Watts 909 Series Basic Installation Instructions

Watts 909 Series Basic Installation Instructions

Reduced pressure zone, backflow preventers, sizes 3/4"-2" 20-50mm

Advertisement

Quick Links

Series 909
Reduced Pressure
Zone Backflow Preventers
Sizes:
/
" – 2" (20 – 50mm)
3
4
• Installation
• Service
• Repair Kits
• Maintenance
No. 909QT-S 1
" shown
1
2
IMPORTANT: Inquire with governing authorities for local instal-
lation requirements.
NOTE: For Australia and New Zealand, line strainers should be
installed between the upstream shutoff valve and the inlet of
the backflow preventer.
Its important that this device be tested periodically in
compliance with local codes, but at least once per year
or more as service conditions warrant. If installed on a
fire sprinkler system, all mechanical checks, such as
alarm checks and backflow preventers, should be flow
tested and inspected internally in accordance with NFPA
13 and NFPA 25.
Limited Warranty: Watts Regulator Co. (the "Company") warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of
original shipment. In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge.
THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHER
WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty, and the Company shall not be responsible for any incidental,
special or consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs
resulting from labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or any other circumstances over which the Company
has no control. This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product.
Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages. Therefore the above
limitations may not apply to you. This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws to
determine your rights. SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT.
For field testing procedure, send for IS-TK-DP/DL,
IS-TK-9A, IS-TK-99E and IS-TK-99D.
For troubleshooting guide, send for S-TSG.
For other repair kits and service parts, send for
PL-RP-BPD.
For technical assistance, contact your local Watts
representative on back page.
RP/IS-909S

Advertisement

loading

Summary of Contents for Watts 909 Series

  • Page 1 13 and NFPA 25. Limited Warranty: Watts Regulator Co. (the “Company”) warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of original shipment. In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge.
  • Page 2: Basic Installation Instructions

    4. Normal discharge and nuisance spitting are accommo- avoid dislodging O-rings or causing damage to internal dated by the use of a Watts air gap fitting and a fabricated components. indirect waste line. Floor drains of the same size MUST 10.
  • Page 3 Installation Indoors ASSE approved for vertical installation 909QT-S ⁄ " – 2" flow up and down Min. For indoor installations, it is important that the ⁄ " valve be easily accessible to facilitate testing and servicing. Series 909 may be installed either vertically Air In or horizontally.
  • Page 4 Test Procedure for Reduced Pressure Assembly A. All needle valves must be closed on test kit. B. Open test cock No. 4 and flush test cocks Nos. 1, 2 and 3 on reduced pressure assembly then close test cock No. 4. C.
  • Page 5 Servicing First and Second Check Valves " to 2" (20 to 50mm) Note: No special tools required to service Series 909 Relief Valve Service Parts Kit Cover First Check Service Parts Kit Cover O-ring Second Check Body Spring Service Parts Kit Disc 1.
  • Page 6: Repair Kits

    Servicing the Relief Valve " to 2" 1. Remove the four bolts that hold the relief valve cover Piston in place. Piston Size ⁄ ” – 1” Relief Valve 2. Remove the cover. The stainless steel adapter, with o-ring O-ring Assembly attached will be free to be removed simultaneous with the Seat...
  • Page 7 B.4 Excessive backpressure, freezing or water hammer has distorted the second check. water hammer in the system downstream of the device. Use Watts No. 601 to dampen out back pressure and No. 15 to eliminate water hammer. Replace defective second check assembly. In case of freezing;...
  • Page 8 For additional information, visit our web site at: www.watts.com A Watts Water Technologies Company USA: No. Andover, MA • Tel. (978) 688-1811 • Fax: (978) 794-1848 • www.watts.com Canada: Burlington, ON • Tel. (905) 332-4090 • Fax: (905) 332-7068 • www.wattscanada.ca...

This manual is also suitable for:

909qt-s909qt