This instruction manual explains how to: ® • Install the Micro Motion Model RFT9739 rack-mount transmitter for use with Micro Motion Coriolis flow sensors, including instructions for: - Power-supply and sensor wiring - Output wiring • Initialize the transmitter • Diagnose and troubleshoot problems with the transmitter For more information about the Micro Motion sensors, see the appropriate sensor instruction manual.
Before You Begin continued Figure 1-1. RFT9739 exploded view Control board Module cassette Top cover Back panel Power board Side panel Front panel Side panel Bottom cover RFT9739 Rack-Mount Transmitter Instruction Manual...
• Install the transmitter in a non-hazardous area. • For intrinsically safe sensor installations, use this document with Micro Motion UL or CSA installation instructions. • For hazardous area installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
For configuration, calibration, or characterization procedures, see one of the following communications manuals: • Using the HART Communicator with Micro Motion Transmitters • Using ProLink Software with Micro Motion Transmitters • Using Modbus Protocol with Micro Motion Transmitters ™...
Getting Started continued Switch settings Switches 1 through 10, located inside the transmitter on the control board, control the following transmitter functions (see Figure 1-1, page 2, for the location of the control board): • Communications settings, including baud rate, stop bits and parity, data bits, communication protocol, and physical layer •...
Getting Started continued Security modes Switches 1, 2, and 3 are security switches, which enable the user to disable flowmeter zeroing, disable resetting of totalizers, and write- protect all configuration and calibration parameters. Switch settings enable any of eight possible security modes. Different modes determine which functions are disabled and whether configuration and calibration parameters are write-protected.
AMS on-line help: • Using the HART Communicator with Micro Motion Transmitters • Using ProLink Software with Micro Motion Transmitters • Using Modbus Protocol with Micro Motion Transmitters To enter security mode 8: 1.
Page 18
For more information about digital communications, see the following instruction manuals or use AMS on-line help: • Using the HART Communicator with Micro Motion Transmitters • Using ProLink Software with Micro Motion Transmitters • Using Modbus Protocol with Micro Motion Transmitters 3.
Getting Started continued Communication settings Switch 5 enables the user to choose the standard communication configuration or user-defined parameters. With switch 10 in the ON (CONFIG) position, switches 1 through 6 can be used for setting user- defined communication parameters. Standard communication setting To use the standard communication configuration, set switch 5 to the STD COMM position.
Transmitter Mounting General guidelines Follow these guidelines when installing the rack-mount RFT9739 transmitter: • Locate the transmitter where it is accessible for service and calibration. • Install the transmitter in a location that is compliant with the area specified on the RFT9739 approvals tag (see Figure 2-1, page 3). •...
Transmitter Mounting continued Figure 3-1. RFT9739 dimensions inches Dimensions in (mm) 5 17/32 (140.4) Back panel with Back panel with DIN 41612 male DIN 41612 male Y-shaped screw terminals fast-on/solder terminals 2 19/32 2 19/32 (66) (66) 13TE 13TE With Y-shaped With fast-on/solder screw terminals terminals...
Transmitter Mounting continued Figure 3-3. Space requirements for proper ventilation inches Dimensions in (mm) 5 3/64 (128.4) 1 22/32 (42.8) 5 3/64 (128.4) 1 22/32 (42.8) 5 3/64 (128.4) When installing multiple transmitters in a single rack, 15 watts of forced-air cooling, per transmitter, is required.
Transmitter Mounting continued Connectors The back panel of the transmitter housing has two 32-pin connectors, labeled CN1 and CN2, and a 2-pin connector, labeled CN3. Mating terminal strips, shipped with the transmitter, plug into the connectors. The detachable terminal strips enable wiring to remain connected when the transmitter is removed from the rack.
Sensor wiring is intrinsically safe. • Install the transmitter in a non-hazardous area. • For intrinsically safe sensor installations, use this document with Micro Motion UL or CSA installation instructions. • For hazardous area installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
CN2, terminals D2 (AC+), D6 (AC–), and Z2 (GND). In Europe, before making AC power-supply wiring connections at CN2, contact the Micro Motion Customer Service Department. In Europe, phone +31 (0) 318 549 443. To install power-supply wiring, refer to Figure 4-1 and follow these steps: 1.
To ensure proper grounding: • If the sensor installation must comply with UL or CSA standards, refer to the instructions in one of the following Micro Motion documents: - UL-D-IS Installation Instructions - CSA-D-IS Installation Instructions •...
Power-Supply and Sensor Wiring continued Figure 4-2b. Grounding detail — hazardous-area sensor installations If national standards are not in effect, adhere to these guidelines for grounding: • Use copper wire, 14 AWG (2.5 mm²) or larger wire size. • Keep all ground leads as short as possible, less than 1 ohm impedance.
Power-Supply and Sensor Wiring continued Fuses Fuses for the power-supply input are located inside the transmitter housing on the power board. The transmitter has two fuses: one for an AC power supply and one for a DC power supply. • The AC power supply uses a UL/CSA 250mA/250V, time-lag, 5x20mm. •...
The instructions in this section explain how to connect a fully prepared Micro Motion flowmeter cable to the RFT9739 and a sensor. The sensor can be a Micro Motion ELITE, F-Series, Model D, DL, or DT sensor. • The procedure for preparing Micro Motion flowmeter cable and cable glands is described in the instructions that are shipped with the cable.
Power-Supply and Sensor Wiring continued Table 4-2. Wire Sensor Transmitter Terminal designations color terminal terminal Function Black* No connection CN1-Z4 Drain wires* Brown CN1-Z2 Drive + CN1-B2 Drive – Orange CN1-B6 Temperature – Yellow CN1-B4 Temperature return Green CN1-Z8 Left pickoff + Blue CN1-Z10 Right pickoff +...
Power-Supply and Sensor Wiring continued Figure 4-6. Wiring to Model DT sensors Model DT Flowmeter RFT9739 sensor terminals cable terminals Maximum cable length 1000 ft. (300 m) Black User-supplied* (Drains from all Brown metal junction box wire sets) Yellow Black (Drains) with terminal block Brown Orange...
Output Wiring General guidelines WARNING Failure to comply with requirements for intrinsic safety if the sensor is installed in a hazardous area could result in an explosion. Output wiring is not intrinsically safe. • Keep output wiring separated from power-supply wiring and intrinsically safe sensor wiring.
Output Wiring continued Figure 5-1. Output terminals Table 5-1. Output wiring terminal designations CN2 terminal CN2 terminal number Function number Function D4, Z2 and Z4 Grounds DC power to pressure or DP transmitter D10 and D12 Optocoupler output Z10 and D26 Dual-channel (quadrature) frequency output, channel A D14 and Z14...
AMS on-line help: • Using the HART Communicator with Micro Motion Transmitters • Using ProLink Software with Micro Motion Transmitters • Using Modbus Protocol with Micro Motion Transmitters The mA outputs can produce a user-selected 0-20 or 4-20 mA current.
Output Wiring continued Use RFT9739 terminals CN2-D30 and CN2-Z30 for the primary mA output. Use terminals CN2-D28 and CN2-Z28 for the secondary mA output. See Figure 5-3. • Primary and secondary mA output loops are isolated and floating. Additional grounding will result in optimum performance, and optimum HART communication on the primary mA output.
Output Wiring continued ® Connections for HART Figure 5-4 illustrates how to connect a HART Communicator, the communication devices ProLink PC-Interface adaptor, or an AMS modem to the RFT9739 for digital communication over the primary mA output. For information about using the HART Communicator or ProLink program, see the appropriate instruction manual.
"Setting voltage level for VDE output requirements," page 37. • Output impedance is 2.2 kohm. • For use with receivers other than Micro Motion peripheral devices, check the instruction manual for the receiver to make sure its input- voltage and electrical-current ratings match the RFT9739 ratings.
Output Wiring continued Default configuration When the RFT9739 is shipped from the factory, the frequency/pulse output is internally powered by an isolated 15-volt source via a 2.2 kohm pull-up resistor. This internal current is limited to approximately 7 mA. See Figure 5-5. Figure 5-5.
Output Wiring continued Configuration for constant Applications with high capacitance loading will benefit by wiring the current frequency/pulse output circuit to maintain a constant current source of 50 mA for any load between 0 and 220 ohms. This configuration renders the control output circuit inoperable, and could affect the optocoupler and dual-channel frequency outputs.
After clipping resistor R5, an external power supply is required to use the transmitter’s frequency/pulse output. Before permanently altering any equipment, contact the Micro Motion Customer Service: • In the U.S.A., phone 1-800-522-6277, 24 hours • Outside the U.S.A., phone 303-530-8400, 24 hours •...
Output Wiring continued Figure 5-8. Frequency/pulse output RFT9739 wiring for open collector output terminals mode power supply Resistor (See note) FREQ+ (signal line) pulse counter RETURN (ground) Resistor must be of sufficient value to limit loop current to less than 0.1 ampere, depending on total loop resistance. Figure 5-9.
Output Wiring continued Figure 5-10. Resistor R5 on inside of back panel Inside of back panel Resistor R5 RFT9739 Rack-Mount Transmitter Instruction Manual...
Output Wiring continued Dual-channel frequency The transmitter has a dual-channel, phase-shifted frequency output for output custody transfer applications. The dual-channel frequency is derived from the frequency/pulse output, and represents the same flow rate as the frequency/pulse output. Each dual-channel frequency is always half the value of the frequency/pulse output.
Output Wiring continued Setting voltage level for To set the voltage level to 30 volts to meet VDE requirements for the VDE output requirements frequency/pulse output and dual-channel frequency output: 1. Remove the bottom cover of the transmitter housing. 2. Remove the back panel, and carefully pull it loose from the power board and the control board.
Output Wiring continued Figure 5-13. Jumper J10 on power board Power board Jumper Figure 5-14. Jumper JP1 on inside of back panel Inside of back panel Detail of back panel Jumper Area of detail RFT9739 Rack-Mount Transmitter Instruction Manual...
Output Wiring continued Optocoupler output The transmitter has an externally powered passive optocoupler output in addition to the frequency/pulse and dual-channel frequency outputs. The optocoupler output is derived from the primary frequency output, and represents the same flow rate variable as the frequency/pulse output.
1 or event 2. For information on configuring the control output for events, see any of the following manuals or AMS on-line help: • Using the HART Communicator with Micro Motion Transmitters • Using ProLink Software with Micro Motion Transmitters • Using Modbus Protocol with Micro Motion Transmitters Use RFT9739 terminals CN2-Z24 and CN2-D26 for the control output.
After clipping resistor R4 an external power supply is required to use the transmitter’s control output. Before permanently altering any equipment, contact the Micro Motion Customer Service: • In the U.S.A., phone 1-800-522-6277, 24 hours • Outside the U.S.A., phone 303-530-8400, 24 hours •...
Output Wiring continued Figure 5-17. Control output wiring for RFT9739 open collector mode output terminals power supply Resistor (See note) CONTROL (signal line) Receiving device RETURN (ground) Resistor must be of sufficient value to limit loop current to less than 0.1 ampere, depending on total loop resistance. Figure 5-18.
Output Wiring continued Figure 5-19. Location of resistor R4 on inside of back panel Resistor R4 Inside of back panel RFT9739 Rack-Mount Transmitter Instruction Manual...
Output Wiring continued Peripheral device wiring The wiring diagrams listed in Table 5-2 illustrate connections from the transmitter to Micro Motion peripheral devices. Table 5-2. Micro Motion peripheral device Figure Page Peripheral wiring DMS Density Monitoring System 5-20 diagrams DRT Digital Rate Totalizer with LED display...
Output Wiring continued Figure 5-21a. Wiring to DRT with LED RFT9739 output terminals DRT LED terminals Clip shields at this end Earth ground Figure 5-21b. Wiring to DRT with LCD RFT9739 output terminals DRT LCD terminals Clip shields at this end Earth ground RFT9739 Rack-Mount Transmitter Instruction Manual...
Output Wiring continued Figure 5-22a. Wiring to FMS-3 with LED RFT9739 output terminals FMS-3 LED terminals Clip shields at this end Earth ground Figure 5-22b. Wiring to FMS-3 with LCD RFT9739 output terminals FMS-3 LCD terminals Clip shields at this end Earth ground RFT9739 Rack-Mount Transmitter Instruction Manual...
Output Wiring continued Figure 5-25a. Wiring to Model 3300 with screw-type or solder-tail terminals RFT9739 Model 3300 output terminals terminals Clip shields at this end Figure 5-25b. Wiring to Model 3300 with I/O cable RFT9739 output terminals Model 3300 terminals Clip shields at this end RFT9739 Rack-Mount Transmitter Instruction Manual...
Output Wiring continued Figure 5-26. Wiring to Model 3350 RFT9739 Model 3350 output terminals terminals Clip shields at this end RFT9739 Rack-Mount Transmitter Instruction Manual...
Instructions for configuring the RFT9739 for pressure compensation are provided in the following instruction manuals and in the AMS on-line help: - Using the HART Communicator with Micro Motion Transmitters - Using ProLink Software with Micro Motion Transmitters - Using Modbus Protocol with Micro Motion Transmitters...
Output Wiring continued If the pressure transmitter requires a power supply less than or equal to 11.75 V, the RFT9739 can power the pressure transmitter. Use RFT9739 terminals CN2-Z6 and CN2-Z20. Terminal Z6 (P) is the power output to the pressure transmitter, and terminal Z20 (S) is the signal input to the RFT9739, as shown in Figure 5-27a.
Output Wiring continued Figure 5-27b. Wiring to pressure transmitter — external power, analog input WARNING: Pressure transmitter wiring is not intrinsically safe Power Optional supply loop device(s) 24 VDC 4-20 mA RFT9739 Pressure output terminals transmitter Terminal CN2-D14 must be connected directly to the negative (–) terminal of the external power supply.
Output Wiring continued Remote-zero switch The transmitter can be zeroed from a remote switch. If the transmitter display indicates flow rate, this contact will zero the flowmeter. If the transmitter display indicates flow total, this contact will reset the flow total.
• Some installations require a 120-ohm, ½-watt resistor at each end of the network cable to reduce electrical reflections. For information on communication protocol requirements for implementing an RS-485 network, phone the Micro Motion Customer Service Department: • In the U.S.A., phone 1-800-522-6277, 24 hours •...
Output Wiring continued Figure 5-29. RS-485 wiring One RFT9739 and a host controller Host See note See note RFT9739 controller Multiple RFT9739s and a host controller Host See note See note RFT9739 controller RFT9739 RFT9739 For long-distance communication, or if noise from an external source interferes with the signal, install 120-ohm ½-watt resistors across terminals of both end devices.
Page 67
Output Wiring continued To connect the transmitter to a Bell 202 network, use RFT9739 terminals CN2-Z30 and CN2-D30. See Figure 5-30. • SMART FAMILY devices require a minimum loop resistance of 250 ohms. Loop resistance must not exceed 1000 ohms. •...
Output Wiring continued 5.11 Security wiring Security wiring enables the use of remote (keyed) switches to disable the front-panel Scroll and Reset buttons. Scroll inhibit To install a remote (key) switch that disables the front-panel Scroll button, connect a signal line to terminal CN2-D16 (SCROLL INH) and a ground wire to terminal CN2-D14 (SIGNAL GND).
Startup Initialization After wiring has been connected, power can be supplied to the transmitter. During initialization, the transmitter performs a self- diagnostic test and produces the following series of displays, sequentially: 1. All pixels on 2. All pixels off 3. All eights 4.
Startup continued Using the display The RFT9739 display enables the user to: • View process variables, flow totals and inventory levels, and status messages (see page 60) • Set communication parameters (see page 61) • Zero the flowmeter (see page 65) •...
Startup continued When displaying total (TOT) or inventory (INV) screens, display resolution is 10 places, including the decimal point. The position of the decimal point is fixed, and depends on the flow calibration factor and units of measure. If totalizers exceed the maximum display capability, the display reads "*********".
