Armstrong Integrated pumping system controllers, ips control-
lers 4000, are completely factory-assembled, tested, and
shipped to the job site as integral units ready to receive incom-
ing power supply. These instructions describe the procedures
to be followed during installation, commissioning and operation
to ensure optimum performance and reliability. When contact-
ing the factory for assistance, please provide the unit Serial
Number and other pertinent data, such as ips model no.

1.0 ips controllers 4000

1.1
installation instructions
Incoming supply – stand-alone ips controllers (no rack): The
incoming power supply should be brought in through the bot-
tom of the panel adjacent to the main terminals. Note that this
is the only electrical connection required at the panel.
The power supply voltage is 100-240 vac / 50-60 Hz as stan-
dard. Please refer to the wiring diagram supplied with the unit
for instructions on connecting power to the ips controller.
Incoming supply – ips system on rack: The incoming power
supply to the ips controller is achieved through a transformer
in the main enclosure of the whole ips system rack. No power
connection is required.
note:
All electrical wiring should be performed by a qualified
electrician in accordance with the latest edition of the National
Electrical Code, local codes and regulations.

1. 2 environmental limits

Operation temperature Range 0°c to 50°c ( 32°f to 12 2°f )
(must not be exposed to direct sunlight)
Operation humidity Range ( 10% - 85%) non-condensing
Ambient air temperature for storage: -20°c to 70°c
ips 4000 controller - Integrated pumping
system for variable primary applications
(-4°f to 158°f )

1.3 field devices installation instructions

Prior to using the display to configure the ips controller, make
sure all the field installed devices such as dp sensors, flow sen-
sors, temperature sensors are properly installed and wired to
the ips controller as per wiring diagrams provided.
note: Please fill in the ips commissioning check sheet (below)
which will help you through the set-up procedure of the
ips controller
1. 4 building automation system (bas)
connection
When the ips controller is provided with a serial port to com-
municate serially to the ba s, the possible communication
protocols are Modbus or BACnet. Refer to wiring diagrams
supplied with the unit for wiring instructions. ips controller
can also communicate to the ba s through a hard wired op-
tion. Please refer to the ips controller generic terminal block
diagram for the different parameters and data points commu-
nicated to the ba s. For more information please contact your
local Armstrong representative or Armstrong factory service
department.