Electrical Data - LG LSU243HLV Extended Piping Engineering Manual

Single zone wall mounted
Table of Contents

Advertisement

ELECTRICAL DATA

Table 3: Single Zone Wall Mounted Extended Piping Electrical Data
Model Number
Nominal Tons
LS243HLV
2
LS303HLV
2-1/2
LS363HLV
2-3/4
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
RLA = Rated Load Amps.
12 | PRODUCT DATA
Compressor (A)
Compressor Qty
Cool / Heat
1
14.6/14.6
1
14.6/14.6
1
14.6/14.6
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows:
(Largest motor FLA x 2.25) + (Sum of other motor FLA) rounded down
to the nearest standard fuse size.
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG " is a registered trademark of LG Corp.
Outdoor Unit
Fan Qty
Fan (A)
1
0.25
1
0.25
1
0.25
Recommended fuse size: 25A.
MCA (A)
MOP (A)
19
30
19
30
19
30