Page 72
Startup continued M1 — Baud rate To set the baud rate: 1. Press and release the Scroll button to view each baud rate option. Choose from 1200, 2400, 4800, 9600, 19200, or 38400 baud. 2. Press and hold the Reset button to select the displayed baud rate. Release the Reset button when the display stops flashing.
Page 73
Startup continued M3 — Data bits and protocol The M3 screen enables selection of 7-bit or 8-bit mode for Modbus protocol, or 8-bit mode for HART protocol. • The HART protocol can use either the Bell 202 or RS-485 physical layer.
Startup continued Custody transfer event Event registers are provided for security requirements for custody registers transfer applications. When the transmitter is configured for security mode 8 (see Section 2.3, page 5), the transmitter meets security requirements for custody transfer described in National Institute of Standards and Technology (NIST) Handbook 44.
Startup continued Flowmeter zeroing CAUTION Failure to zero the flowmeter at initial startup could cause measurement error. Zero the flowmeter before putting it in operation. Flowmeter zeroing establishes flowmeter response to zero flow and sets a baseline for flow measurement. Zeroing procedure To zero the transmitter, follow these steps: 1.
For more information, see any of the following instruction manuals: • Using the HART Communicator with Micro Motion Transmitters • Using ProLink Software with Micro Motion Transmitters • Using Modbus Protocol with Micro Motion Transmitters Table 6-1.
Startup continued Totalizer control The transmitter's mass totalizer and volume totalizer can be started, stopped, and reset using any of the following: • A HART Communicator • ProLink software version 2.4 or higher • A Modbus device • AMS software In addition, the totalizer can be reset from the RFT9739 front panel.
Startup continued Table 6-2. Effect of security modes on totalizer control Flow Performed Mode Mode Mode Mode Mode Mode Mode Mode condition with No flow Scroll and Reset Disabled Disabled Disabled Disabled buttons HART or Modbus Disabled Disabled Disabled device With flow Scroll and Reset Disabled...
Troubleshooting General guidelines Troubleshooting a Micro Motion flowmeter is performed in two parts: 1. Tests of wiring integrity 2. Observation of the transmitter's diagnostic tools, which include diagnostic messages and fault output levels. CAUTION During troubleshooting, the transmitter could produce inaccurate flow signals.
• Use ProLink software version 2.3 or higher. • Use AMS software. • Contact the Micro Motion Customer Service Department to upgrade your HART Communicator or ProLink program: - In the U.S.A., phone 1-800-522-6277 - Outside the U.S.A., phone 303-530-8400...
Page 81
Troubleshooting continued ® ® Figure 7-1. HART Communicator, ProLink PC-Interface, and AMS modem connections Rack-mount RFT9739 HART socket (same circuit as PV terminals) HART Communicator, ProLink PCI, or AMS modem (Note 1) DCS or PLC with internal HART socket or (Note 3) resistor PV terminals...
Page 82
HART device displays an error message. Self-testing allows the transmitter to check its own circuitry. The transmitter works with a Micro Motion flow sensor to provide flow information. Therefore, many of the troubleshooting checks pertain only to the sensor.
• "Xmtr Failed" • "(E)eprom Error" • "RAM Error" • "RTI Error" If a transmitter failure occurs, contact the Micro Motion Customer Service Department. Table 7-2 describes transmitter failure messages. CAUTION Transmitter failures are critical, and could cause unintentional switching of process control devices.
Troubleshooting continued Overrange and sensor If a sensor failure occurs, if the sensor cable is faulty, or if measured flow, error messages measured temperature, or measured density go outside the sensor limits, the display produces one of the following messages: •...
Troubleshooting continued Table 7-3. Using overrange and sensor error messages Instructions 1. Turn off power to transmitter. 2. Unplug terminal blocks from transmitter back panel to check circuits. Message Other symptoms Cause(s) Corrective action(s) Drive Overrng or • Transmitter produces fault outputs •...
