Contact Adjustments; Measurements; Adjusting Center-Pole Contact Wipe And Overlap; Field Discharge Contacts - Center Pole - GE AK-2-50 Maintenance Manual

Low-voltage power circuit breakers
Table of Contents

Advertisement

GEK-7303 Low Voltage Power Circuit Breakers
6
5
4
3
2
1.
Springs
2.
Insulation
3. Stationary Contact
4. Pin
.
5. Screw
6. Movable Contact
7. Pin
8.
Buffer
·
9
•.
Crossbar
10.
Adjusting
Plate
11.
Bolt
12. Buffer
13. Screw
14. Shims
15.
Bolt
16. Pin
17. Pin
13 14
Fig.
17
(227Dl
74)
Field discharge c~ntacts (center pole)
When the breaker is tripped, the opening springs
pull crossbar
(9)
downward, opening the breaker's
outer poles. As the crossbar moves downward, link
(A) rotates about a fixed center (17)", collapsing
toggle links (B) and (C) upward, therby closing
center-pole contacts through
connecting
link
(D).
Link (C) consists of two
links
riveted together,
forming a single
triangular·
link.
Contact Adjustments
Measurements
For
contact measurements and adjustments
of the two outside poles of the breaker, refer
to POLE UNIT ASSEMBLY.
Contact measurements of the center-pole field
discharge contacts should
be
made on the left
contact and
be
within
the
following
limits:
1.
Contact wipe,
3/16 in.
to
7/16
in.
2.
Contact pressure,
·
1 0 lb. to 16
lb.
3.
Ga_p between contacts when center pole is
open,
1
1/2 in. to
1
3/4 in.
4.
Overlap
·
between the center-pole contacts
and the arcing contacts of the outer poles, 3/16 in
··
to 7/16 in.
_
·
Measurements of the center-pole contact wipe
20
and pressure may be made by following the same
procedure as outlined for the standard pole unit
in POLE UNIT
ASSEMBLY:
·
Overlap of the center-
pole contacts and the outer pole arcing contacts
may be checked by the following procedure:
.
-
.
1.
Remove arc quenchers (see ARC
QUEN-
CHER).
·
.
.
2.
Insert safety pin in push rod. (See
Fig.
3
under MAINTENANCE.)
3.
Operate closing me~hanism
with
mainten-
ance handle until arcing contacts of outer poles
just touch.
4.
Measure distance between forward edge of
left stationary contact of center pole
and
surface
of insulation block behind contact.
5.
Continue to operate maintenance closing
handle
until center-pole contact opens fully.
6.
Repeat measurement
described in step 4.
Difference between
measurements indicates amount
of overlap.
Adjusting
Center-pole Contact
Wipe
and Overlap
·{Fig.
17)
If
measurements
reveal either
incorrect center-
pole contact wipe
or incorrect
overlap of confacts,
adjustments should be made by the following
procedure: