Details Of Commands - Mitsubishi ME96NSR Programming Manual

Electronic multi-measuring instrument
Table of Contents

Advertisement

6.2.2

Details of Commands

The details of the command and reply data supported by ME96NSR are described here.
How to view the details of each command described is the following page is shown below.
Command value
1H
Data Monitor
After writing the command as shown below into the remote register RWwm, set the command execution
request flag to ON(1). When the command completion reply flag turned on, the specified item is reset.
The details of data written into the remote resister RWwm are shown in the table below.
Remote register RWwm(PLC→ME96NSR)
b15
m
Group No.
m+1
m+2
m+3
m, n: Address is allocated to the master module by the station number setting.
Contents of the resister sent from the master
station to the remote device station (ME96NSR).
The command value should be stored in the 1st
byte of the resister to be transmitted.
Because the length of transmission data is fixed
to 4 words, 00H should be stored in areas in
which no data is contained.
*1: It is described as 8 bits data by combining the unit No. (high 4 bits) and the command (low 4 bits).
b7
For example, When the unit No. is 0H and the command is 1H, it becomes "01H".
Command name
b8
b7
b4
b3
Unit No.
00H
Channel No.
00H
00H
00H
00H
b4 b3
b0
Command: data range ・・・ 0H~7H
Unit No.: data range ・・・ 0H~7H
Remote register RWrn(ME96NSR→PLC)
b0
b15
*1
1H
n
Channnel No.
n+1
Index number
n+2
n+3
Command
Contents of the resister received by the
master station from the remote device station
(ME96NSR).
Because the length of receive data is fixed to
4 words, 00H is stored in areas in which no
reply data is contained.
0H and 1H are used in ME96NSR
(18/n)
Description
b8
b7
b0
Group No.
00H
Low data
High data
LEN080334