Troubleshooting continued Informational messages Information messages are described below. Table 7-5, page 77, summarizes informational messages and lists typical corrective actions. Power Reset indicates a power failure, brownout, or power cycle has interrupted operation of the transmitter. The transmitter has a nonvolatile memory, which remains intact despite power interruptions.
CN2, terminals D2 (AC+), D6 (AC–), and Z2 (GND). In Europe, before making AC power-supply wiring connections at CN2, contact the Micro Motion Customer Service Department. In Europe, phone +31 (0) 318 549 443. • If the transmitter is wired for an AC power supply, ensure switch S1 on the power board is in the appropriate position.
Troubleshooting continued Wiring For transmitter wiring instructions, refer to Chapter 4, page 17, and Chapter 5, page 25. Wiring problems are often incorrectly diagnosed as a faulty sensor. At initial startup of the transmitter, always check the following: 1. Proper cable, and use of shielded pairs 2.
CAUTION All configuration data will be lost by performing a master reset. Before performing a master reset, phone the Micro Motion Customer Service Department: • In the U.S.A., phone 1-800-522-6277, 24 hours • Outside the U.S.A., phone 303-530-8400, 24 hours •...
Troubleshooting continued Table 7-7. Default values after a master reset Characterization variables Default Default Flow calibration factor 1.00005.13 Mass flow factor Density Volume flow factor Density A 0.0000 g/cc Density factor K1 density constant 5000.00 Pressure Density B 1.0000 g/cc Pressure polling K2 density constant 50000.00...
For more information about troubleshooting the RFT9739 transmitter, about troubleshooting see any of the following instruction manuals or AMS on-line help: • Using the HART Communicator with Micro Motion Transmitters • Using ProLink Software with Micro Motion Transmitters • Using Modbus Protocol with Micro Motion Transmitters...
Appendix RFT9739 Specifications Performance specifications Sensor model Mass flow accuracy* ELITE liquid ±0.10% ± [(zero stability / flow rate) x 100]% of rate ±0.50% ± [(zero stability / flow rate) x 100]% of rate F-Series liquid ±0.20% ± [(zero stability / flow rate) x 100]% of rate ±0.70% ±...
Page 94
RFT9739 Specifications continued Functional specifications Output signals Analog Two independently configured analog outputs, designated as primary and secondary, can represent mass or volumetric flow rate, density, temperature, event 1 or event 2. With a pressure transmitter, can also provide indication for pressure. Internally powered, can be selected as 4-20 mA or 0-20 mA current outputs.
Page 95
RS-485 signal is a ±5 V square wave referenced to transmitter ground. Baud rates between 1200 baud and 38.4 kilobaud can be selected. Additional outputs Sensor frequency For use with Micro Motion peripheral devices, 8 V peak-to-peak at sensor natural frequency, referenced to sensor ground, 10 kohm output impedance. Sensor temperature For use with Micro Motion peripheral devices, 5 mV/°C, referenced to...
Page 96
RFT9739 Specifications continued API gravity API gravity references to 60°F (15°C). Uses correlation based on API equation 2540 for Generalized Petroleum Products. Accuracy of corrected density calculation relative to API-2540 from 0 to 300°F: Process fluid g/cc kg/m °API Diesel, heater, and fuel oils ±0.0005 ±0.5 ±0.2...
Page 97
RFT9739 Specifications continued Output testing Output testing can be conducted with a HART Communicator, the ProLink program, a Modbus host, or AMS software. Current source Transmitter can produce a user-specified current between 0 and 22 mA on a 0-20 mA output, or between 2 and 22 mA on a 4-20 mA output. Frequency source Transmitter can produce a user-specified frequency between 0.1 and 15,000 Hz.
Page 98
(1991) for surge and EFT. To meet the above specifications, the transmitter must be installed with an approved Micro Motion sensor, and the sensor cable must be either doubly shielded with full contact glands, or installed in continuous, fully bonded metallic conduit. The transmitter and sensor must be directly connected to a low-impedance (less than 1 ohm) earth ground.
Page 99
RFT9739 Specifications continued Physical specifications Housing 19-inch rack, European standard DIN 41494: 128 mm (3HE) high x 142 mm (28TE) wide x 231.9 mm deep. Electrical connections Two connectors per DIN 41612, type F. Choose either fast-on (wire-pin) solder connectors (standard) or Y-shaped screw-terminal connectors (optional).
12 to 30 VDC Code Configuration Enhanced EMI immunity (CE compliant) — requires installation with Micro Motion cable type CPLTJ or CFEPJ installed in conduit, or type CPLTS, CPLTA, CFEPS, or CFEPA installed with approved cable glands Code Approval Micro Motion standard — no approvals...
Page 102
Ordering Information continued Micro Motion instruction manuals ® Sensors • ELITE Sensor Instruction Manual • R-Series Flowmeter Instruction Manual ™ • R-Series Flowmeter with F fieldbus OUNDATION • T-Series Flowmeter Instruction Manual • F-Series Sensor Instruction Manual • Model D and DT Sensors Instruction Manual •...
Appendix Theory of Operation The flow tubes of the Coriolis mass flow sensor are driven to vibrate at their natural frequency by a magnet and drive coil attached to the apex of the bent tubes (see Figure C-1). An AC drive control amplifier circuit in the transmitter reinforces the signal from the sensor’s left velocity pickoff coil to generate the drive coil voltage.
Page 104
Theory of Operation continued Mass flow measurement The vibrating motion of the flow tube, combined with the momentum of the fluid flowing through the tubes, induces a Coriolis force that causes each flow tube to twist in proportion to the rate of mass flow through the tube during each vibrational cycle.
Page 105
The transmitter software contains a simplification of this correlation to maximize sampling frequency of the measurement. Accuracy of the Micro Motion correlation is ±0.0005 g/cc (±0.5 kg/m relative to the API-2540 equation. After temperature correction to 60°F (15°C), the density is converted to °API by the following expression:...
Page 106
Theory of Operation continued Pressure compensation A pressure transmitter can be connected to the RFT9739 for pressure compensation. The RFT9739 or an external source can supply power to the pressure transmitter. If the input is configured to indicate gauge pressure, the transmitter uses the pressure input to account for effects of pressure on the flow tubes of certain sensors.
Appendix HART Communicator ® Menu Trees Figure D-1. On-line menu 1 Mass flow 1 PROCESS 1 VIEW FIELD DEVICE 2 Temperature VARIABLES VARIABLES 3 Mass total 4 Density 5 Mass inventory 6 Volume flow 7 Volume total 8 Volume inventory 1 View primary variable 2 View secondary variable 2 VIEW OUTPUT...
Page 108
HART ® Communicator Menu Trees continued Figure D-1. On-line menu continued 1 Process variables See page 97 1 DensA 1 Flow cal factr 2 K1 2 Diagnostics and 3 DensB See page 97 2 DENS CAL FACTR service 4 K2 5 Temp coeff 3 Basic setup See page 97...
Page 109
HART ® Communicator Menu Trees continued Fast key The fast key code is a sequence of numerical button presses that corresponds to a specific menu option. Compare the fast key sequences in the table below with the menu options in the menu trees on pages 97 and 98.
2. If the identification sticker has been removed, use a HART device to identify the software version. See one of the following communications manuals for instructions: • Using the HART Communicator with Micro Motion Transmitters • Using ProLink Software with Micro Motion Transmitters Figure E-1. RFT9739 back panels...
Appendix Replacing Older Transmitters Step 1 Disconnecting the old transmitter WARNING Hazardous voltage can cause severe injury or death. Shut off power before disconnecting the transmitter. CAUTION Process control will stop when the transmitter is disconnected. Set control devices for manual operation before disconnecting the transmitter.
• If the serial number is 87263 or lower, check resistance values as described below. b. If the sensor and transmitter were properly wired with Micro Motion color-coded cable, the orange and violet wires provide temperature detection. These wires were connected to RE-01 terminals 3 and 9, or RFT9712 terminals 3 and 7, or RFT9729 terminals CN1-14d and CN1-16d.
