  • Page 1 VLSP SD230 BPV10 SD230 BPV10 ..2 ..16 ..9 ..23 ..30 ..44 ..37 ..51...
  • Page 2 VLSP Components VLSP , pressure independent valve kit on/off TAC (TA Compact-P) SD230 BPV10 VLSP15LF Type Specification TAC15LF Two way pressure independent regulation and adjustment valve Low flow, DN15 SD230 Actuator on/off 230V 230V~ Shut off valve DN15 AV15 BPV10 By-pass valve DN10 VLSP15NF...
  • Page 3 VLSP VLSP , pressure independent If the valve (TAC) is closed, a low flow passes through the by-pass valve (BPV10) so valve kit on/off that there is always hot water in the water Two way pressure independent control and coil. This is to provide quick heat supply adjustment valve with on/off actuator, shut-off when a door is opened but also to provide a valve and bypass.
  • Page 4 VLSP Two way pressure independent regulation and adjustment valve TAC (TA Compact-P) Dimensions and technical specifikations ØB M30x1.5* Type Flow Vikt [mm] [mm] [mm] [mm] [kg] TAC15LF Low flow G3/4 M30x1,5 0,54 Normal flow G3/4 M30x1,5 0,54 TAC15NF TAC20 Normal flow M30x1,5 0,69 TAC25...
  • Page 5 VLSP Leakage rate: Noise Leakage flow ≤ 0,01% of max. q (setting 10) In order to avoid noise in the installation and correct flow direction. the valve must be correctly installed and the (Class IV according to EN 60534-4). water de-aerated. Connection: Measuring Male thread according to ISO 228.
  • Page 6: Measuring Accuracy

    VLSP Setting Shut-off 1. Turn the setting wheel to desired value, e.g. 5.0. 1. Turn the setting wheel clockwise to X. Measuring accuracy Sizing Maximum flow deviation at different settings. 1. Choose the smallest valve size that can obtain the design flow with some safety margin, see “q values”.
  • Page 7 VLSP Closing force Working range: X (closed - fully open) = 11,6 - 15,8 Closing force: Min. 125 N (max. 500 N) Ø22 The maximum recommended pressure drop over a valve and actuator combination for close off (DpV ) and to fulfill all stated close performances (DpV kPa*...
  • Page 8 VLSP By-passvalve (BPV10) On/Off-regulation, linear Action motion Supply voltage 230V, 50-60 Hz Power consumption <1,5 VA in operation <0,5 VA in the end position 100 N Stroke force Stroke length 6,5 mm Full stroke time "On" Nominal 3 s Full stroke time "Off" Nominal 12 s IP54 Protection class Screw-nut...
  • Page 11 Main offi ce Frico AB Tel: +46 31 336 86 00 Box 102 SE-433 22 Partille mailbox@frico.se Sweden www.frico.se For latest updated information and information about your local contact: www.frico.se...