Installation; Instructions; Guidelines - Panduit PViQ PU 1 User Manual

Pviq networked pou
Table of Contents

Advertisement

Installation

Instructions

1. Using appropriate hardware, mount POU to rack.
2. Plug POU into de-energized receptacle
3. Connect devices into POU's output receptacles. Panduit recommends that the devices are turned
off until all devices are connected to POU.
4. Turn on branch circuit to energize POU.
5. Power on devices. Sequential power up is recommended to avoid high inrush current.

Guidelines

If the POU is installed in a cabinet the ambient temperature of the rack should be no greater than
45°C.
Install the POU such that the amount of airflow required for safe operation of equipment is not
compromised.
Mount the POU so that a hazardous condition is not achieved due to uneven mechanical loading.
Follow nameplate ratings when connecting equipment to the branch circuit.
consideration the effect that overloading of the circuits might have on over-current protection and
supply wiring.
The POU relies on the building installation for protection from over-current conditions. A certified
overcurrent protection device is required in the building installation. The overcurrent protection
device should be sized according to the POU's nameplate ratings and local/national electrical
codes.
Reliable earthing of rack-mount equipment should be maintained. Particular attention should be
given to supply connections other than direct connections to the branch circuit. The POU must
be connected to an earthed socket-outlet.
The POU is intended for Restricted Access Locations only and only qualified service personnel
should install and access the POU.
For pluggable equipment, install the POU so that the input plug or appliance coupler may be
disconnected for service.
Sequential power-up of devices powered by the POU is recommended to avoid high inrush
current.
Caution: Disconnect all power cords before servicing.
The POU is intended for use with TN, TT, or IT power supply systems
1
Branch Circuit should be sized based on the POU's nameplate electrical rating. For example a 24 Amp
rated PDU is intended for use on a 30 Amp Branch Circuit. For Global Units a 32 Amp rated PDU is
intended for use on a 32 Amp Branch Circuit.
6
1
.
Networked POU
Take into
Version 1.0