Replacing Older Transmitters continued Step 3 Installing the RFT9739 transmitter WARNING Hazardous voltage can cause severe injury or death. Shut off power before disconnecting the transmitter. Follow these instructions to mount and wire the new RFT9739 transmitter: a. Mount the RFT9739 transmitter in accordance with the instructions in Chapter 3, page 11.
Figure F-2. RE-01 Remote Electronics Unit terminals Table F-2. RE-01 to RFT9739 terminal conversions Take the wire from ...and connect it to Wire color RE-01 terminal RFT9739 terminal (Micro Motion number: number color-coded cable) Function CN1-Z2 Brown Drive + CN1-B2 Drive –...
Figure F-3. RFT9712 Remote Flow Transmitter terminals Table F-3. RFT9712 to RFT9739 terminal conversions Take the wire from ...and connect it to Wire color RFT9712 terminal RFT9739 terminal (Micro Motion number: number color-coded cable) Function CN1-Z4 Black Shields CN1-Z2...
Figure F-4. RFT9729 Remote Flow Transmitter terminals Table F-4. RFT9729 to RFT9739 terminal conversions Take the wire from ...and connect it to Wire color RFT9729 terminal RFT9739 terminal (Micro Motion number: number color-coded cable) Function CN1-8d CN1-B2 Drive –...
Page 119
Use the procedures in one of the following manuals to characterize the sensor for flow, or see AMS on-line help: • Using the HART Communicator with Micro Motion Transmitters • Using ProLink Software with Micro Motion Transmitters • Using Modbus Protocol with Micro Motion Transmitters When entering the flow calibration factor, replace the second decimal point with the letter "C", if the sensor has a copper RTD, as shown in the...
Appendix Return Policy General guidelines Micro Motion return procedures must be followed for you to meet the legal requirements of applicable U.S. Department of Transportation (DOT) regulations. They also help us provide a safe working environment for our employees. Failure to follow these requirements will result in your equipment being refused delivery.
Index Page numbers in bold indicate illustrations. CMF sensor. See ELITE sensor About this manual Communication configuration Accuracy master reset default values Agency approvals 61–63 mode approved areas switches hazardous area installation 60–63 using display order an approved transmitter using switches Ambient temperature limits Communication output specification Conduit fitting...
Page 124
Index continued "mA fixed" security mode 8 74–75 "mA saturated" specification 72, 87 "Msg" test "not configured" wiring "power reset" F-Series sensor "RAM error" accuracy with "RTI error" repeatability with "security breach" wiring 74–75 84–88 "sensor error" Functional specifications 74–75 21, 87 "slug flow"...
Page 125
Index continued 27–29 30–35 mA outputs frequency/pulse 32, 32 AMS modem constant current Bell 202 multidrop network default configuration 31, 31 fault indication increased current 33, 34 HART Communicator open collector mode master reset default value test performance wiring 27–29 ProLink PC interface 56, 57 rangeability specification...
Page 126
Index continued ProLink program Scroll and Reset buttons communication configuration about 6–8 using switches security modes 29, 29 connecting to transmitter totalizer reset custody transfer event registers using 65–66 diagnostic messages zeroing with instruction manual Scroll inhibit 70–72 interrogation with Secondary output 79–80 master reset...
Page 127
Index continued 69–70 Temperature diagnostic tools 73–76 effect on transmitter display limits fault outputs Terminals. See also Wiring frequency/pulse output test Bell 202 network general guidelines 70–72 ELITE sensors HART Communicator F-Series sensors 23 mA outputs test Model D sensors 23 mA outputs trim 79–80 Model DL sensors 23...
Page 128
Index continued 51–53 ProLink PC interface pressure transmitter remote-zero switch sensor 22–24 RS-485 network sensor connections security diagrams sensors general guidelines DT sensor troubleshooting ELITE ELITE sensor Zero button security modes F-Series, D, DL sensor Zero failure grounding 65–66 Zeroing instruction manuals 66, 76 failure...
Need help?
Do you have a question about the Fisher Rosemount RFT9739 and is the answer not in the manual?
Questions and answers