Emerson Fisher Y692VB Series Instruction Manual
Emerson Fisher Y692VB Series Instruction Manual

Emerson Fisher Y692VB Series Instruction Manual

Vacuum breakers

Advertisement

Quick Links

Instruction Manual
Form 5479
January 2010
Y692VB Series Vacuum Breakers
Introduction
Scope of the Manual
This manual provides instructions and a parts list
for Types Y692VB and Y692VBM vacuum breakers.
Instructions and parts lists for other equipment used
with these breakers are found in separate manuals.

Product Description

The Y692VB Series vacuum breakers are used for
precise control of small capacity, low-pressure service
applications where an increase in vacuum must be
limited. These direct-operated vacuum breakers come
in NPS 1-1/2 and 2 (DN 40 and 50) body sizes and
have a 3/4 or 1-3/16-inch (19 or 30 mm) orifice and
a 3/4-inch (19 mm) spring case vent connection with
optional umbrella vent assembly. The products are
described as follows:
Type Y692VB—Type Y692VB has internal pressure
registration, so it does not require a control line.
Type Y692VBM—Type Y692VBM has a control line
connection and an O-ring stem seal to block the throat
for external pressure registration.

Specifications

Some general ratings and specifications for the
Y692VB Series vacuum breakers are given on page 2.
Individual vacuum breakers come from the factory with
the specific data stamped on the nameplate.
Installation
WARNING
!
Personal injury, property damage,
equipment damage, or leakage due to
escaping gas or bursting of pressure-
containing parts may result if this
W7429
Figure 1. Type Y692VB Vacuum Breaker
equipment is overpressured or is
installed where service conditions
could exceed the limits given in the
Specifications, or where conditions
exceed any ratings of the adjacent
piping or piping connections. To
avoid such injury or damage, provide
pressure-relieving or pressure-limiting
devices (as required by the appropriate
code, regulation, or standard) to prevent
service conditions from exceeding
those limits. Additionally, physical
damage to this equipment could cause
personal injury or property damage due
to escaping gas. To avoid such injury or
damage, install the equipment in a safe
and well-ventilated location.
Equipment operation within ratings does not preclude
the possibility of damage from debris in the lines
or from external sources. This equipment should
be inspected for damage periodically and after any
overpressure condition.
www.fisherregulators.com
Y692VB Series

Advertisement

Table of Contents
loading

Summary of Contents for Emerson Fisher Y692VB Series

  • Page 1: Product Description

    Y692VB Series Instruction Manual Form 5479 January 2010 Y692VB Series Vacuum Breakers Introduction Scope of the Manual This manual provides instructions and a parts list for Types Y692VB and Y692VBM vacuum breakers. Instructions and parts lists for other equipment used with these breakers are found in separate manuals.
  • Page 2 Y692VB Series Specifications Body Sizes Spring Case Connection NPS 1-1/2 or 2 (DN 40 or 50) 3/4 NPT End Connection Styles Type Y692VB Gauge Tap Connection See Table 1 1/4 NPT Maximum Allowable Inlet (Positive) Pressure Type Y692VBM Control Line Connection and Orifice Sizes 1/2 NPT 3/4-inch (19 mm) Orifice: 30 psig (2,1 bar)
  • Page 3: Principle Of Operation

    Y692VB Series Type Y692VB Type Y692VB VACUUM PUMP VACUUM VACUUM PUMP BEING LIMITED VACUUM BEING LIMITED UNION NUT TYPE Y692VB VACUUM BREAKER INLET PRESSURE B2579 CONTROL PRESSURE (VACUUM) POSITIVE PRESSURE, ATMOSPHERE, INLET PRESSURE INLET PRESSURE ATMOSPHERIC PRESSURE OR A LESSER VACUUM THAN THE CONTROL PRESSURE (VACUUM) CONTROL PRESSURE (VACUUM) VACUUM BEING LIMITED...
  • Page 4: Maintenance

    Y692VB Series between the equipment and the downstream shut-off 5. Install the disk holder assembly (key 25). Use the valve nearest to it. All pressure between these shut-off cotter pin (key 14) to secure it to the valve stem valves is released through the open vent valve. (key 13).
  • Page 5: Parts Ordering

    Y692VB Series 7. Install the lever assembly (key 9) into the valve 4. To replace the lever assembly (key 9), remove the stem (key 13) and secure the lever assembly machine screws (key 11). (key 9) with the machine screws (key 11). 5.
  • Page 6: Parts List

    Y692VB Series A7178 Figure 3. Y692VB Series Assembly Table 3. Body Materials and Part Numbers (Key 28) MATERIAL BODY SIZE AND END CONNECTION STYLE Cast Iron WCB Steel WCB Steel (NACE) CF8M Stainless Steel 1B403619012 2L244522012 - - - - 2L244533092 - - - - 2E2291X0012...
  • Page 7 Y692VB Series A7179 Figure 4. Type Y692VBM O-Ring Stem Seal Detail Description Part Number Description Part Number Machine Screw (2 Required) Hex Nut (12 required) Standard 1A866935032 Standard 1A309324122 NACE 1A8669X0012 NACE 1A309338992 Valve Stem Spring Case Standard 1E767635032 Cast iron 2B155719042 NACE 1E7676X0012...
  • Page 8 For further information visit www.fisherregulators.com The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls, Inc., a business of Emerson Process Management.

This manual is also suitable for:

Fisher y692vbmFisher y692vb

Table of Contents