Overview of scaling an arbitrary range ................... 8 Scaling of range ..........................8 Diagram for scaling of range ......................9 Factory setting ..........................10 Error search ............................10 Technical data ............................10 Housing Type K ............................ 12 MU1000K 12370-0705-01 Page 2 / 12 www.ziehl.de...
1 Application and short description Universal-measuring-transducers MU1000K can measure signals Pt100 (RTD) and DC current (0/4-20 mA) and voltage (DC 0/2-10 V). Several measuring-ranges are pre-programmed. More can be easily scaled. Temperatures at sensors Pt 100 can be evaluated from -200 °C to + 800 °. The output-signals 0/2-10 V and 0/4-20 mA are potentially separated from inputs and supply voltage.
If the cooling becomes more difficult e.g. through close proximity of apparatus with elevated surface temperature or hindrance of the cooling air, the tolerable environmental temperature is diminishing. MU1000K 12370-0705-01 Page 4 / 12...
6 Commissioning 6.1 Overview of commissioning The MU1000K can be commissioned to predefined standard ranges or scaled to an arbitrary range. There are two different ways to do the settings: Point 6.2 – 6.4: MU1000K setting a predefined range Point 6.5 – 6.7: MU1000K scaling an arbitrary range 6.2 Overview of the predefined standard ranges...
• Select with button [Set] the output range flashes U / I 0 - 10V / 0 - 20mA 2 - 10V / 4 - 20mA • Press button [Down] End of parameterization, Power LED lights permanently MU1000K 12370-0705-01 Page 6 / 12 www.ziehl.de...
• Select with button [Set] the output range flashes U / I 0 - 10V / 0 - 20mA 2 - 10V / 4 - 20mA • Press button [Down] End of parameterization, Power LED lights permanently MU1000K 12370-0705-01 Page 8 / 12 www.ziehl.de...
6.8 Diagram for scaling of range Mode Normal state Signal input = Zero point Signal input = Full scale MU1000K 12370-0705-01 Page 9 / 12 www.ziehl.de...
Resolution 11,6 Bit < 6,1 µA ≤ 500 Ω Load (250 Ω – resistance) / 250 Ω * 0,3 % of final value Error from Load Response-time T09 Pt100 sensor input < 350ms MU1000K 12370-0705-01 Page 10 / 12 www.ziehl.de...
Page 11
Protection class housing / terminals IP40 / IP 20 Snap mounting on 35 mm standard rail EN60715 or Mounting M4 screws (additional bar not included) Mounting position beliebig Weight app. 100 g Subject to technical changes MU1000K 12370-0705-01 Page 11 / 12 www.ziehl.de...
9 Housing Type K Dimensions in mm 22,5 110,0 100,5 lower part upper part screw holes for screw-mount MU1000K 12370-0705-01 Page 12 / 12 www.ziehl.de...