3. Configuration Conditions of CC-Link System

A total of 64 remote I/O stations, remote device stations, or local stations can be connected for one master
station. Station type of ME96NSR is remote device station, and the number of occupied stations is 1
station.
However, the following conditions must be satisfied:
(1) { (1×a) + (2×b) + (3×c) + (4×d) } ≦ 64
a:Number of modules occupying 1 station
b:Number of modules occupying 2 stations
c:Number of modules occupying 3 stations
d:Number of modules occupying 4 stations
(2) { (16×A) + (54×B) + (88×C) } ≦ 2304
A:Number of remote I/O stations
B:Number of remote device stations (ME96NSR is applied.)
C:Number of local stations, standby master stations and intelligent device stations ≦ 26
(ME96NSR is applied.)
ME96NSR
(3/n)
≦ 64
≦ 42