Allen-Bradley Guardmaster EtherNet/IP 440R-ENETR Installation Instructions Manual
Allen-Bradley Guardmaster EtherNet/IP 440R-ENETR Installation Instructions Manual

Allen-Bradley Guardmaster EtherNet/IP 440R-ENETR Installation Instructions Manual

Network interface

Advertisement

Quick Links

Advertisement

Table of Contents
loading

Summary of Contents for Allen-Bradley Guardmaster EtherNet/IP 440R-ENETR

  • Page 1: Table Of Contents

    Installation Instructions Guardmaster® EtherNet/IP™ Network Interface Catalog number 440R-ENETR Table of Contents Topic Page Important User Information Environment and Enclosure Preventing Electrostatic Discharge About the Interface Before You Begin Determine Compatibility Install the Interface Set the Network Address Replace the Interface Wire the Interface Meaning of Status Indicators Specifications...
  • Page 2: Important User Information

    2 Guardmaster® EtherNet/IP™ Network Interface Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-IN001_-EN-P available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices.
  • Page 3: Environment And Enclosure

    Guardmaster® EtherNet/IP™ Network Interface Environment and Enclosure ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
  • Page 4: Preventing Electrostatic Discharge

    1770-4.1. If you would like a manual, you can: • download a free electronic version from the internet: http://www.rockwellautomation.com/literature/ • purchase a printed manual by contacting your local Allen-Bradley distributor or Rockwell Automation representative. Publication 440R-IN078A-EN-P - January 2014...
  • Page 5: About The Interface

    Guardmaster® EtherNet/IP™ Network Interface About the Interface Read this publication for information about the Guardmaster EtherNet/IP network interface, a communications interface for Guardmaster safety relays. This interface is designed for the Guardmaster safety relay optical bus that provides connectivity to an EtherNet/IP network with two RJ-45 connectors for two port pass-through to support daisy-chain or ring, and the existing star and tree network topologies.
  • Page 6: Before You Begin

    6 Guardmaster® EtherNet/IP™ Network Interface Before You Begin To effectively use the interface, note the following considerations. Determine Compatibility RSLogix 5000™ software version 19, or greater, must be used for the 440R-ENETR Add-on Profile. The 440R-ENETR EtherNet/IP network interface can be used with the following Guardmaster safety relays with version 2 (or greater) firmware: •...
  • Page 7 Guardmaster® EtherNet/IP™ Network Interface Mount the 440R-ENETR Interface on a DIN Rail Install the interface to the left of Guardmaster safety relays equipped with an optical communications bus. There must be no more than 5 mm horizontal separation between two adjacent relays for the optical communication bus to operate properly.
  • Page 8 8 Guardmaster® EtherNet/IP™ Network Interface 1. Position the interface module on an IEC standard (35 x 7.5 x 1 mm) top-hat DIN rail at a slight angle (DIN rail: Allen-Bradley part number 199-DR1; 46277-3; EN50022). 2. Press down firmly to install the interface on a DIN rail.
  • Page 9: Set The Network Address

    Guardmaster® EtherNet/IP™ Network Interface WARNING: If you connect or disconnect the communications cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
  • Page 10 10 Guardmaster® EtherNet/IP™ Network Interface This example shows the network address set at 163. When you use the rotary switches to assign an address and set it to 001, the interface gateway address is set to 0.0.0.0, and the subnet mask is 255.255.255.0.
  • Page 11: Replace The Interface

    Guardmaster® EtherNet/IP™ Network Interface WARNING: When you change switch settings while power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
  • Page 12 12 Guardmaster® EtherNet/IP™ Network Interface WARNING: If you connect or disconnect the communications cable while power is applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
  • Page 13: Wire The Interface

    Guardmaster® EtherNet/IP™ Network Interface Wire the Interface A1 = Supply A2 = Common Ethernet RJ-45 connector TOP VIEW ATTENTION: Do not connect 120/240V AC power to the A1/A2 DC supply. WARNING: Do not wire more than two conductors on any single terminal.
  • Page 14: Meaning Of Status Indicators

    14 Guardmaster® EtherNet/IP™ Network Interface Meaning of Status Indicators Refer to the following diagram and table for information on how to interpret the status indicators. 440R-ENETR Interface Module Module Status Link 1 Status Link 2 Status Network Status Indicator Status for Interface Module Indicator Status Description Module...
  • Page 15 Guardmaster® EtherNet/IP™ Network Interface Indicator Status for Interface Module Network Device is not on-line: Status - Device has not completed dup_MAC_id test. - Device not powered - check module status indicator Flashing green Device is on-line but has no CIP connections in the established state.
  • Page 16: Specifications

    16 Guardmaster® EtherNet/IP™ Network Interface Specifications Guardmaster EtherNet/IP Network Interface Attribute Value Safety classification value • Not applicable. This product is not intended for safety-related control or diagnostics. Guardmaster Safety Relay capacity • 6 Guardmaster safety relays Supported modules (FW Rev 2.xx •...
  • Page 17 Guardmaster® EtherNet/IP™ Network Interface General Specifications Attribute Value Indicators 2 red/green status indicators: – Module status – Network status (Ports 1 and 2 combined) 2 green/yellow status indicators: – Link 1 status – Link 2 status Power consumption, max. 2.2 W @ 26.4V DC Power dissipation, max.
  • Page 18 18 Guardmaster® EtherNet/IP™ Network Interface Environmental Specifications Attribute Value Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20...55 °C (-4...131 °F) Temperature, surrounding air max. 55 °C (131 °F) Temperature, nonoperating IEC60068-2-1 (Test Ab, Unpackaged Nonoperating Cold) IEC60068-2-2 (Test Bb, Unpackaged Nonoperating Dry...
  • Page 19 Guardmaster® EtherNet/IP™ Network Interface Certifications Certification (when Value product is marked) c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E192904. European Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4;...
  • Page 20 Documentation Feedback Please forward us your comments and suggestions using form RA-DU002. Allen-Bradley and Rockwell Automation are trademarks of Rockwell Automation, Inc. Guardmaster is a registered trademark of Rockwell Automation, Inc. EtherNet/IP is a trademark of ODVA. Trademarks not belonging to Rockwell Automation are property of their respective companies.