• Cable Size Range: Feeder: #8 AWG—500 kcmil Motor Lead: #10 AWG—500 kcmil Pigtail Splice Kits • Copper Conductors for 5/8 kV or less Non-Shielded Cables 5316, 5317, 5318, 5319 Caution Working around energized systems may cause serious injury or death. Installation should be performed by 78-8096-4634-8-F personnel familiar with good safety practice in handling electrical equipment. De-energize and ground all...
Page 2
1.2 Remove cable insulation for length recommended by terminal lug manufacturer; if no information is available, remove fordepth of lug barrel. 2.0 Install Lugs 2.1 Install and crimp lugs per manufacturer’s direction. See back page if 3M Scotchlok Copper Lugs are used.
Page 3
3.3 FOR 8 kV ONLY. Cover the lugs and bolt with four half-lapped layers of Scotch ® Linerless Rubber Splicing Tape130C (Figure 4). Note: Lug cover will be printed with 5 kV rating. Mastic layer qualifies the part as 8 kV. Figure 4 ® Scotch Linerless Rubber Splicing Tape 130C 3.4 Install Lug Cover. Position Lug Cover so the punch holes are positioned between the cables (Figure 5). Note: ...
Page 4
INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. If this product is defective within the warranty period stated above, your exclusive remedy shall be, at 3M’s option, to replace or repair the 3M product or refund the purchase price of the 3M product.