Differential pressure transducer for use with hobo h22, u12, u30, ux120-006m, and rx3000 data loggers and hobo zw data nodes

Advertisement

Configuring the Data Logger for the Differential Pressure Transducer using HOBOware Software
HOBOware software provides configuration files for the transducers. The table below lists the recommended configuration values
that these files contain. For information on loading configuration files, refer to the software documentation.
Onset Part Nos.
Channel
Name
T-VER-PX3UL
Diff Pressure
Velocity
Notes:
Excitation power provided by the FlexSmart Analog Module (Onset Part No. S-FS-CVIA) with H22; by the Analog
Sensor Port/Module with U30 and RX3000; and by power adapter (Onset Part No. AC-SENS-1) with ZW, U12, or
UX120-006M.
Both differential pressure transducer models have switch-selectable ranges and scales, as listed.
Veris Differential Pressure Transducer Connection Instructions
Warm-Up
Measurement
Type
20 sec
Current
Voltage
20 sec
Current
Voltage
Raw
Raw
Raw
Value 1
Value 2
Units
4
20
mA
0
5 (or 10)
V
4
20
mA
0
5 (or 10)
V
Page 3 of 3
Scaled
Scaled
Scaled
Value 1
Value 2
Units
0
0.1 (or 0.25,
in WC
0.5, 1, 2.5,
5, or 10)
0
500, 1000,
ft/min
2000, 3000,
4000, 5000,
6000, or
7000