Anti-Bacteria - Danfoss ECL Comfort 210 Instructions Manual

Communication description
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Instructions
ECL Comfort 210 / 310, communication description
For circuit 2 add 100 to the addresses in Table 6-5 and for
circuit 3 add 200 to the addresses in Table 6-5.
Example:
The schedule for Tuesday is P1 starts at 6:30 and stops at
08:00, P2 starts at 16:30 and ends 22:00 and P3 is not active.
Write 630 to address 3120
Write 800 to address 3121
Write 1630 to address 3122
Write 2200 to address 3123
Write 2400 to address 3124
Write 2400 to address 3125
A time period can be deactivated by writing 2400 as start and
stop time.
If 0 is written as a value then all other previous values on that
day are also set to 0. Therefore 0 is recommended to only be
used as a start value for P1.

6.8 Anti-bacteria

The anti-bacteria function can be set to be active on several
days per week by setting the day setting to a value
corresponding to a combination of the days. Table 6-6 shows
how to calculate the value for days on which the function is
active. The letter combination is for Sunday, Saturday, Friday,
Thursday, Wednesday, Tuesday and Monday. Each day
corresponds to a bit in the day setting so they can be
combined together to give a binary value for the whole week.
Table 6-6 shows some examples of how the days can be
combined and gives the corresponding binary and decimal
values. Table 6-7 gives the addresses for the anti-bacteria
settings.
Table 6-6: Value examples for the day setting
Sun
Sat
Fri
0
0
0
0
0
0
0
0
0
0
0
1
1
0
0
1
1
1
The start time value must be in the range 0-47 which
corresponds to half-hour periods during the day like this: 0 =
00:00, 1 = 00:30, 2 = 01:00, 3 = 01:30 ... 47 = 23:30. The
function will activate at the same time for each of the chosen
days.
The duration is set in minutes and can last from 10 minutes to
600 minutes. The duration is 120 minutes by default.
The desired temperature can be set between 10 °C and 110 °C
but is typically around 80 °C. The anti-bacteria function is
turned off by writing the value 9 to the desired temperature
setting.
Danfoss District Energy
Thu
Wed
Tue
0
0
0
0
0
1
1
0
0
0
1
0
1
0
0
1
1
1
VI.LG.V3.02
Mon
Binary value
1
0000001
1
0000011
0
0001000
1
0010101
1
1001001
1
1111111
Decimal value
1
3
8
21
73
127
15
DEN-SMT/DK