Quick Close Breaker Adjustments; Quick-Closing Release Latch; Release Arm Adjusting - GE AK-2-50 Maintenance Manual

Low-voltage power circuit breakers
Table of Contents

Advertisement

GEK-7303 Low Voltage Power Circuit Breakers
reduction unit and through a worm gear and a
planetary
g~ar
train drives the
crank
(10, Fig. 10)
with a reduction 1000:1. To remove the motor
and gear-reduction unit,
_
proceed
as
follows:
1
.
Remove the front frame (see SEPARATION
OF FRONT AND R~AR FRAME.)
2.
.
R emove
closing
springs
and crank-shaft
as
illustrate~ iii Fig. -12 and 13.
3.
Disconnect the leads from motor and remove
the -wires
attached to gear unit housing.
4.
Remove
four
bolts
at
the bottom of the
front frame and one bolt at top of
gear
reduction
unit.
The.
motor
and gear
unit may n!JW be removed
.
NOTE:
If
it
is desired to replace
only
the
motor unit, disconnect the
motor.
leads
-
and
remove only the hardware fastening it to the
. -
-gear-reduction unit. When removing the motor
·
only, the front frame
should
be
placed
front
·
side
down to
prevenJ.
the oil escaping
from
the
.
·
gear unit.
·
The
gear
.
reduction
unit
contains 4 ounces of
oil similar to Atlantic Refining Company's Grade
HFS No. 3.
·n
should not be necessary to add
or·
change oil except
when
the gear'.'.'reduction
unit-and motor are disassembled •
.
-
·
QUICK CLOSE BREAKER
· .
ADJUSTMENTS
.
The quick
close
breaker basically differs from
the standard breaker in that ~e p~echarging
_
operati<;m
is extended to and slightly past the top
dead-
center
position
of
the closing spring assembly.
As
_.!tie springs
start
.
to
discharge~
to
close
the
bre_aker, the discharge operation is arrested by
~
pi:ap
and latch
arrangement.
The subsequent
closing operation
is accomplished
·
by tripping
the-latch to release the prop which in turn allows
the
springs
to
continue
the interrupted discharging
operation
and close the breaker.
The
gear
reduction unit for the standard breaker
is
·
not interchangeable with the gear reduction
uniLon the quick close unit because the quick
close
gear
reduction unit employs a slip
clutch
to
relieve the pressure that would otherwise
be.
exerted between the output crank plate and
the
prop. .
·
After the
·
closing springs have been completely
charged and the prop and latch system are pre-
venting closure
of
the breaker, the closing opera-
tion may be .accomplished by energizing the closing
relay.
thni the control relay contacts, or man-
ually- by depressing the push to close lever which
mechanically displaces the latch to allow the
break~r to close.
·
.
.
.
.
On drawout breakers an interlock between the
··
breaker and enclosure requires the springs to
be discharged before the breaker
can
be removed
from the enclosure.
16
.
.'
' c"
Fig.
14A
·
Quick-Closing
Release Latch - Fig. 14A
Adjust
the
engagement of the roiler
on
the latch
to
1/8
11
±1/64"
by turning the
screw
"A".
After
adjustment is set, lock the bolt with the hex nut
"B".
Adjust the clearance between the latch and
the
roller
to 1/32+0-1/64 by turning the screw
"C".
D
Fig. 14B
Release Arm Adjusting - Fig. l4B
Adjust release arm screw
"P"
so
that the stroke of
the armature of the closing solen<:>id releases the
roller from the latch with a minimum
of
1/32"
over-travel. ·Check
.
by
using
1/32"
GO
and
3/32"
NO·
GO
gauge between armature
·
and
magnet.

Hide quick links:

Advertisement

Table of Contents
loading