature - The influence of temperature on switching point of the device is described in Figure 4. Figure 4: Influence of Process Temperature on Switching Point Sapcon Instruments Pvt.Ltd.
User Manual & Datasheet V 2.3 3. Liquid Density - The influence of liquid density on switching point of the device can be seen in the graph in Figure 5. Figure 5: Influence of Liquid Density on Switching Point Sapcon Instruments Pvt.Ltd.
User Manual & Datasheet V 2.3 11 Installation & Handling Guide- lines The elixir can be installed in the vessel in almost any posi- tion. Previously existing bosses welded in any direction can be used. Since the fork can be screwed into a mounting...
Figure 9: Electrical Connections Figure 12: Setting Cover Delay • Else, elixir will indicate error after 2 minutes of pressing 4. Delay is entered, but not saved. To save and test the the ENTER key for the last time. Cover Delay, set the COVER switch back to OPEN po- sition as shown in Figure 13.
User Manual & Datasheet V 2.3 5. To test, dip elixir into the application material until the ELIXIR switching point is reached. STATUS COVER The STATUS LED will start blinking RED if the switch UNCOVER point is reached. It will blink for the number of seconds for...
In fail-safe ’High’ mode, instrument will switch to alarm condition if the connectivity between vibrat- ing fork and electronics is lost. 18 Maintenance The electronics of elixir instrument needs no mainte- nance. When cleaning and checking the vessel, free the Sapcon Instruments Pvt.Ltd.
User Manual & Datasheet V 2.3 20 Product Selection Order Code Product ELIXIR - Liquid Level Switch for Sticky, Corrosive, Agitated, Splashing, Foaming Liquids suitable for liquids with viscosity up to 10,000cp Type I : Integral (sensor in same unit)
Page 16
1.75H : 175 mm (Only with “VF110”) Probe Length (Depends on “Vibrating Fork”) 1.25H10H : 125 to 1000 mm (Only with “VF44”) 2H30H : 200 to 3000 mm (Only with “VF110”) Example - ELIXIR-I-SCUTE-PCPG13-SPN-U-MB10S4-VF110-HB-ES4-STS4-20T-2H30H Shows First Priority Entity Sapcon Instruments Pvt.Ltd.