Carrier 09DK Series Installation, Start-Up And Service Instructions Manual page 5

Air-cooled condenser units 50/60 hz
Table of Contents

Advertisement

COIL CONNECTION DIMENSIONS — MM [IN.]
UNIT
A
B
09DK
34.9 I.D.
28.5 I.D.
044
3
1
[1
/
]
[1
/
]
8
8
NOTES:
1. There must be 1220 mm [4-0] for service and for unrestricted airflow on
all sides of unit.
2. There must be minimum 2440 mm [8-0] clear air space above unit.
3. The approximate operating weight of the unit follows:
TOTAL
WEIGHT
UNIT 09DK
Lb
Kg
044
1676
760.2
044C
1984
900.0
C
— Units with optional copper-fin coils
4. Dimensions are in mm. Dimensions in [ ] are in feet-inches.
5. Dimension "E" for 34.9 mm I.D. is 118 mm [4
Dimension "E" for 28.5 mm I.D. is 112 mm [4
C
D
E
22.2 I.D.
15.9 I.D.
SEE
7
5
[
/
]
[
/
]
NOTE #5
8
8
OPERATING WT. AT SUPPORT
POINTS
1 & 2
3 & 4
Lb
Kg
Lb
Kg
391
177.4
447
202.8
462
209.6
529
240.0
].
5
/
8
].
7
/
16
Fig. 5 — Dimensions, 09DK044