3M 5316 Instructions
3M 5316 Instructions

3M 5316 Instructions

Motor lead pigtail splice for 5/8 kv non-shielded cables, for 1000 volts or less cables heavy-duty and two-hole lug applications

Advertisement

Quick Links

Motor Lead Pigtail Splice
for 5/8 kV Non-Shielded Cables
for 1000 Volts or less cables (heavy-duty and two-hole lug applications)
Instructions
Kit Contents (kit contains 3 splices):
3—Lug Covers
3—Locking Pins
3—Tubes Silicone Grease
3—Bag Solvent Cleaning Cloths
3—Mastic Sealing Strip(s)*
3— Strips Scotch
Linerless Rubber Splicing Tape 130C
®
3—Instruction Sheet
*Quantity varies with kit number.
Technical Information:
• For non-shielded cables
• Rated 5/8 kV
• For cables rated 1000 Volts or less (heavy-duty and two
hole lug applications)
• Cable Size Range: Feeder: #8 AWG—500 kcmil
Motor Lead: #10 AWG—500 kcmil
• Copper Conductors
 Caution
Working around energized systems may cause serious
injury or death. Installation should be performed by
personnel familiar with good safety practice in handling
electrical equipment. De-energize and ground all
electrical systems before installing product.
Table 1
Kit
Cable
Size
Range
(AWG/kcmil)
Number
Feeder Motor
5316
8–4
10–4
5317
2–1/0
4–1/0
5318
1/0–250
2–250
5319
250–500
4/0–500
3M
Motor Lead
Pigtail Splice Kits
for 5/8 kV or less Non-Shielded Cables
5316, 5317, 5318, 5319
78-8096-4634-8-F
CSA Certified for
600V or Less
Max.
Cable
Insulation
Bolt
Lead O.D.
Range
Length
0.30–0.51
in.
1
2
0.43–0.65
in.
3
4
in.
1
0.53–0.88
1
0.75–1.12
in.
1
in.
in.
in.
4
in.
1
2

Advertisement

loading
Need help?

Need help?

Do you have a question about the 5316 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for 3M 5316

  • Page 1 • Cable Size Range: Feeder: #8 AWG—500 kcmil Motor Lead: #10 AWG—500 kcmil Pigtail Splice Kits • Copper Conductors for 5/8 kV or less Non-Shielded Cables 5316, 5317, 5318, 5319  Caution Working around energized systems may cause serious injury or death. Installation should be performed by 78-8096-4634-8-F personnel familiar with good safety practice in handling electrical equipment. De-energize and ground all...
  • Page 2 1.2 Remove cable insulation for length recommended by terminal lug manufacturer; if no information is available, remove fordepth of lug barrel. 2.0 Install Lugs 2.1 Install and crimp lugs per manufacturer’s direction. See back page if 3M Scotchlok Copper Lugs are used.
  • Page 3 3.3 FOR 8 kV ONLY. Cover the lugs and bolt with four half-lapped layers of Scotch ® Linerless Rubber Splicing Tape130C (Figure 4). Note:  Lug cover will be printed with 5 kV rating.  Mastic layer qualifies the part as 8 kV. Figure 4 ® Scotch Linerless Rubber Splicing Tape 130C 3.4 Install Lug Cover. Position Lug Cover so the punch holes are positioned between the cables (Figure 5). Note:  ...
  • Page 4 INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. If this product is defective within the warranty period stated above, your exclusive remedy shall be, at 3M’s option, to replace or repair the 3M product or refund the purchase price of the 3M product.

This manual is also suitable for:

531753195318