Piping Checklist - Bell and Gossett e-80SC Series Instruction Manual

Table of Contents

Advertisement

Guideline
Make sure that the space around the pump is sufficient.
If you require lifting equipment such as a hoist or tackle,
make sure that there is enough space above the pump.
For pumps with the optional ITSC/IT installed, be careful not
to damage the ITSC/IT during lifting. Do not wrap the sling
around the ITSC/IT.
Protect the unit from weather and water damage due to rain,
flooding, and freezing temperatures.
Do not install and operate the equipment in closed systems
unless the system is constructed with properly-sized safety
devices and control devices.
Take into consideration the occurrence of unwanted noise and
vibration.
If the pump location is overhead, undertake special
precautions to reduce possible noise transmission.
When possible, locate the pump below the fluid level.

4.1.3 Piping checklist

WARNING:
• The heating of water and other fluids causes volumetric expansion. The associated
forces can cause the failure of system components and the release of high-
temperature fluids. In order to prevent this, install properly sized and located
compression tanks and pressure-relief valves. Failure to follow these instructions can
result in serious personal injury or death, or property damage.
• Avoid serious personal injury and property damage. Make sure that the flange bolts
are adequately torqued.
NOTICE:
Never force piping to make a connection with a pump.
Check
Check that a section of straight pipe, with a length that
is five times its diameter, is installed between the
suction side of the pump and the first elbow, or that a
B&G Suction Diffuser Plus is installed.
Check that the suction and discharge pipes are
supported independently by use of pipe hangers near
the pump .
Check that there is a strong, rigid support for the
suction and discharge lines.
For pumps with flanges, check that the bolt holes in
the pump flanges match the bolt holes in the pipe
flanges.
Series e-80SC INSTRUCTION MANUAL
Explanation/comment
This facilitates ventilation, inspection, maintenance,
and service.
This makes it easier to properly use the lifting
equipment and safely remove and relocate the
components to a safe location.
This is applicable if nothing else is specified.
Acceptable devices:
• Pressure relief valves
• Expansion tanks
• Pressure controls
• Temperature controls
• Flow controls
If the system does not include these devices, consult
the engineer or architect in charge before you
operate the pump.
The best pump location for noise and vibration
absorption is on a concrete floor with subsoil
underneath.
Consider a consultation with a noise specialist.
This facilitates priming, ensures a steady flow of
liquid, and provides a positive suction head on the
pump.
Explanation/comment
This reduces suction turbulence by
straightening the flow of liquid before it enters
the pump.
This eliminates pipe strain on the pump .
As a rule, ordinary wire or band hangers are not
adequate to maintain proper alignment.
4 Installation
Checked
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents