This equipment manual is only complete in conjunction with the product-related hardware and software user Completeness manuals required for the individual application. You can reach us at: Berghof Automation GmbH Harretstr. 1 72800 Eningen Germany T +49.7121.894-0 F +49.7121.894-100 e-mail: controls@berghof.com www.berghof.com Berghof Automation GmbH works in accordance with DIN EN ISO 9001:2000.
Page 3
Transition into new CD. New corporate name “Berghof Automation GmbH”. Update of chapter “Extension modules”. 1.10 03.05.2016 New EMC directive. Correction standards. Update of chapter “Chemical resistance”. Update of section “Nameplate”. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx...
The manual contains information about the following topics Areas of application Safety Mechanical construction Electrical construction Connections Commissioning Care and maintenance Decommissioning Disposal Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100106FE05.docx | DC1000_HB_en_2D0982010ZD00.docx...
Failure to observe the information indicated by this warning may result in injury or property damage. NOTICE No hazard Information indicated in this manner provides additional notes concerning the product. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100106FE05.docx...
Dialog Controller is employed are complied with. that the users always have available all relevant information they require with regard to the Dialog Controller and its employment. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100106FE05.docx | DC1000_HB_en_2D0982010ZD00.docx...
This can result in death, serious injury or extensive property damage. Only open the housing cover once the Dialog Controller has been safely dis- HAZARDOUS connected from the power supply. VOLTAGE Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100106FE05.docx...
All types of failure and the associated fuse systems are to be taken into ac- count at system level. The advice of the SPC manufacturer should be sought if necessary. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100106FE05.docx | DC1000_HB_en_2D0982010ZD00.docx...
With connected contact line system the compliance of the EMC requirements on the complete system must be checked and ensured („fixed installation“ for the purpose of the EMC directive). Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100106FE05.docx...
When installing the Dialog Controller, take particular care to ensure that the included seal profiles are not damaged. Also ensure compliance with the ambient conditions specified under “Technical specifications”. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100106FE05.docx | DC1000_HB_en_2D0982010ZD00.docx...
RS232 and an RS485 port. E-bus extension The Dialog-Controller’s I/O level can be expanded via the E-bus socket to include up to seven E-bus sub- scribers. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100107FE10.docx | DC1000_HB_en_2D0982010ZD00.docx...
Page 18
MMC/SD card slot The scope of supply of the controller module consists of: Scope of supply Dialog-Controller DC10xx incl. 2-pin plug-in connector for power supply Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100107FE10.docx...
Communication is the forte of the DC1000. Its spectrum of interfaces and exten- Prime Interface sion options makes is the reason for this. The DC1000 with a Prime interface is extremely adaptable. The maximum scope of the interfaces can be supplemented with further commu- nication an I/O extension cards.
DC1005M T grey Clean Basic 2.2.4. Variable thanks to extension cards The DC1000 can be fitted with a maximum of three extension cards. The spectrum encompasses pure I/O cards as well as communication cards, which are already installed by Berghof.
Keyboard Display Front FRONT Controller Grafik Flash +24 V BASIS 2VF100233DG01.cdr No potential isolation of the CAN and RS485 interface on the Basic Interface NOTICE version. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100107FE10.docx...
EN 61000-6-4, industrial environments Interference resistance EN 61000-6-2, industrial environments Protection class Insulating resistance EN 61131-2; DC 500 V test voltage Protection type IP20 (front: IP65) Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100107FE10.docx | DC1000_HB_en_2D0982010ZD00.docx...
Page 24
3 slots for 3 I/O modules or 2 I/O modules and one AnyBus module (Prime Interface only) Further features Yes, battery backed. Real-time clock SD card 1 SD card slot or RS232 (X5) (Prime Interface only) Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100107FE10.docx...
It must therefore be installed vertically and the upper and lower housing aper- tures must not be covered over! DANGER OF OVERHEATING AND FIRE! Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100107FE10.docx | DC1000_HB_en_2D0982010ZD00.docx...
EN 61000-6-4, industrial environments Interference resistance EN 61000-6-2, industrial environments Protection class Insulating resistance EN 61131-2; DC 500 V test voltage Protection type IP20 (front: IP65) Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100107FE10.docx...
Page 29
3 slots for 3 I/O modules or 2 I/O modules and one AnyBus module (Prime Interface only) Further features Yes, battery backed. Real-time clock SD card 1 SD card slot or RS232 (X5) (Prime Interface only) Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100107FE10.docx | DC1000_HB_en_2D0982010ZD00.docx...
It must therefore be installed vertically and the upper and lower housing aper- DANGER OF tures must not be covered over! OVERHEATING AND FIRE! Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100107FE10.docx...
EN 61000-6-4, industrial environments Interference resistance EN 61000-6-2, industrial environments Protection class Insulating resistance EN 61131-2; DC 500 V test voltage Protection type IP20 (front: IP65) Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100107FE10.docx | DC1000_HB_en_2D0982010ZD00.docx...
Page 34
3 slots for 3 I/O modules or 2 I/O modules and one AnyBus module (Prime Interface only) Further features Yes, battery backed. Real-time clock SD card 1 SD card slot or RS232 (X5) (Prime Interface only) Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100107FE10.docx...
It must therefore be installed vertically and the upper and lower housing aper- tures must not be covered over! DANGER OF OVERHEATING AND FIRE! Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100107FE10.docx | DC1000_HB_en_2D0982010ZD00.docx...
EN 61000-6-4, industrial environments Interference resistance EN 61000-6-2, industrial environments Protection class Insulating resistance EN 61131-2; DC 500 V test voltage Protection type IP20 (front: IP65) Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100107FE10.docx...
Page 39
3 slots for 3 I/O modules or 2 I/O modules and one AnyBus module Further features Yes, battery backed. Real-time clock SD card 1 SD card slot or RS232 (X5) Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100107FE10.docx | DC1000_HB_en_2D0982010ZD00.docx...
It must therefore be installed vertically and the upper and lower housing aper- DANGER OF tures must not be covered over! OVERHEATING AND FIRE! Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100107FE10.docx...
EN 61000-6-4, industrial environments Interference resistance EN 61000-6-2, industrial environments Protection class Insulating resistance EN 61131-2; DC 500 V test voltage Protection type IP20 (front: IP65) Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100107FE10.docx | DC1000_HB_en_2D0982010ZD00.docx...
Page 44
3 slots for 3 I/O modules or 2 I/O modules and one AnyBus module Further features Yes, battery backed. Real-time clock SD card 1 SD card slot or RS232 (X5) Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100107FE10.docx...
It must therefore be installed vertically and the upper and lower housing aper- tures must not be covered over! DANGER OF OVERHEATING AND FIRE! Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100107FE10.docx | DC1000_HB_en_2D0982010ZD00.docx...
(PE) with a copper cross-section of at least 1.5 mm². The Dialog-Controller is equipped with a 6.3 x 0.8 mm plug-in tab for this purpose. 2VF100236DG00.cdr Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100107FE10.docx...
The onboard 10/100 Base-T Ethernet adapter with an RJ45 connector is used to connect the unit to a net- work. The “LNK” and “RCV” status LEDs provide information regarding a successful network link. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100107FE10.docx | DC1000_HB_en_2D0982010ZD00.docx...
Based on the variety and number of available USB chip and USB drive manufactures, there is no guar- antee that every available USB drive on the market works with the device. Every USB drive has to be Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100107FE10.docx...
NC (Do not connect) CAN_L CAN_GND NC (Do not connect) Sub-D9 M NC (Do not connect) NC (Do not connect) CAN_H NC (Do not connect) NC (Do not connect) Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100107FE10.docx | DC1000_HB_en_2D0982010ZD00.docx...
NC (Do not connect) NC (Do not connect) Sub-D9 F NC (Do not connect) NC (Do not connect) NC (Do not connect) NC (Do not connect) Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100107FE10.docx...
Page 53
The interface is terminated “softly” in the Dialog-Controller at 500 Ω (older devices 5 kΩ ). A 120 Ω differen- tial terminating resistor can be activated for each S4 switch. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100107FE10.docx | DC1000_HB_en_2D0982010ZD00.docx...
Page 54
An attenuating connection, for example via 200 Ω at multi-ple points on the bus. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100107FE10.docx...
Always hold a lead by the plug when connecting or disconnecting a device. Never pull on the lead itself! The connection level for all external devices is located on the rear of the Dialog-Controller. All connections are plug-in. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100107FE10.docx | DC1000_HB_en_2D0982010ZD00.docx...
At present data memory cards with a memory capacity of up to 1 GB can be used. 2VF100312DG01.cdr If the SD card reader is activated, then the second RS232 interface (X5) is not NOTICE longer available. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100107FE10.docx...
Dialog-Controller. CP1131-P: PLC programming using CODESYS and Berghof Target Support Package CPC++: C programming directly on the LINUX operating system Status-LED Ethernet Status-LED 2VF100232DG00.cdr Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100108FE04.docx | DC1000_HB_en_2D0982010ZD00.docx...
Page 58
perform a controller reset; or alternatively: Mode selection switch / Service menu / CODESYS/ web browser return the controller to operation Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100108FE04.docx...
Up to two lines reflecting the current PLC status can be displayed. Line 1 will always be visible, while line 2 will only appear when an error occurs. Parameter window PLC window 2VF100273DG01.cdr Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100108FE04.docx | DC1000_HB_en_2D0982010ZD00.docx...
Info to display the hardware and software version levels as well as diagnostic data; and it also offers the save function (USB, SD, Flash). Display to adjust contrast values. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100108FE04.docx...
New settings will only take effect after a restart! The “EXIT” button allows you to leave the menu without saving any changes which may have been made. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100108FE04.docx | DC1000_HB_en_2D0982010ZD00.docx...
Page 62
The “EXIT” button allows you to leave the menu without saving any changes which may have been made. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100108FE04.docx...
Page 63
PPP: TCP/IP over PPP protocol PG Tool: CODESYS can upload and debug serial pro- grams CNW: reserved RTC: Setting the battery-buffered realtime clock. CLOCK “RTC” Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100108FE04.docx | DC1000_HB_en_2D0982010ZD00.docx...
Acknowledgement of the RESET COLD command. As soon as the “CONTINUE” button is pressed the PLC program and all variables, including the RETAIN variab- les, are reset. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100108FE04.docx...
PLC program usb0: the first USB to be plugged in (a maximum of 8 sticks can be plugged in via a USB hub). Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100108FE04.docx | DC1000_HB_en_2D0982010ZD00.docx...
(although such changes will remain in effect until the next restart). Dialog-Controllers with monochrome displays: The contrast can be adjusted here. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100108FE04.docx...
PLC ERROR STOP Operating mode selection switch S1 is set to the RUN position. However, the PLC program could not be started due to an error. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100108FE04.docx | DC1000_HB_en_2D0982010ZD00.docx...
Page 68
E-bus modu- les. Once the number of actually available E-bus modules agrees with the controller configuration setting, the controller can be restarted using a reset command. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100108FE04.docx...
Page 69
“Reboot” button. Note: The diagnostic data must definitely be saved prior to re- booting because only at this time can all the important data be saved! Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100108FE04.docx | DC1000_HB_en_2D0982010ZD00.docx...
All electronic components such as PCBs, drives, etc. must be set aside and disposed of separately. Disposal is generally regulated by national and local ordinances which must be complied with. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100108FE04.docx...
The Dialog-Controller fails to Memory fault. Return the device for service. completely boot. Corrupted software. Put the device in the configuration mode and reload the firmware. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100108FE04.docx | DC1000_HB_en_2D0982010ZD00.docx...
Connection for a 5-place 7-segment display with remote control receiver The scope of supply of the control module consists of: Scope of supply I/O card installed in the Dialog-Controller Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100124FE08.docx...
4 (X2) Output current 0.5 A Short circuit protection Potential isolation Connection technique Standing front wiring for 3.81 terminal strips (not part of the standard deli- very) Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100124FE08.docx | DC1000_HB_en_2D0982010ZD00.docx...
Page 76
Standing front wiring for 3.81 terminal strips (not part of the standard deli- very) Operating and display elements Display elements Interface (X11) for 5-place, 7-segment display with IR receiver diode for remote control Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100124FE08.docx...
8 A (depending on the number of I/Os). External power supply The CAN communications interface is supplied from the Dialog-Controller’s power supply. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100124FE08.docx | DC1000_HB_en_2D0982010ZD00.docx...
Page 78
USER MANUAL 1.10 | DC1000 DIALOG-CONTROLLER The I/O card is factory installed and may only be installed in the Dialog-Controller in the position shown in Installation the figure below. 2VF100306DG00.cdr Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100124FE08.docx...
Page 79
SC_CAN. Termination The SC_CAN must be terminated at both line ends. The values for these terminating resistors deviate from the ISO 11898 (CAN bus) standard and they can be ordered separately from Berghof (CTR-SC-T2, part no.: 201601200). CAUTION If the SC_CAN bus is incorrectly terminated, its operation can result in...
Page 80
External 7-segment display the I/O subassembly. Connection is to connector X11 by means of a cable available from Berghof. The exter- nal display can be addressed from the software in the same way as the digital I/Os. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com...
The maximum value will be indicated if no sensor is connected to an analog input. NOTICE Shield support in switchgear cabinet is urgently recommended for rea- sons of EMC! Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100124FE08.docx | DC1000_HB_en_2D0982010ZD00.docx...
(filtering) can be activated in individual groups of 32 inputs. This function is only available for C applications. The sampling rate is prede- NOTICE fined under IEC 61131-3. Basic input circuit diagram 2VF100009DG01.cdr Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100124FE08.docx | DC1000_HB_en_2D0982010ZD00.docx...
Page 84
Potential isolation Yes (optocoupler) in groups Status indicator None Alarms Definable depending on the software Input delay Definable via the software Input capacitance < 10 nF Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100124FE08.docx...
Page 85
Limits for “0” signal for the “OFF” condition 5.5 V Upper voltage limit max. 1.5 mA Upper current limit max. Lower voltage limit min. 0 mA Lower current limit min. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100124FE08.docx | DC1000_HB_en_2D0982010ZD00.docx...
The LED is on when the associated output is activated, that is, when it is logical “1” (HIGH). Basic output circuit diagram 2VF100011DG01.cdr Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100124FE08.docx...
Page 87
Prohibited Insulation resistance Reference voltage 0 V < U < 50 V Test voltage up to an altitude of 2000 m DC 500 V Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100124FE08.docx | DC1000_HB_en_2D0982010ZD00.docx...
Page 88
Therefore, this state should be avoided! The output will again be operational once the overload has been corrected and the unit has cooled down. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100124FE08.docx...
Digital OUT +24 V OUT4 Digital OUT +24 V OUT5 Digital OUT +24 V OUT6 Digital OUT +24 V OUT7 Digital OUT +24 V OUT8 Digital OUT +24 V Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100124FE08.docx | DC1000_HB_en_2D0982010ZD00.docx...
Page 90
Encoder 2 IN 3 (X1) IN 4 (X1) The encoder values are only reset (0) when the unit is switched on or rebooted after a reset. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100124FE08.docx...
The PROFIBUS-MASTER communications interface is supplied from the Dialog-Controller's power supply. Installation The PROFIBUS-MASTER card is factory installed and may only be installed in the Dialog-Controller in the position shown in the figure below. 2VF100309DG00.cdr Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100124FE08.docx | DC1000_HB_en_2D0982010ZD00.docx...
Page 94
RS232 signal RS232 signal N.C. Do not connect Bus ground N.C. Do not connect N.C. Do not connect N.C. Do not connect N.C. Do not connect Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100124FE08.docx...
Page 95
The baud rate is set in the CODESYS controller configuration. GSD file The PROFIBUS-MASTER module is integrated in the CODESYS controller configuration with a GSD file. As of Version 1.10.0, this GSD file will be part of the Berghof Target installation package. Indicator LEDs Indica-...
All required DP services as well as user parameter data and device-specific diagnostics The scope of supply consists of: Scope of supply PROFIBUS-SLAVE card installed in the Dialog-Controller Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100124FE08.docx...
The PROFIBUS-SLAVE communications interface is supplied from the Dialog-Controller's power supply. Installation The PROFIBUS-SLAVE card is factory installed and may only be installed in the Dialog-Controller in the po- sition shown in the figure below. 2VF100311DG00.cdr Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100124FE08.docx...
Page 99
GSD file The PROFIBUS-SLAVE module is integrated in the CODESYS controller configuration with a GSD file. As of Version 1.10.0, this GSD file will be part of the Berghof Target installation package. Indicator LEDs Four diagnostic LEDs indicate the current operating state and any error messages.
Page 100
Red, flashing at 2 Hz: Missing user parameter; initialized data length does not match configuration Red, flashing at 4 Hz: Initialization error in the ASIC Off: No diagnostic data available Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100124FE08.docx...
The PROFIBUS card is factory installed and may only be installed in the Dialog-Controller in the position shown in the figure below. State Reset Profibus T ermination DC Profibus-DPV 2VF100405DG00.cdr Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100124FE08.docx | DC1000_HB_en_2D0982010ZD00.docx...
Page 104
DPSlave.gsd: GSD file for the PROFIBUS Master which can access the card configured as a PROFIBUS Slave All application and diagnostic data are set up via the CODESYS controller con- NOTICE figuration or are provided by the application. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100124FE08.docx...
Page 105
DP Slave not yet correctly addressed by DP Master Green 4x flashing Watchdog error If the watchdog is active the connection to the Master has been lost. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100124FE08.docx | DC1000_HB_en_2D0982010ZD00.docx...
The digital inputs (X2) can also be used as counters. 2VF100468DG00.cdr The scope of supply of the controller module consists of: Scope of supply max. 3 XR I/O cards installed in the Dialog-Controller Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100124FE08.docx...
4 analog ±10 V or ±20 mA inputs/outputs Resolution Min. 16 bit Connection technique Standing front wiring for terminal strips (not part of the scope of supply) Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100124FE08.docx | DC1000_HB_en_2D0982010ZD00.docx...
“IO_VALID” does not become valid again until the controller has been restart- ed. Therefore, it is necessary to constantly monitor “IO_VALID” in the PLC pro- gram. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100124FE08.docx...
Makes it easier to connect the shield or GND line 15420 BL-I/O 3.5/10F SW Without LED for analog channels (X3 and X4) Single-wire connection Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100124FE08.docx | DC1000_HB_en_2D0982010ZD00.docx...
The inputs are transferred internally to the core of the CPU in cycles. An open input is inter- preted as static 0 (LOW). Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100124FE08.docx...
Page 111
If there is a risk of lightning impact, please consult the manufacturer. Load nominal voltage L+ DC 24 V (SELV) Polarity reversal protection Potential isolation Status display Yes, green LED per input on the plug-in connector. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100124FE08.docx | DC1000_HB_en_2D0982010ZD00.docx...
Page 112
Limits for “0” signal for the “OFF” condition 5.0 V Upper voltage limit max. 0.8 mA Upper current limit max. Lower voltage limit min. 0 mA Lower current limit min. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100124FE08.docx...
Page 113
If thermal loads occur owing to energetic recovery L(SCr) or fast de-excitation, the overload protection may react prematurely even in the case of outputs which are not involved. off(SC) 2VF100392DG01.cdr Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100124FE08.docx | DC1000_HB_en_2D0982010ZD00.docx...
Page 114
The output stage is protected against overload, which must be taken into ac- count for high inrush currents from lamps, for example. Principal output circuit diagram, positive-switching + 24 V OUT (IN) 2VF100465DG00.cdr Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100124FE08.docx...
Page 115
0.5 A Total current of all outputs max. 2 A Two outputs switched in parallel for logic link permissible for increased output permissible up to 1 A Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100124FE08.docx | DC1000_HB_en_2D0982010ZD00.docx...
Digital IN +24 V Counter input +24 V Encoder 4 A/up IN16 Digital IN +24 V Counter input +24 V Encoder 4 B/down GND I/O supply Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100124FE08.docx...
Voltage transmitter Connector AO-U ±10 V AO-U AO-U AO-U AO-U AO-U4 ±10 V AO-U4 AO-U4 AO-U4 AO-U4 Current transmitter Connector AO-I ±20 mA AO-I AO-I AO-I AO-I Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100124FE08.docx | DC1000_HB_en_2D0982010ZD00.docx...
Page 118
Filter rate and If the scanning rate is above 1 ms the digital filtering ensures constant value scanning rate curves instead of delivering the same value repeatedly. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100124FE08.docx...
Page 119
60 dB (direct current); 20 dB at 50 Hz Dynamic characteristics Greatest temporary differential 1.5 % of the measuring range during electrical interference test in compliance with IEC 61131-2 Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100124FE08.docx | DC1000_HB_en_2D0982010ZD00.docx...
Page 120
USER MANUAL 1.10 | DC1000 DIALOG-CONTROLLER Typical example of external connections 2VF100469DG02.cdr CAUTION The module is damaged at input voltages of more than ±14 V. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100124FE08.docx...
Page 121
Dynamic characteristics (refer also to Dynamic characteristics of the analog inputs) Greatest temporary differential 1.5 % of the measuring range during electrical interference test in compliance with IEC 61131-2 Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100124FE08.docx | DC1000_HB_en_2D0982010ZD00.docx...
Page 122
Calibration to maintain the 12 months accuracy class Greatest temporary differential ±1.5 % of the measuring range during electrical interference test in compliance with IEC 61131-2 Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100124FE08.docx...
Page 123
> 500 Ω Load impedance range Overload protection Short-circuit proof. Current limitation at around 24 mA. Interruption for 300 ms. Cyclical reattempt. Typical example of external connections 2VF100471DG00.cdr Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100124FE08.docx | DC1000_HB_en_2D0982010ZD00.docx...
Page 124
A+ to A- > 300 kΩ During booting routine The analog output is not yet active during the booting routine of the DC1000. of the DC1000 Differences to zero value when switched on and off is around < 2 %.
Page 125
32 bit Real (24 bit payload) program General characteristics Permissible load types Load to AGND Greatest inductive load 0.1 mH 0…500 Ω Load impedance range Typical example of external connections 2VF100472DG00.cdr Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100124FE08.docx | DC1000_HB_en_2D0982010ZD00.docx...
Page 126
The voltage between A+ and A- can be displayed if the analog input is confi-gured as AI-U. A- must be connected to AGND for the sensor to be monitored. Readjustment is not required because it is readjusted internally. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100124FE08.docx...
All connections are correct and secure; The ground wire (PE) is properly connected. NOTICE Be sure all covers on the Dialog-Controller are closed before returning the unit to service! Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100109FE04.docx | DC1000_HB_en_2D0982010ZD00.docx...
Replace batteries only with batteries which have the same rating! EXPLOSION HAZARD Make sure the battery is facing the right way when installed. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100109FE04.docx...
Push the old battery out to the side, can be accessed from above. Insert the new battery from the side. Check for correct polarity and battery type. 2VF100269DG03.cdr Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100109FE04.docx | DC1000_HB_en_2D0982010ZD00.docx...
Low humidity (< 10 % rel.H.): 85 °C Outdoor use As is the case for all polyester-based sheeting, AUTOTEX is not intended for extended exposure to direct sunlight. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100123FE04.docx | DC1000_HB_en_2D0982010ZD00.docx...
Ketchup Lemon juice 6.3.3. Outdoor use As is the case for all polyester-based sheeting, AUTOTEX is not intended for extended exposure to direct sunlight. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100123FE04.docx | DC1000_HB_en_2D0982010ZD00.docx...
FTL, refer to free-type license (FTL) When required, the source code for the free software can be requested from Berghof within three years after delivery at cost price. The exact address for this: Berghof Automation GmbH Harretstrasse 1 72800 Eningen (Germany) The licenses used by Berghof are listed in the ‘Copyright and software licens-...
Sold under statutory warranty conditions. Warranty lapses in the event of unauthorised attempts to repair the equipment and/or product, or in the event of any other form of intervention. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com 2VF100055FE06.docx | DC1000_HB_en_2D0982010ZD00.docx...
Identification no. (item no. + serial no.) Customer no. Supply voltage Manufacturer’s address Mac addresses Production date QR code (identification no.) CE marking Brand of the manufacturer (trademark) Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100055FE06.docx...
Page 142
CiA users' or- ganisation. Notice: Our Technical Support team will be glad to provide other literature references on request. Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com DC1000_HB_en_2D0982010ZD00.docx | 2VF100055FE06.docx...